Conductive Level Controller - OMRON Industrial Automation

New Product
Conductive Level Controller
K8AK-LS
Ideal for Liquid Level Control in
Industrial Facilities and Equipment.
• Self-holding circuit implemented with circuit processing that is
not depending on external wiring.
• Switch between water supply and discharge with a DIP switch
setting.
• Sensitivity adjustment of operating resistance from 10 to 100 kΩ
for application to a wide range of liquids.
• Prevents chattering of relay contacts that occurs with ripples.
• Easy wiring with ferrules.
• Use 2 × 2.5 mm2 solid wire or 2 × 1.5 mm2 ferrules.
• Applicable as a floatless switch.
Refer to Safety Precautions on page 7.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Ordering Information
Power supply voltage
24 VAC/DC
100 to 240 VAC
Model
K8AK-LS1 24 VAC/DC
K8AK-LS1 100−240 VAC
Accessories (Order Separately)
●Electrode Holders/Underwater Electrodes
For general-purFor areas with
Application pose use, such as
limited space
water supply lines
Model
PS-3S/-4S/-5S
PS-31
SUS304, 300 mm
When mounting
For liquids with
strength is relow resistance
quired
BF-1
BF-3/-5
For resistance to
For installation at
high-temperature For resistance
long distances
or high-pressure against corrosion
from the liquid level
liquids
BS-1
BS-1T
PH-1/-2
PH-2
SUS
Appearance
Hastelloy
titanium
PH-1
●Electrode Rods
Electrode Rods are available in sets with the connection nuts, lock nuts, and tightening screws.
Application
Purified water service, industrial water, and sewage
Model
F03-60 SUS304
Purified water service, industrial water, sewage, and weak
alkaline solutions
F03-60 SUS316
●Others
Item
Model
Protective Cover
(Electrode Holders for the PS
or BF Series)
F03-11
Mounting Piece
(Electrode Holder for the PS Series)
F03-12
Separator (to prevent contact between electrodes)
F03-14 1P (one pole)
F03-14 3P (three poles)
F03-14 5P (five poles)
1
K8AK-LS
Ratings and Specifications
Ratings
24 VAC 50/60 Hz or 24 VDC
100 to 240 VAC 50/60 Hz
Operating voltage
range
85% to 110% of rated voltage
Voltage across electrodes
5 V p-p (Approx. 20 Hz)
24 VAC/DC: 2.0 VA/1.1 W max.
100 to 240 VAC: 4.6 VA max.
Installation environment
Installation category II, pollution level 2
Power consumption
Approved standards
EN 61010-1
Operating resistance
10 to 100 kΩ (variable)
EMC
EN 61326-1 Industrial electromagnetic environment
Reset resistance
250 kΩ max.
Response time
Approx. 0.1 to 10 s (variable)
Safety standards
Length of cable
100 m max. (fully insulated 3-core 0.75-mm2 cabtyre cable, 600 V)
UL 508 (Recognition),
Korean Radio Waves Act (Act 10564),
CSA: C22.2 No.14, CCC: GB14048.5
Indicators
PWR: Green, RY: Yellow
Output contact ratings
Rated load
Resistive load
5 A at 250 VAC
5 A at 30 VDC
Maximum switching capacity: 1,250 VA, 150 W
Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life:
5 A at 250 VAC or 30 VDC: 50,000 operations
3 A at 250 VAC/30 VDC: 100,000 operations
Power supply voltage
2
Specifications
Ambient operating
temperature
−20 to 60°C (with no condensation or icing)
Storage temperature
−25 to 65°C (with no condensation or icing)
Ambient humidity
25% to 85% (with no condensation)
Storage humidity
25% to 85% (with no condensation)
Altitude
2,000 m max.
Terminal screw
tightening torque
0.49 to 0.59 N·m
Case color
N1.5
Case material
PC and ABS, UL 94 V-0
Weight
Approx. 150 g
Mounting
Mounts to DIN Track.
Dimensions
22.5 × 90 × 100 mm (W×D×H)
20 MΩ min.
Between all external terminals and the case
Between all power supply terminals and all input
terminals
Insulation resistance
Between all power supply terminals and all output
terminals
Between all input terminals and all output terminals
Dielectric strength
2,000 VAC for 1 min
Between all external terminals and the case
Between all power supply terminals and all input
terminals
Between all power supply terminals and all output
terminals
Between all input terminals and all output terminals
Noise immunity
1,500 V power supply terminal common/normal
mode
Square-wave noise of ±1-μs/100-ns pulse width with
1-ns rise time
Vibration resistance
Frequency: 10 to 55 Hz, acceleration 50 m/s2
10 sweeps of 5 min each in X,Y, and Z directions
Shock resistance
100 m/s2, 3 times each in 6 directions along 3 axes
Degree of protection
Terminals: IP20
K8AK-LS
Connections
Terminal Diagram
K8AK-LS1 100-240VAC
A
B
Relay Output
Control Output
11
14
12
Common
Relay output
250 VAC, 5 A (resistive load)
30 VDC, 5 A (resistive load)
11
A Water Level Inputs
14
12
E1
E2
LS1
E3
E1
E3
Water or
other liquid
B Power Supply Voltage
100 to 240 VAC
A1
E2
24 VAC/DC
A2
A1
A2
A1
A2
(No polarity)
Note: 1. Do not connect anything to terminals that are shaded in gray.
2. Use the recommended ferrules if you use twisted wires.
Wiring Example
L1
Three-phase
power supply
L2
L3
11
12
14
E1
E2
E3
Power supply
AC/DC
Motor
Power
supply voltage
A2
A1
Pump
A1
A2
Water or
other liquid
Source of liquid
Pump motor protection mechanisms have been omitted.
3
K8AK-LS
Timing Charts
●DIP Switch Pin 1: OFF (Automatic Liquid
Supply Operation)
●DIP Switch Pin 1: ON (Automatic Liquid
Discharge Operation)
Power supply voltage A1-A2
Power supply voltage A1-A2
Electrode terminals E2-E3
Electrode terminals E2-E3
Electrode terminals E1-E3
Electrode terminals E1-E3
Control output terminals 11-14
(operation indication)
Control output terminals 11-14
(operation indication)
P
OFF (stop)
ON (start)
Operation indicator OFF
E1
Operation indicator ON
E2
E3
• When the liquid level falls to E2 (indicator turns ON), the pump starts.
When the liquid level rises above E1 (indicator turns OFF), the pump stops.
4
Operation indicator ON
E1
ON (start)
Operation indicator OFF
E2
P
E3
OFF (stop)
• When the liquid level reaches E1 (indicator turns ON), the pump starts.
When the liquid level falls below E2 (indicator turns OFF), the pump stops.
K8AK-LS
Nomenclature
Front Panel
●Indicators
Item
Description
Lit when power is being supPower indicator (PWR: Green)
plied.
Relay status indicator (RY: Yellow) Lit when contacts are operating.
Terminal block
(See notes 1 and 2.)
Operating resistance knob
●Setting Knobs
Power indicator
Operating time knob
Item
Relay status indicator
Operating resistance knob
Operating time knob
Description
Used to set the resistance to 10
to 100 kΩ.
Used to set the operating time
to 0.1 to 10 s.
Note: 1. Use solid-core wires of 2.5-mm2 max. or ferrules with an
insulation sleeve to wire to this terminal.
To ensure the dielectric strength of the connection, do not
expose more than 8 mm of wire for insertion into the
terminal.
Terminal block
(See notes 1 and 2.)
For a solid wire
of 2.5-mm2 of max.
8 mm max.
For ferrules with
an insulation sleeve.
8 mm max.
Recommended ferrules
Phoenix Contact
• Al 1,5-8BK (for AWG16)
• Al 1-8RD (for AWG18)
• Al 0,75-8GY (for AWG18)
2. Screw tightening torque: 0.49 to 0.59 N·m
Operation Method
DIP Switch Settings
The operating mode is set using the DIP switch located at the
bottom of the Unit. The K8AK-LS does not have SW2.
OFF
ON
SW2
SW1
DIP switch pins
●DIP Switch Function
Pin
OFF ● ↑
OFF
ON ❍ ↓
ON
Automatic liquid supply operation
Operating mode Automatic liquid discharge operation
1
●
❍
2
Not
used.
Note: All pins are set to OFF by default.
5
K8AK-LS
Dimensions
(Unit: mm)
Conductive Level Controller
K8AK-LS
22.5
90
100
(5)
72
Optional Parts for DIN Track Mounting
●DIN Tracks
PFP-100N
PFP-50N
7.3±0.15
4.5
35±0.3
15
25
10
25
25
1,000 (500)*
10
25
15 (5)*
27±0.15
1
*Dimensions in parentheses are for the PFP-50N.
6
K8AK-LS
Safety Precautions
Be sure to read the precautions for all models in the website at the following URL: http://www.ia.omron.com/.
Warning Indications
CAUTION
Indicates a potentially hazardous situation
which, if not avoided, may result in minor or
moderate injury or in property damage.
Precautions for Safe
Use
Supplementary comments on what to do or
avoid doing, to use the product safely.
Precautions for
Correct Use
Supplementary comments on what to do or
avoid doing, to prevent failure to operate,
malfunction, or undesirable effects on
product performance.
Meaning of Product Safety Symbols
CAUTION
Electrical shock may cause minor injury.
Do not touch terminals while electricity is being supplied.
There is a risk of minor electrical shock, fire, or device failure.
Do not allow any pieces of metal, conductors, or cutting chips
that occur during the installation process to enter the product.
Explosions may cause minor injuries. Do not use the product
in locations with inflammable or explosive gases.
Used to warn of the risk of electric shock under
specific conditions.
There is a risk of minor electrical shock, fire, or device failure.
Do not disassemble, modify, repair, or touch the inside of the
product.
Used for general prohibitions for which there is no
specific symbol.
Loose screws may cause fires. Tighten terminal screws to the
specified torque of 0.49 to 0.59 N·m.
Used to indicate prohibition when there is a risk of
minor injury from electrical shock or other source if
the product is disassembled.
Used for general mandatory action precautions for
which there is no specified symbol.
Use of excessive torque may damage the terminal screws.
Tighten terminal screws to the specified torque of 0.49 to
0.59 N·m.
Use of the product beyond its life may result in contact welding
or burning. Make sure to consider the actual operating
conditions and use the product within its rated load and
electrical life count. The life of the output relay varies
significantly with the switching capacity and switching
conditions.
7
K8AK-LS
Precautions for Safe Use
1. Do not use or store the product in the following locations.
• Locations subject to water or oil
• Outdoor locations or under direct sunlight
• Locations subject to dust or corrosive gases (particularly
sulfurizing gases, ammonia, etc.)
• Locations subject to rapid temperature changes
• Locations prone to icing and dew condensation
• Locations subject to excessive vibration or shock
• Locations subject to wind and rain
• Locations subject to static electricity and noise
Precautions for Correct Use
Observe the following operating
methods to prevent failure and
malfunction.
1. Use the power supply voltage, input power, and other power
supplies and converters with suitable capacities and rated
outputs.
2. Use a precision screwdriver or similar tool to adjust the setting
knobs.
3. When cleaning the product, do not use thinners or solvents. Use
commercial alcohol.
• Habitats of insects or small animals
2. Use and store the product in a location where the ambient
temperature and humidity are within the specified ranges. If
applicable, provide forced cooling.
3. Mount the product in the correct direction.
4. Check terminal polarity when wiring and wire all connections
correctly. The power supply terminals do not have polarity.
5. Do not wire the input and output terminals incorrectly.
6. Make sure the power supply voltage and loads are within the
specifications and ratings for the product.
7. Make sure the crimp terminals for wiring are of the specified size.
8. Do not connect anything to terminals that are not being used.
9. Use a power supply that will reach the rated voltage within 1
second after the power is turned ON.
10.Keep wiring separate from high voltages and power lines that
draw large currents.
Do not place product wiring in parallel with or in the same path as
high-voltage or high-current lines.
11.Do not install the product near equipment that generates high
frequencies or surges.
12.The product may cause incoming radio wave interference. Do not
use the product near radio wave receivers.
13.Install an external switch or circuit breaker and label it clearly so
that the operator can quickly turn OFF the power supply.
14.Make sure the indicators operate correctly. Depending on the
application environment, the indicators may deteriorate
prematurely and become difficult to see.
15.The terminal blocks may heat up to 65°C. Use care when
handling them.
16.Do not use the product if it is accidentally dropped. The internal
components may be damaged.
17.Be sure you understand the contents of this catalog and handle
the product according to the instructions provided.
18.Do not install the product in any way that would place a load on it.
19.When discarding the product, properly dispose of it as industrial
waste.
20.When using the product, remember that the power supply
terminals carry a high voltage.
21.The product must be handled only by trained electrician.
22.Prior to operation, check the wiring before you supply power to
the product.
23.Do not install the product immediately next to heat sources.
24.Perform periodic maintenance.
Correct Mounting Direction, Mounting,
and Removing
• Mounting to DIN Track
1. Attach the product to the DIN Track with the tab at the top and
the hooks at the bottom.
2. Push the product onto the Track until the hooks lock into place.
A
B
• Removing from the DIN Track
Pull down on the bottom hook with a flat-blade screwdriver and lift
up on the product.
Applicable DIN Tracks:
PFP-100N (100 cm)
PFP-50N (50 cm)
Adjusting the Setting Knobs
• Use a screwdriver to adjust the setting knobs. The knobs have a
stopper that prevents them from turning beyond the full right or left
position. Do not force a knob beyond these points.
Setting knob
8
MEMO
9
MEMO
10
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg,
IL 60173-5302 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2014 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
CSM_4_2_0715
Cat. No. N188-E1-01
0513
0314 (0314)