EPS10EXP Explosion Proof Alarm Pressure Switch

INSTALLATION AND MAINTENANCE INSTRUCTIONS
EPS10EXP Explosion Proof
Alarm Pressure Switch
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Specifications
Contact Ratings:
10 A, 1/2 HP @ 125/250 VAC
2.5 A @ 6/12/24 VDC
Operating Temperature Range:
–40° F to +160°F
Maximum Service Pressure:
250 PSI
Maximum Adjustment Range:
4 – 20 PSI
Enclosure Rating:
NEMA Type 4 — Indoor or/Outdoor Use
Hazardous Atmospheres Classification: Class I, Groups B, C, D, Div. 1
Class II, Groups E, F, G, Div. 1
Class III, Div. 1
Approximate Differential:
3 PSI throughout range
Important
Please Read Carefully and Save
This instruction manual contains important information
about the installation and operation of alarm pressure
switches. Purchasers who install switches for use by others
must leave this manual or a copy of it with the user.
WARNING
To prevent ignition of hazardous atmospheres, disconnect
circuits before removing cover. Keep cover closed while circuits are live. Conduit runs must have sealing fittings connected within 18” of the enclosure.
Installation
1. Back out cover tamper set screw and remove cover (Fig. 1).
2. Mounting the Switch
The device is designed to be mounted in the upright or
horizontal position; side mounting is also acceptable.
Read all instructions carefully before installation, following
only those instructions that apply to the model you are
installing.
Before installing any alarm device, be thoroughly familiar
with:
NFPA 72:
Installation, Maintenance, and Use of
Protective Signaling Systems
NFPA 13:
Installation of Sprinkler Systems
Figure 1. Pressure switch basic dimensions:
4.9"
Other applicable NFPA standards, local codes, and the
requirements of the authority having jurisdiction.
HEX ADJUST
SCREW
1/4" HEX HEAD
COVER
Failure to follow these directions may result in failure of the
device to report an alarm condition. System Sensor is not
responsible for devices that have been improperly installed,
tested, or maintained.
COVER
TAMPER
SET SCREW
(WRENCH
PROVIDED)
ADJUSTMENT
WHEEL
9.5"
COVER
(WRENCH
PROVIDED)
Operation
As pressure changes, a diaphragm actuates 2 snap action
switches. The pressure switch actuation is determined by
adjustment settings.
LOCKING
SCREW
MAIN ADJUSTMENT
WHEEL (TURN
COUNTERCLOSKWISE
TO INCREASE
PRESSURE)
1/2" NPT
D770-25-00
1
I56-1427-001R
Figure 2. Typical piping diagram for EPS10EXP
EPS10EXP
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
EPS10EXP
TO
SPRINKLER
SYSTEM
WET
SYSTEM
ALARM
CHECK
VALVE
OS & Y
VALVE
TO
SPRINKLER
SYSTEM
WATER
MOTOR
GONG
RETARD
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
EPS10EXP
LOCAL ALARM
SHUT OFF
VALVE
WET SYSTEM
CHECK
VALVE
DRY
SYSTEM
ALARM
CHECK
VALVE
RETARD
WATER
BY-PASS
VALVE
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
TO
SPRINKLER
SYSTEM
WATER
MOTOR
GONG
WET
SYSTEM
ALARM
CHECK
VALVE
OS & Y
VALVE
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
WATER
MOTOR
GONG
WATER
BY-PASS
VALVE
OS & Y
VALVE
WET SYSTEM
LOCAL ALARM
SHUT OFF
VALVE
DRY SYSTEM
A78-2398-00
Table 1. Electrical connections (referenced at factory settings):
Locate it where vibration, shock, and mechanical loading
are minimal. Refer to piping diagram (Figure 2 on page 2).
a. Mount the device directly to the line via the 1/2" NPT
pressure connection. The use of teflon pipe sealant
tape is recommended. Be sure the fitting is tight
enough to prevent leaks.
b. Apply tightening torque to the brass hex portion of
device.
MODEL EPS10EXP
SWITCHES AT 0 P.S.I.
B
COM
A
B
COM
A
SW1
SW2
SWITCHES AT 4-8 P.S.I. (HIGH TRIP PT.)
B
B
COM
COM
A
A
SW1
SW2
CAUTION
High voltage. Electrocution hazard. Do not handle live AC
wiring or work on a device to which AC power is applied.
Doing so may result in severe injury or death.
BOTH SWITCHES ACTIVATE SIMULTANEOUSLY
Figure 3. Switch terminals:
3. Wire the device in accordance with the National
Electrical Code. Two 1/2” NPT conduit entry holes have
been provided in the mounting base to accept explosion
proof conduit fittings. If necessary, remove conduit entry
plug with 3/8” square wrench.
4. Connect wiring to terminals (see Figure 3 and Table 1).
COMMON
TERMINALS
TERMINAL
“A”
SWITCH #1
SWITCH #2
TERMINAL
“B”
Adjustments To Factory Settings
GROUND
SCREW
(GREEN)
BREAK WIRE AS SHOWN FOR
SUPERVISION OF CONNECTION.
DO NOT ALLOW STRIPPED WIRE
LEADS TO EXTEND BEYOND
SWITCH HOUSING. DO NOT
LOOP WIRES.
A78-2346-02
D770-25-00
2
I56-1427-001R
NOTE: The sensor assembly is not field replaceable. Do
not attempt to disassemble these parts. If you have
any questions, consult System Sensor. System
Sensor recommends careful consideration of the
following factors when specifying and installing
Alarm Pressure Switches. Always refer to the
Installation and Maintenance Instruction for specific recommendations on individual devices
before installing the unit.
The EPS10EXP device is pre-adjusted at the factory to alarm
at 4–8 PSI on rising pressure (see Table 2). Pressure switch
settings may be adjusted in the field to obtain a different
pressure alarm response from 4 PSI to 20 PSI. The switch
has an override feature on the adjustment mechanism to
prevent exceeding the 20 PSI max. setting of the switch.
This override feature carries with it a tolerance band that
may limit the upper adjustment to 16–20 PSI. Care must be
used when setting the switch to ensure that the lower limit
of 4 PSI is not exceeded. This will allow the switch to reset
within the 3 PSI differential stated.
1. Install pressure switch as stated in “INSTALLATION”
portion of instruction manual. Attach pressure test
source to system.
2. Remove adjustment wheel cover and back off locking
screw (see Figure 1) to allow main adjustment wheel to
rotate freely.
3. Test trip point by slowly introducing pressure from the
pressure test source. When trip point is found, reduce
pressure to zero. Rotate main adjustment wheel (counterclockwise to increase pressure) and retest until switch
trip point is at the desired pressure setting (4–20 PSI
range). Each tine on the wheel represents an approximate trip point change of 0.2 PSI. One full rotation
changes the trip point setting by approximately 2.5 PSI.
A reset differential of approximately 3 PSI is typical
throughout the entire adjustment range of switch.
4. Retest the set point several times to ensure accuracy of
setting.
5. Re-seat locking screw.
6. Re-install adjustment wheel cover.
• Electrical ratings stated in literature and on nameplates should not be exceeded.
• Overload on switch can cause failure on the first
cycle. Always wire devices according to national and
local electrical codes.
• Install units away from shock and vibration. Proper
electrical fittings should be used to prevent moisture
from entering the enclosure via the conduit.
• Test all devices for proper operation after initial installation. Perform preventive maintenance and periodic
testing as required by the applicable NFPA standards
but not less than bi-monthly.
• Install a back-up control for all critical applications
where control failure could endanger life or property.
A backup control to serve as a high or low limit control is especially recommended for applications where
a runaway condition could result.
• Do not mount unit where ambient temperatures will
exceed published limits.
Table 2.
MODEL
EPS10EXP
D770-25-00
FACTORY SETTINGS (PSI)
Approx. Reset
Rise
4—8
3 PSI Diff.
• Avoid impact or mechanical loading.
3
I56-1427-001R
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed pressure switch to be free from
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
defects in materials and workmanship under normal use and service for a
Please include a note describing the malfunction and suspected cause of
period of three years from date of manufacture. System Sensor makes no
failure. The Company shall not be obligated to repair or replace units
other express warranty for this pressure switch. No agent, representative,
which are found to be defective because of damage, unreasonable use,
dealer, or employee of the Company has the authority to increase or alter
modifications, or alterations occurring after the date of manufacture. In no
the obligations or limitations of this Warranty. The Company’s obligation
case shall the Company be liable for any consequential or incidental damof this Warranty shall be limited to the repair or replacement of any part
ages for breach of this or any other Warranty, expressed or implied whatof the pressure switch which is found to be defective in materials or worksoever, even if the loss or damage is caused by the Company’s negligence
manship under normal use and service during the three year period comor fault. Some states do not allow the exclusion or limitation of incidental
mencing with the date of manufacture. After phoning System Sensor’s toll
or consequential damages, so the above limitation or exclusion may not
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
apply to you. This Warranty gives you specific legal rights, and you may
send defective units postage prepaid to: System Sensor, Return
also have other rights which vary from state to state.
D770-25-00
4
I56-1427-001R
© System Sensor 2002