INSTALLATION AND MAINTENANCE INSTRUCTIONS
EPS40 Series and EPS120 Series
Supervisory Pressure Switches
SPECIFICATIONS
Contact Ratings:
Overall Dimensions:
Operating Temperature Range:
Maximum Service Pressure:
Adjustment Range:
Enclosure Rating:
Approximate Differential:
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
10 A, 1/2 HP @ 125/250 VAC
8A @ 125/250 VAC ~ (LPCB ONLY)
2.5A @ 6/12/24 VDC
See Figure 1
–40°F to +160°F
EPS40-1, EPS40-2: 300 PSI
EPS120-1, EPS120-2: 300 PSI
EPS40-1, EPS40-2: 10-100 PSI
EPS120-1, EPS120-2: 10-200 PSI
UL 4x — Indoor or Outdoor Use
NEMA 4 — Indoor or Outdoor Use
IP54
EPS40-1, EPS40-2:
3 PSI at 10 PSI
6 PSI at 100 PSI
EPS120-1, EPS120-2: 3 PSI at 10 PSI
9 PSI at 200 PSI
IMPORTANT
Please Read Carefully and Save
WARNING
High voltage. Electrocution hazard. Do not handle live AC wiring or work on
a device to which AC power is applied. Doing so may result in severe injury
or death. When utilizing switches at voltages greater than 74 VDC
or
49 VAC
, means to provide all-pole disconnection must be incorporated in
the field wiring, such as a circuit breaker.
This instruction manual contains important information about the installation and operation of supervisory pressure switches. Purchasers who install
switches for use by others must leave this manual or a copy of it with the user.
Read all instructions carefully before installation, following only those instructions that apply to the model you are installing.
3.Wire the device in accordance with the National Electrical Code. Two 7/8″
diameter conduit connection holes have been provided in the mounting
plate to accept standard 1⁄2″ conduit fittings (one is removable knock-out
type). If a NEMA 4/UL 4x (waterproof unit) is required, waterproof flexible metallic conduit and appropriate conduit fittings must be used. Recommended connectors are Thomas and Betts PN 5332 (180° coupling),
PN 5352 (90° coupling), and PN 5262 seal ring.
4. Connect wiring to terminals (see Figure 4 and Table 1).
Adjustments to Factory Settings
Before installing any alarm device, be thoroughly familiar with:
NFPA 72: National Fire Alarm Code
NFPA 13: Installation of Sprinkler Systems
NFPA 25:Inspection, Testing, and Maintenance of Water-based Fire Protection Systems
NFPA 13D: Standard for 1 and 2 Family Dwellings and Manufactured Homes
NFPA 13R: Standard for Multi-family Dwellings
Other applicable NFPA standards, local codes, and the requirements of the
authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report
an alarm condition. System Sensor is not responsible for devices that have
been improperly installed, tested, or maintained.
FIGURE 1. PRESSURE SWITCH BASIC DIMENSIONS:
4-1/4"
CAUTION
Do not use in potentially explosive atmospheres.Do not leave unused wires exposed.
M
CO
A
OPERATION
As pressure changes, a diaphragm actuates 1 or 2 snap action switches. The
pressure switch actuation is determined by adjustment settings.
SWITCH #2
INSTALLATION
1. Remove Cover
Cover is held on by two screws.
2. Mounting the Switch
The device is designed to be mounted in the upright position; side mounting
is also acceptable. Locate it where vibration, shock, and mechanical loading
are minimal. Refer to piping diagram above (Fig. 2 and 3).
a.Mount the device directly to the line via the 1⁄2" NPT pressure connection. The use of teflon pipe sealant tape is recommended. Be sure
the fitting is tight enough to prevent leaks.
b. Apply tightening torque to the black plastic hex portion of the device.
B
GROUND
SCREW
(GREEN)
HEX
ADJUSTMENT
SCREW
5-1/8"
LOCKING SCREW
MAIN ADJUSTMENT
WHEEL
1/2" NPT
W0170-00
D770-17-00
1
I56-0986-008R
FIGURE 2. TYPICAL PIPING DIAGRAM FOR EPS40-1, EPS40-2
EPS40
CHECK
VALVE
WIRE TO SUPERVISORY
CIRCUIT OF FIRE ALARM
CONTROL PANEL
TO
SPRINKLER
SYSTEM
DRY
PIPE
VALVE
INSTALL
BLEEDER
VALVE FOR
TESTING
EPS10
CHECK
VALVE
AIR LINE
SHUT-OFF
VALVE
AIR
PRESSURE
SUPPLY
LOCAL ALARM
SHUT OFF
VALVE
DRY SYSTEM
OS & Y
VALVE
C0141-01
TABLE 2.
MODEL
EPS40-1
EPS40-2
EPS120-1
EPS120-2
SINGLE-SWITCH MODEL — EPS40-1 AND EPS120-1
1.Install pressure switch as stated in “INSTALLATION” portion of instruction manual. Attach pressure test source to system.
2.Back off locking screw (see Fig. 4) to allow main adjustment wheel to
rotate freely.
3.Test the switch for the set point by introducing 40 PSI pressure from the
pressure test source for the EPS40-1 (115 PSI for the EPS120-1). Decrease
pressure slowly until the switch trips. Rotate main adjustment wheel,
Figure 5, (counterclockwise to increase pressure) and retest by first introducing a higher pressure than desired and slowly reducing pressure until
the switch trips. Repeat process until switch trip point is at desired pressure setting. Each number represents an approximate trip point change
of 1.8 PSI for the EPS40-1 and 6.6 PSI for the EPS120-1. For each 1/2
rotation of the adjustment wheel, the trip point setting changes by approximately 11 PSI for the EPS40-1 and 40 PSI for the EPS120-1.
4. Retest the set point several times to ensure accuracy of setting.
5. Re-seat locking screw.
FIGURE 4. SWITCH LOCATION:
COMMON
TERMINALS
TERMINAL “A”
SWITCH #2
M
CO
A
2
H#
ITC
WATER
MOTOR
GONG
WET
SYSTEM
ALARM
CHECK
VALVE
OS & Y
VALVE
RETARD
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
C0142-01
DUAL-SWITCH MODEL — EPS40-2 AND EPS120-2
1.Install pressure switch as stated in “INSTALLATION” portion of instruction manual. Attach pressure test source to system.
2.Back out the locking screw (see Fig. 4) to allow main adjustment wheel
to turn freely.
3.
Option 1: Adjust nominal pressure setting without affecting PSI window.
a) Adjust main adjustment wheel (see Fig. 5) to desired setting using
pressure source (i.e., valve or air maintenance device).
b) Turn main adjustment wheel counterclockwise to increase (see arrow
on mounting base) or clockwise to decrease pressure. Each number
on main adjust wheel represents an approximate window shift of 1.8
psi for EPS40-2 and 6.6 psi for EPS120-2. For each 1/2 rotation of the
adjustment wheel the window changes by approximately 11 psi for
EPS40-2 and 40 psi for EPS120-2.
c) Retest the set point several times to ensure the accuracy of the setting.
Option 2: Adjust pressure window size and nominal setting of pressure window.
a) Adjust main adjustment wheel (see Fig. 5) until high switch (SW1)
trips at desired pressure using pressure test source (valve or air maintenance device).
b) Refer to step B from Option 1.
c) Decrease pressure until the low switch trips (SW2).
d) Adjust 1/4˝ low pressure hex head nut (see Fig. 5) to either increase
(counterclockwise) or decrease (clockwise) the window size (the low
switch will be affected).
e) The approximate sensitivity of the hex screw adjustment: 1/2 turn =5
psi. A maximum of 30 psi is attainable.
4.Retest the set points several times to ensure the accuracy of the settings,
and adjust as necessary.
5. Re-seat locking screw.
NOTE: EPS40 models are able to be set to a range within 8-100psi only when
used with Victaulic series 768 and 769 FireLock NXT valves pre-set for use
with low pressure actuators. When used on Victaulic series 768 and 769
FireLock NXT all units must be 100% tested to verify pressure setting. Both
the main adjustment wheel and low pressure adjusting screw (See Figure 5)
need to be customer set and tested to insure proper functionality. For pressure setting instructions refer to Installation section for dual switch models in
this manual.
FACTORY SETTINGS (PSI)
Fall SW2
Nominal
Rise SW1
(Low Switch)
(Hi Switch)
30± 1.5
40
––
40
50± 2.5
30± 1.5
115
––
101.5 - 112.5
101.5 - 112.5
115
117.5 - 128.5
SWITCH #1
EPS120
BLEEDER
TEST
VALVE
WATER
MOTOR
GONG
WATER
BY-PASS
TEST
VALVE
OS & Y
VALVE
FIGURE 3. TYPICAL PIPING DIAGRAM FOR EPS120-1, EPS120-2
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
SW
B
TERMINAL “B”
TABLE 1. ELECTRICAL CONNECTIONS (REFERENCED AT FACTORY
SETTINGS):
MODELS EPS40-1, EPS120-1
GROUND
SCREW
SWITCH AT NORMAL SYSTEM PRESSURE
B
COM
A
LOCKING
SCREW
SWITCH AT TRIP POINT
B
COM
A
SWITCHES AT NORMAL SYSTEM PRESSURE
B
COM
A
B
COM
A
SW1
SWITCH 1
BREAK WIRE AS SHOWN FOR
SUPERVISION OF CONNECTION.
DO NOT ALLOW STRIPPED WIRE
LEADS TO EXTEND BEYOND
SWITCH HOUSING. DO NOT
LOOP WIRES.
W0185-01
D770-17-00
MODELS EPS40-2, EPS120-2
SWITCHES AT LOW TRIP POINT
B
B
COM
COM
A
A
SW1
SW2
SW2
SWITCHES AT HIGH TRIP POINT
B
COM
A
B
COM
A
SW1
SW2
W0186-00
2
I56-0986-008R
FIGURE 5. ADJUSTMENTS (DUAL-SWITCH MODEL SHOWN):
NOTE: The sensor assembly is not field replaceable. Do not attempt to disassemble these parts. If you have any questions, consult System Sensor. System
Sensor recommends careful consideration of the following factors when specifying and installing Alarm and Supervisory Pressure Switches. Always refer to
the Installation and Maintenance Instruction for specific recommendations on
individual devices before installing the unit.
Switch 2
(Low Switch
EPS40-2 and
EPS120-2)
Low Pressure
Adjusting
Screw
1/4" Hex Head
(Not Present in
Single Switch
Models)
• Electrical ratings stated in literature and on nameplates should not be exceeded.
• Overload on switch can cause failure on the first cycle. Always wire
devices according to national and local electrical codes.
• Install units away from shock and vibration. Proper electrical fittings should
be used to prevent moisture from entering the enclosure via the conduit.
• Test all devices for proper operation after initial installation. Perform preventive maintenance and periodic testing as required by the applicable
NFPA standards but not less than bimonthly.
Switch 1
(High Switch
EPS40-2 and
EPS120-2; Low
Switch EPS40-1)
Main Adjusting Wheel
(Turn Counterclockwise
to Increase Pressure)
NOTE: Each 1/2 turn of Low Pressure adjsuting screw adjusts
pressure approximately 5 psi. Turn counter clockwise to increase
pressure. Turn clockwise to decrease pressure. Each 1/2 turn
of High Pressure adjusting wheel adjusts pressure 11 psi on the
EPS40-2 and 40 psi on the EPS120-2.
• Install a back-up control for all critical applications where control failure
could endanger life or property. A backup control to serve as a high or
low limit control is especially recommended for applications where a
runaway condition could result.
W0144-02
• Do not mount unit where ambient temperatures will exceed published limits.
• Avoid impact or mechanical loading.
D770-17-00
3
I56-0986-008R
Please refer to insert for the Limitations of Fire Alarm Systems
THREE-YEAR LIMITED WARRANTY
System Sensor warrants its enclosed pressure switch to be free from defects in materials
and workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for this pressure switch.
No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of the pressure
switch which is found to be defective in materials or workmanship under normal use
and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System Sensor, Return
D770-17-00
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a
note describing the malfunction and suspected cause of failure. The Company shall not
be obligated to repair or replace units which are found to be defective because of damage,
unreasonable use, modifications, or alterations occurring after the date of manufacture.
In no case shall the Company be liable for any consequential or incidental damages for
breach of this or any other Warranty, expressed or implied whatsoever, even if the loss
or damage is caused by the Company’s negligence or fault. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation
or exclusion may not apply to you. This Warranty gives you specific legal rights, and you
may also have other rights which vary from state to state.
4
I56-0986-008R
© System Sensor 2014