EPS40EXP and EPS120EXP Explosion Proof

INSTALLATION AND MAINTENANCE INSTRUCTIONS
EPS40EXP and EPS120EXP Explosion Proof
Supervisory Pressure Switches
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Specifications
Contact Ratings:
10 A, 1/2 HP @ 125/250 VAC
2.5A @ 6/12/24 VDC
Operating Temperature Range:
–40°F to +160°F
EPS40EXP
EPS120EXP
Maximum Service Pressure (in PSI): 250
250
Adjustment Range:
10-100
10-200
Approximate Differential:
3 PSI @ 10 PSI
3 PSI @ 10 PSI
8 PSI @ 100 PSI
9 PSI @ 200 PSI
Enclosure Rating:
NEMA Type 4 — Indoor/Outdoor use
Hazardous Atmospheres
Classification:
Class I, Groups B, C, D, Div. 1
Class II, Groups E, F, G, Div. 1
Class III, Div. 1
Important
Please Read Carefully and Save
This instruction manual contains important information
about the installation and operation of supervisory pressure switches. Purchasers who install switches for use by
others must leave this manual or a copy of it with the user.
Operation
As pressure changes, a diaphragm actuates 2 snap action
switches. The pressure switch actuation is determined by
adjustment settings.
Figure 1. Pressure switch basic dimensions:
Read all instructions carefully before installation, following
only those instructions that apply to the model you are
installing.
4.9"
Before installing any alarm device, be thoroughly familiar
with:
NFPA 72:
NFPA 13:
NFPA 25:
HEX ADJUST
SCREW
1/4" HEX HEAD
COVER
National Fire Alarm Code
Installation of Sprinkler Systems
Inspection, Testing, and Maintenance of Waterbased Fire Protection Systems
COVER
TAMPER
SET SCREW
(WRENCH
PROVIDED)
Other applicable NFPA standards, local codes, and the
requirements of the authority having jurisdiction.
ADJUSTMENT
WHEEL
9.5"
COVER
(WRENCH
PROVIDED)
Failure to follow these directions may result in failure of the
device to report an alarm condition. System Sensor is not
responsible for devices that have been improperly installed,
tested, or maintained.
LOCKING
SCREW
MAIN ADJUSTMENT
WHEEL (TURN
COUNTERCLOSKWISE
TO INCREASE
PRESSURE)
1/2" NPT
D770-26-00
1
I56-1428-001R
Figure 2. Typical piping diagram for EPS40EXP
EPS40EXP
WIRE TO SUPERVISORY
CIRCUIT OF FIRE ALARM
CONTROL PANEL
EPS10EXP
Figure 3. Typical piping diagram for EPS120EXP
WIRE TO ALARM
INDICATING CIRCUIT
OF FIRE ALARM
CONTROL PANEL
AIR
PRESSURE
SUPPLY
EPS120EXP
TO
SPRINKLER
SYSTEM
CHECK
VALVE
INSTALL
BLEEDER
VALVE FOR
TESTING
DRY
PIPE
VALVE
AIR LINE
SHUT-OFF
VALVE
OS & Y
VALVE
CHECK
VALVE
WATER
BY-PASS
TEST
VALVE
WATER
MOTOR
GONG
BLEEDER
TEST
VALVE
WATER
MOTOR
GONG
WET
SYSTEM
ALARM
CHECK
VALVE
LOCAL ALARM
SHUT OFF
VALVE
OS & Y
VALVE
DRY SYSTEM
RETARD
OS & Y
VALVE
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
A78-2397-00
A78-2398-02
b. Apply tightening torque to the brass hex portion of
the device.
WARNING
To prevent ignition of hazardous atmospheres, disconnect
circuits before removing cover. Keep cover closed while circuits are live. Conduit runs must have sealing fittings connected within 18” of the enclosure.
CAUTION
High voltage. Electrocution hazard. Do not handle live AC
wiring or work on a device to which AC power is applied.
Doing so may result in severe injury or death.
Installation
1. Back out cover tamper set screw and remove cover (Fig. 1).
2. Mounting the Switch
The device is designed to be mounted in the upright position; side mounting is also acceptable. Locate it where
vibration, shock, and mechanical loading are minimal.
Refer to piping diagram above (Figures 2 and 3).
a. Mount the device directly to the line via the 1/2″ NPT
pressure connection. The use of teflon pipe sealant
tape is recommended. Be sure the fitting is tight
enough to prevent leaks.
Figure 4. Switch location:
3. Wire the device in accordance with the National
Electrical Code. Two 1/2″ NPT conduit entry holes have
been provided in the mounting base to accept explosion
proof conduit fittings. If necessary, remove conduit entry
plug with 3/8” square wrench.
4. Connect wiring to terminals (see Figure 4 and Table 1).
Table 1. Electrical connections (referenced at
factory settings):
COMMON
MODELS EPS40EXP, EPS120EXP
SWITCHES AT LOW TRIP POINT
B
B
COM
COM
A
A
SW1
SW2
TERMINAL
SWITCH #1
(HIGH SWITCH)
SWITCH #2
(LOW SWITCH)
SWITCHES AT NORMAL SYSTEM PRESSURE
B
COM
A
TERMINAL
“B”
B
COM
A
SW1
GROUND
SCREW
SW2
SWITCHES AT HIGH TRIP POINT
B
COM
A
B
COM
A
SW1
SW2
BREAK WIRE AS SHOWN FOR
SUPERVISION OF CONNECTION.
DO NOT ALLOW STRIPPED WIRE
LEADS TO EXTEND BEYOND
SWITCH HOUSING. DO NOT
LOOP WIRES.
A78-2346-02
D770-26-00
2
I56-1428-001R
Adjustments To Factory Settings
NOTE: The sensor assembly is not field replaceable. Do
not attempt to disassemble these parts. If you have
any questions, consult System Sensor. System
Sensor recommends careful consideration of the
following factors when specifying and installing
Alarm and Supervisory Pressure Switches. Always
refer to the Installation and Maintenance
Instruction for specific recommendations on individual devices before installing the unit.
Table 2.
FACTORY SETTINGS ( PSI)
MODEL
Fall Sw2
(Low Switch)
Nominal
Rise Sw1
(Hi Switch)
EPS40EXP
30 ± 1.5
40
50 ± 2.5
EPS120EXP
101.5 - 112.5
115
117.5 - 128.5
• Electrical ratings stated in literature and on nameplates should not be exceeded.
Dual-switch Model — EPS40EXP and EPS120EXP
1. Install pressure switch as stated in “INSTALLATION”
portion of instruction manual. Attach pressure test
source to system.
2. Remove adjustment wheel cover and back off locking
screw (see Figure 1) to allow main adjustment wheel to
rotate freely.
3. Option 1: To adjust the nominal setting of the pressure
window (low switch setting to high switch setting)
without affecting the size of the window, adjust the
main adjustment wheel, Figure 1, to the desired setting
using the pressure source to verify each switch setting.
Each tine on the wheel represents an approximate window shift of 1.8 PSI for the EPS40EXP and 6.6 PSI for the
EPS 120EXP. For each 1/2 rotation of the adjustment
wheel, the window changes by approximately 11 PSI for
the EPS 40EXP and 40 PSI for the EPS 120EXP.
• Overload on switch can cause failure on the first
cycle. Always wire devices according to national and
local electrical codes.
• Install units away from shock and vibration. Proper
electrical fittings should be used to prevent moisture
from entering the enclosure via the conduit.
• Test all devices for proper operation after initial installation. Perform preventive maintenance and periodic
testing as required by the applicable NFPA standards
but not less than bi-monthly.
• Install a back-up control for all critical applications
where control failure could endanger life or property.
A backup control to serve as a high or low limit control is especially recommended for applications where
a runaway condition could result.
Option 2: To adjust the pressure window size and the
nominal setting of the pressure window, adjust the main
adjustment wheel, Figure 1, until the high switch (SW1)
trips at the desired pressure using the pressure test
source. Decrease the pressure until the low switch
(SW2) trips. Note pressure and determine how much
change is desired on the low switch. Adjust the 1/4″ hex
screw, Figure 1, to either increase (counterclockwise) or
decrease (clockwise) the window size. (The low switch
will be affected.) The approximate sensitivity of the hex
screw adjustment: 1/2 turn = 5 PSI. An approximate
maximum window size of 30 PSI is obtainable. Retest
the high switch after adjusting the low switch.
4. Retest the set points several times to ensure the accuracy of the settings.
5. Re-seat locking screw.
6. Re-install adjustment wheel cover.
D770-26-00
• Do not mount unit where ambient temperatures will
exceed published limits.
• Avoid impact or mechanical loading.
3
I56-1428-001R
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed pressure switch to be free from
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
defects in materials and workmanship under normal use and service for a
Please include a note describing the malfunction and suspected cause of
period of three years from date of manufacture. System Sensor makes no
failure. The Company shall not be obligated to repair or replace units
other express warranty for this pressure switch. No agent, representative,
which are found to be defective because of damage, unreasonable use,
dealer, or employee of the Company has the authority to increase or alter
modifications, or alterations occurring after the date of manufacture. In no
the obligations or limitations of this Warranty. The Company’s obligation
case shall the Company be liable for any consequential or incidental damof this Warranty shall be limited to the repair or replacement of any part
ages for breach of this or any other Warranty, expressed or implied whatof the pressure switch which is found to be defective in materials or worksoever, even if the loss or damage is caused by the Company’s negligence
manship under normal use and service during the three year period comor fault. Some states do not allow the exclusion or limitation of incidental
mencing with the date of manufacture. After phoning System Sensor’s toll
or consequential damages, so the above limitation or exclusion may not
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
apply to you. This Warranty gives you specific legal rights, and you may
send defective units postage prepaid to: System Sensor, Return
also have other rights which vary from state to state.
D770-26-00
4
I56-1428-001R
© System Sensor 2002