WFDTN Series Waterflow Detector

WFDTN Series
Waterflow Detector
System Sensor WFDTN T-Tap Waterflow detectors are
designed for primary signaling in residential systems and
branch line signaling.
Features
• New directional cover allows installers and inspectors to
easily see the direction of flow
• UL-listed models are NEMA 4 rated
• New cover provides a better seal, is lighter weight, not painted
and corrosion resistant
• Sealed retard mechanism immune to dust and other contaminants
• Less exposed metal reduces shock hazard, plastic cover acts
as insulator and is resistant to arcing
• Visual switch activation
The new WFDTN Series waterflow detectors from System
Sensor consists of a rugged, NEMA 4-rated enclosure that is
more damage resistant than previous metal designs. The waterflow
detector is designed for both indoor and outdoor use, with the widest
available temperature range, from 32°F to 150°F.
Both the WFDTN with incorporated timer and WFDTNRN with
immediate activation fit any tee that has a 1 in. NPT branch,
including: 1in., 1¼in., 1½ in. and 2in. NPT threaded ferrous and
brass tees; 1in., 1¼in., 1½in. and 2in. copper sweat tees; Tyco,
Spears, NIBBCO brand 1 in. CPVC tees. Twelve different clearly
marked plastic paddles are available to fit different installation
configurations.
• Audible switch activation (73 dBA)
• Field-replaceable timer/switch assembly
• Accommodates up to 12 AWG wire
• Switch Synchronization activates both alarm panel
and local bell or horn strobe
• Tamper-resistant cover screws
• Improved water sealing
UL-listed models are equipped with tamper-resistant cover screws
to prevent unauthorized entry. Inside, two sets of SPDT (Form C)
synchronized switches are enclosed in a durable terminal block with
new layout designed to make wiring easy with wire ready terminals,
COM terminals are on a different elevation, large barrier between
switches and easy to read raised textured lettering all make wiring
easy. An optional cover tamper switch is available, securely snaps
into place, no tools required.
• Reduced product weight
• Wire-ready terminals
• Improved wiring with new terminal block layout
• Snap-in optional cover tamper switch
Agency Listings
S739
The WFDTN incorporates a mechanical time delay feature, which
minimizes the risk of false alarm due to pressure surges or air
trapped in the fire sprinkler system. The larger and easy to turn timer
dial makes setting the waterflow detector easy with high contrast
pad printed markings. The dial offers three tabs to help with turning,
with one larger tab located on the dial position for approximately 60
seconds, a notch is also indicated on the dial to locate approximately
30 seconds making setting the detector in dimmly lit locations easy.
The WFDTN series is designed for accuracy and repeatability. The
detector also offers improved performance during vibration in riser
applications where detectors are exposed to a large in rush of water.
30512266
Waterflow Detector Specifications
Engineering Specifications
Model shall be WFDTN or WFDTNRN as manufactured by System Sensor. T-Tap waterflow detectors shall be installed on a tee that has a 1in.
NPT branch including: 1in., 1¼in., 1½in. and 2in. NPT threaded ferrous and brass tee; 1in., 1¼in., 1½in. and 2in. copper sweat tees; Tyco,
Spears, NIBBCO brand 1in. CPVC tees as designed on the drawing and /or as specified herein. Detectors shall mount on any clear pipe span
of the appropriate nominal size, either a vertical upflow or horizontal run at least 6˝ from any fittings or valves that may change water direction,
flow rate, or pipe diameter or no closer than 24in. from a valve or drain. Detectors shall have a sensitivity in the range of 4 to 10 gallons per
minute and a static pressure rating of 375 psi. The WFDTN detector with incorporated time delay mechanism shall respond to waterflow in the
specified direction after a preset time delay that is field adjustable. The delay mechanism shall be a sealed mechanical pneumatic unit with visual
and audible indication of actuation. The actuation mechanism shall include a ethylene vinyl acetate vane inserted through a hole in the pipe
and connected by a mechanical linkage to the delay mechanism. Outputs shall consist of dual SPDT switches (Form C contacts). Two conduit
entrances for standard fittings of commonly used electrical conduit shall be provided on the detectors. A grounding provision is provided. Unless
noted, enclosures shall be NEMA 4 listed by Underwriters Laboratories Inc. All detectors shall be listed by Underwriters Laboratories Inc. for
indoor or outdoor use.
Standard Specifications
Static Pressure Rating
Maximum Surge
Triggering Threshold
Bandwidth (Flow Rate)
Conduit Entrances
Contact Ratings
Compatible Tee Fittings
375 PSI
18 Feet Per Second (FPS)
4–10 GPM
Operating Temperature Range
Enclosure Rating*
Cover Tamper Switch
Two openings for ½in. conduit.
One open, one knock-out type
Service Use
Two sets of SPDT (Form C)
10.0 A, ½ HP @ 125/250 VAC
2.5 A @ 6/12/24 VDC
Threaded ferrous and brass tees,
copper sweat tees, CPVC tees.
U.S. Patent Numbers
32°F to 150°F (0°C to 60°C)
NEMA 4 – suitable for indoor/outdoor use
Standard with ULC models, optional for
UL models, part no. CTS
Automatic Sprinkler: NFPA-13
One or Two Family Dwelling: NFPA 13D
Residential Occupancies up to 4 Stories:
NFPA 13R National Fire Alarm Code: NFPA-72
5,213,205
Warranty
3 Years
WFDTN Field Wiring Diagram
SSM24-X
SSV120-X
UL-LISTED
COMPATIBLE
CONTROL PANEL
POWER
24VDC OR
120VAC
+
NOTE: COMMON AND B-NO
CONNECTIONS WILL CLOSE
WHEN VANE IS DEFLECTED, I.E.,
WHEN WATER IS FLOWING. DUAL
SWITCHES PERMIT APPLICATIONS
TO BE COMBINED ON A SINGLE DETECTOR.
–
CONTACT RATINGS
+
INITIATING
LOOP
–
SUGGESTED EOL
RESISTOR
125/250 VAC
10 AMPS
24 VDC
2.5 AMPS
SCHEMATIC OF
INDIVIDUAL
SWITCH IN
“NO WATERFLOW’
CONDITION
BREAK WIRE AS
SHOWN FOR
SUPERVISION OF
CONNECTION. DO
NOT ALLOW
STRIPPED WIRE
LEADS TO EXTEND
BEYOND SWITCH
HOUSING. DO NOT
LOOP WIRES.
A-NC
COM
B-NO
Delay Adjustment Dial
DELAY
ADJUSTMENT
DIAL
NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST
AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS.
NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN SECONDS
Overall Dimensions, Installed
3-1/2"
2-5/8"
4"
TEE
ADAPTER
INSTALLATION GAUGE
TEE DEPTH
END OF PADDLE TREE MUST
FIT BETWEEN TOP OF TEE
AND BOTTOM OF FLANGE
TEE FITTING
PLASTIC VANE
DESIGNED TO FIT WITHIN 2 X 4 STUD WALL CONSTRUCTION
Ordering Information
Description
UL Model
WFDTN
ULC Model
WFDTNA
WFDTNRN
—
Accessories
FS-RT
CTS
WFDW
Delay mechanism and switch assembly
Tamper-proof switch kit
Tamper-proof wrench for cover
Waterflow Detector, Fits 1in., 1¼in., 1½in., 2in. ferrous and brass threaded tees;
1in., 1¼in., 1½in., 2in. copper sweat tees; 1in. CPVC tees.
Waterflow Detector without incorporated time delay mechanism,
fits same tees as WFDTN
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
www.systemsensor.com
©2014 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
WFDS43702 • 7/14