DH500 / DH500ACDC

500 Series™
Intelligent
Duct Smoke Detector
A Division of Pittway
3825 Ohio Avenue, St. Charles, IL 60174
1-800-SENSOR2 (736-7672), Fax 630-377-6495
http://www.systemsensor.com
Models Available
DH500 Duct Smoke Sensor Housing
DH500ACDC Duct Smoke Sensor Housing with
Optional Fan Control
Features
• DH500
–Operates from the control panel communication line
–Has outputs for remote LED output, remote test (24
VDC)
• DH500ACDC
–24 VAC/DC or 120/220 VAC operation
–Powered outputs for remote LED, remote test and
sounder
–Two Form C auxiliary contacts
(external supply is required only when using the
auxiliary relay or connecting any accessories)
• Continuous sensitivity monitoring from the panel
• Intelligent ion or photo heads with twist-in/twist-out
removal
• Air velocity rating from 500 to 4000 fpm
• Remote test station and remote annunciator accessories
• Clear polycarbonate cover for convenient visual
inspection of sampling tube filters
• UL 268A listed
• 3-year warranty
Specifications – DH500
Voltage Range:
Standby Current
(nominal):
Power-up Surge at
Max. Rated Voltage:
LED Current (nominal):
Length:
Width:
Depth:
Weight:
15 – 28 VDC peak
200 µA at 24 VDC
1.5 mA/sec.
6 mA at 24 VDC
14.5 inches (36.7 cm)
5 inches (12.7 cm)
4 inches (10.2 cm)
4 lbs. (1.8 kg)
Operating
Temperature Range:
Operating
Humidity Range:
Duct Air Velocity:
32° to 120° F (0° to 49° C)
10% to 93% relative humidity
500 – 4000 ft./min.
(91.4 – 1219.2 m/min.)
APPROVED
© System Sensor 4/97
This document is not intended to be used for installation purposes.
A05-200-02
General Description
System Sensor premium duct detectors, Models DH500
and DH500ACDC, feature the superior capabilities of an
intelligent sensor in a unit that is easy to install and
maintain. The DH500 Series Duct Housing samples air
currents passing through a duct and gives dependable
performance for shutdown of fans, blowers, and air
conditioning systems, preventing the spread of toxic
smoke and fire gases through the protected area.
Both Model DH500 and DH500ACDC duct housings can
accommodate either the 1551B Intelligent Ionization
Sensor or the 2551B Intelligent Photoelectronic Sensor.
The twist-in, twist-out heads allow for quick and easy
cleaning or application changes without removing the duct
housing.
These sensors communicate and are continuously
monitored through the communication line. Detector
sensitivity changes caused by dirt, smoke, temperature, or
humidity are reported to the panel, allowing compensation
algorithms to maintain the sensor’s set sensitivity. An
advance indication at the panel specifies the sensor
address, allowing for selected maintenance to be
performed as needed.
Remote alarm annunciation can be accomplished by
using the RA400Z Remote Annunciator or the RTS451 or
RTS451KEY Remote Test Station. The RTS451 and
RTS451KEY allow testing of the detector from a remote
location. The detector must be reset from the control
panel. Model DH500 incorporates zener diodes to conserve
power for communications to other devices and limit
power to supplementary accessories at times of high
power demands.
WARNING: Duct smoke detectors have specific limitations.
DUCT DETECTORS ARE
NOT a substitute for an open area smoke detector,
NOT a substitute for early warning detection, and
NOT a replacement for a building’s regular fire
detection system.
Refer to NFPA 72 and 90A for additional duct detector
application information.
Architect/Engineer Specifications
The air duct smoke detector shall be a System Sensor
Model DH500ACDC or DH500 Intelligent Series Smoke
Duct Detector to be used with compatible control units.
The detector housing shall be UL listed per UL 268A
specifically for use in air handling systems. The detector
shall operate in air velocities from 500 to 4000 feet per
minute. The detector housing shall be equipped with an
integral mounting base capable of accommodating either
intelligent photoelectronic or intelligent ionization detector
heads. It shall be capable of local testing via magnetic
switch or remote testing from the RTS451 or RTS451KEY
Remote Test Station. The duct detector housing shall
incorporate an airtight smoke chamber in compliance with
UL 268A, Standard for Smoke Detectors for Duct
Applications. The housing shall be capable of mounting to
either rectangular or round ducts without adapter
brackets. An integral filter system shall be included to
reduce dust and residue effects on detector and housing,
thereby reducing maintenance and servicing. Sampling
tubes shall be easily installed after the housing is mounted
to the duct by passing through the duct housing. Terminal
connections shall be of the strip and clamp method
suitable for 14–18 AWG wiring. Wiring shall be connected
to a terminal strip and be so noted.
Unused
4
Remote
Test
(–)
RA400Z (+)
(+)
RA400Z or (–)
RTS451
LED
(–)
REMOTE ALARM
LED OPTION
1 PER UNIT
8mA CURRENT DRAW
Must break tab
on back of
RA400Z when
used with
DH500.
5
(+)
RA400Z (+)
*
EXTERNAL
(–) POWER (+)
SUPPLY
1
2
3
RTS451
RTS451 (+)
REMOTE TEST STATION
(+)
RA400Z or
(–)
RTS451
Comm.
Line
(–)
Comm.
Line (+)
Communication
Line
Comm.
Line (–)
(–)
LED OPTION
1 PER UNIT
8mA CURRENT DRAW
(+)
UL Listed
Control Panel
1st
Detector
in Loop
2nd
Detector
in Loop
TEST COIL OPTION
1 PER UNIT
95mA CURRENT DRAW
System Wiring Diagram for DH500 Duct Smoke Detector Using a UL Listed Control Panel
Page
2
A05-200-02
DH500ACDC Power Supply Electrical Ratings
Power
120 VAC (120 – 132)
Requirements
mA rms maximum
Device
Standby
Alarm
DH500ACDC
44
52
PA400*
—
3
RA400Z*
—
1.5
RTS451*
—
1.5
RTS451**
11.5
13
RTS451KEY**
11.5
13
240 VAC (204–264)
mA rms maximum
Standby
Alarm
25
30
—
1.5
—
1
—
1
5.5
6.5
5.5
6.5
24 VAC (20.6–26.4)
mA rms maximum
Standby
Alarm
65
182
—
29
—
17.3
—
17.3
140
157
140
157
24 VDC (20–30)
ma DC maximum
Standby
Alarm
26
87
—
15
—
7
—
7
71
78
71
78
The currents shown for the DH500ACDC are maximum values with no accessories.
*All accessory currents are additional to DH500ACDC. There are no additional currents for accessories in standby.
**These devices draw current when the magnet is held in place to initiate an alarm.
Auxiliary Relay Contacts
10 amps maximum at 30 VDC; 10 amps maximum at 277 VAC.
1/3 Hp at 240 VAC; 360 VA at 240 VAC.
Programming Specifications
Additional requirements for intelligent system control
panels:
1. The panel must not continuously poll the same unit for
more than 3 seconds or the auxiliary relay and
auxiliary alarm output could switch states. After 3
seconds of continual polling of a device, the panel must
wait a minimum of 100mS before polling or
communicating to that same device.
2. Communications must not cease for more than 3
seconds without an additional clock pulse (after Pulse
Width 5) to turn off the LED on the sensor.
3. To allow the auxiliary relay and auxiliary alarm output
to return to a standby condition, (after being in alarm)
the panel must wait a minimum of 100mS after turning
off the sensor LED before re-communicating to the
same device.
CONDUIT HOLES
DUCT DETECTOR
HOUSING
INLET SAMPLING TUBE
(SUPPLIED SEPARATELY)
FOAM
GASKETS
TUBE
END
PLUG
1
NOTE: JUMPER WIRE (J5)
IS REQUIRED TO BE
INTACT FOR 2-WIRE
APPLICATIONS.
MUST CUT J5 FOR
POWER SUPERVISION
WHEN EXTERNAL
POWER IS USED.
2
3
K2
4
5
–
6
DUCT DETECTOR
COVER
120 VAC
J5
+
PC BOARD
INSULATOR
7
8
9 10
11
12
13
14 15
16
17
O-RINGS
DETECTOR BASE
240 VAC
24 VAC &
24 VDC
HOUSING
MOUNTING SCREWS
EXHAUST
FILTER ADAPTER
ALWAYS RUN AUXILIARY CONTROL
WIRING IN SEPARATE CONDUIT
COMMUNICATION (+)
LINE
FROM PANEL
(–)
(+) COMMUNICATION
LINE TO REST
(–) OF SYSTEM
SAMPLING TUBE
MOUNTING
SCREWS
NOTE: FOR POWER SUPPLY
WIRES, POLARITY IS NOT
IMPORTANT.
DETECTOR HEAD
(SUPPLIED SEPARATELY)
TEST MAGNET
System Wiring for DH500ACDC
SAMPLING TUBE
FILTERS
Exploded View of DH500ACDC
Duct Smoke Detector Components
24V auxiliary output maximum load is 80 mA;
alarm output maximum load is 20 mA.
2
1
6
2
ALARM SIGNAL (+)
LED
2
AUX POWER (–)
(+)
2
ALARM SIGNAL (+)
ALARM SIGNAL (+)
AUX POWER (–)
AUX POWER (–)
(+)
3 RESET
(NOT USED)
3
AUX POWER (+)
1
TEST (–)
DUCT DETECTOR
DH500ACDC
4
LED
6
TEST (+)
5 TEST (–)
DUCT DETECTOR
DH500ACDC
(–)
PA400 (OPTIONAL)
AUDIBLE ALERT
6
DUCT DETECTOR
DH500ACDC
(–)
DO NOT BREAK TAB
ON RA400Z
RA400Z (OPTIONAL)
REMOTE (LED)
ANNUNCIATOR
RTS451 (OPTIONAL)
REMOTE TEST
STATION
NOTE: THE RTS451 RESET CANNOT BE USED ON THE 500 SERIES.
Accessory Wiring
Page
3
A05-200-02
Ordering Information
Part No.
Description
DH500ACDC Intelligent duct smoke sensor housing with
auxiliary relays
DH500
Intelligent duct smoke sensor housing
1551B
Intelligent ionization sensor head
2551B
Intelligent photoelectronic sensor head
ST-1.5
Metal sampling tube duct widths 1´–2´
ST-3
Metal sampling tube duct widths 2´–4´
ST-5
Metal sampling tube duct widths 4´–8´
ST-10
Metal sampling tube duct widths 8´–10´
Accessories
RTS451
RTS451KEY
RA400Z
PA400
F36-05-00
M02-04-00
P48-21-00
A2650-01
RS24
RS14
MOD400R
CRT400
Remote test station (see below)
Remote test station with key (see below)
Remote LED (see below)
Piezo alert sounder (see below)
Replacement filters
Test magnet
End cap for sampling tube
Installation kit (parts bag)
Photoelectronic replacement screen
Ionization replacement screen
Sensitivity test kit
Ionization cover removal tool
RA400Z
Remote LED
PA400
Piezo Alert Sounder
ALARM
RESET
RTS451
Remote Test Station
ON
TEST
RTS451KEY
Remote Test Station
System Sensor Worldwide Manufacturing & Distribution
In Canada:
System Sensor Canada, A Division
of Pittway Corporation of Canada
6581 Kitimat Road, Unit #7
Mississauga, Ontario
Canada L5N 3T5
Telephone: 905-812-0767
Fax: 905-812-0771
Page
4
In the United Kingdom:
System Sensor Europe, Ltd.
A Member of Pittway Corporation
Horsham Gates III, North St.
Horsham, West Sussex
RH13 5PJ, United Kingdom
Telephone: 44-1403-276500
Fax: 44-1403-276501
In India:
System Sensor India
A Division of Pittway
A-204 Maheshwari Nagar
Orkay Mills Lane
Andheri East, Mumbai 400093
Telefax: 91-022-8202564
In the Far East:
System Sensor Far East
A Division of Pittway
Rm 903, Tower A, New Mandarin
Plaza, 14 Science Museum Road
TST East, Kowloon, Hong Kong
Telephone: 852-2191-9003
Fax: 852-2736-6580
A05-200-02