Product Manual - System Sensor

I56-3871-001
INSTALLATION AND MAINTENANCE INSTRUCTIONS
i4 Series Interface Module
COSMOD2W and COSMOD4W
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6583
www.systemsensor.com
*For use with COSMO-2W and COSMO-4W detectors
Specifications
Electrical Specifications
Power Supply Voltage:
Device Power-up Time:
Max. Standby Current:
Max. Alarm Current:
Nom. Standby Current:
Alarm Contact Rating:
Maintenance Contact Rating:
Max. IDC Loop Wiring Resistance:
Trigger Inputs:
Aux Power Out:
Min. Reset Time:
Initial Communication Cycle:
EZ Walk Test Availability:
Physical Specifications
Operating Temperature Range:
Operating Humidity Range:
Storage Temperature Range:
Height:
Width:
Depth:
Shipping Weight:
Wire Gauge Acceptance:
2-wire Compatibility Requirements
Min. Loop Voltage:
Max. Loop Voltage:
Max. Loop Resistance:
Max. Loop Ripple:
Max. Loading Capacitance:
Max. Alarm Current:
Max. Reset Voltage:
Alarm Delay:
Min. Alarm Reset Time:
Max. Normal Load Current:
Zone Type:
EOL Device:
Loop Style:
Compatibility Zone Identifier:
Detector Zone Identifier:
Max. Detectors Per Zone:
Resettable power; 2-Wire: Min. 8.5 Volts DC (Power limited); Max. 35 Volts DC (Power limited);
4-Wire: Min. 10 Volts DC (Power limited); Max. 35Volts DC (Power limited)
200 milliseconds
2-Wire: 62mA; 4-Wire: 52mA (Does not include current draw from attached detectors or EOL relay)
2-Wire: 174mA; 4-Wire: 75mA (Does not include reverse polarity current draw from attached detectors)
2-Wire: 45mA@12V, 27mA@24V; 4-Wire: 36mA@12V, 21mA@24V
(Does not include current draw from attached detectors or EOL relay)
100 mA @ 36 Volts DC, resistive, 25 ohms
100 mA @ 36 Volts DC, resistive, 25 ohms
2-Wire: 50 Ohms; 4-Wire: 300 Ohms
Min. On Voltage: 1.5V; Max. On Voltage=Vin
Same Voltage as Input Power (Unregulated, limited to 250mA)
300 milliseconds
6 minutes
6 minutes after power up or panel reset
0 - 50° C (32 - 122° F)
5 - 95% RH
-20 - 70° C (-4 - 158° F)
6.04 inches
6.04 inches
1.16 inches
0.6 lbs
Min: 22 AWG; Max: 14 AWG
12.9 Volts DC
14.5 Volts DC
50 Ohms
240 mVpp
0.01 mF
46 mA
0.30 Volts DC
n/a
0.3 seconds
2.4 mA
Standard
3.9k Ohms (+-5%)
B and D
A
A
(12) 2-wire i4 series model #COSMO-2W and/or i3 series model #2WTA-B detectors
BEFORE INSTALLATION
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
module will be installed in an existing operational system, inform the operator
and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the module.
The i4 COSMOD2W, 2-wire interface module, offers additional functionality
including:
• Ability to query for a “need for maintenance” condition from 2-wire i4
series model COSMO-2W and i3 series model 2WTA-B smoke detectors
• One relay is available to indicate a multitude of maintenance conditions
at the control panel
Notice: This manual should be left with the owner/user of this equipment.
This product is intended for use in ordinary indoor locations.
GENERAL DESCRIPTION
The i4 series module is designed to interface between compatible i4 series
combination CO/smoke detectors (Model COSMO-2W and COSMO-4W) and
compatible security/fire panels. It can also be used to retrofit compatible i4
series detectors into an existing loop of i3 smoke detector models 2WTA-B or
4WTA-B, without adding wires. The module interprets signals and translates
them into a separate smoke zone and a separate CO zone, each with alarm
and trouble signals. When signaled by the panel, a module will synchronize
connected detector sounders in either Temporal 3 or Temporal 4 pattern. Local
status indication is provided by 4 LED’s and a 3 position DIP switch enables
user configuration.
SS-500-004
• All conditions are displayed at the module and at the detector
• EZ Walk test mode allows the installer to easily verify that all detectors
on a loop are operational
• Allows 2-wire smoke detectors to be used on any compatible 4-wire
control panel and provides Style D wiring on the detector loop
FEATURES
• Compatible with System Sensor i4 series combination CO/smoke detectors
and System Sensor i3 Series smoke detectors models 2WTA-B or 4WTA-B.
• Allows up to 12 compatible devices including the i4 series combination
CO/smoke detector to be integrated with a panel
1
I56-3871-001
A CO alarm is self-clearing. Once a CO alarm has been signaled, the blue LED
will illuminate. Once the initiating device ceases to signal the CO event, the
blue LED will turn off. If a CO alarm is signaled, and not cleared, prior to a
smoke alarm condition, the module will keep both the blue and red LED’s
illuminated. If a smoke alarm is signaled first, the module will not be able to
receive notification of a CO alarm condition and will not be able to report it
to the panel.
• Allows sounder activation of all detectors on loop in either Temporal 3
or Temporal 4 pattern
VISIBLE ANNUNCIATON
The i4 series interface module has four visible LED’s: The green LED is a supervisory LED; it blinks during power on, reset, and during normal operation.
The yellow LED is used to indicate a loop wiring fault and will blink when it
is in EZ Walk test mode. The red LED signals smoke events; it blinks during
smoke maintenance events and lights constantly during smoke alarm events.
The blue LED signals CO events; it blinks during CO trouble or CO end-of-life,
and lights constantly during CO alarm.
Maintenance
This condition means one or more detectors on the loop have a smoke maintenance issue. See “Smoke Maintenance Inquiry” section for further details.
Freeze Trouble
This condition means one or more detectors on the loop are measuring the
ambient temperature is near the freezing point. See “Freeze Trouble Inquiry”
section for further details.
FIGURE 1: MODULE FRONT VIEW
CO Trouble
The module can be notified of a detector with a CO trouble condition. All CO
trouble conditions will be reported on the CO zone and displayed with a blinking blue LED. The module is not able to determine the number of detectors
that have a CO trouble condition or which trouble condition exists.
Green LED
Yellow LED
Red LED
Blue LED
INSTALLATION
MOUNTING
The module can be mounted to a 4-11/16 inch back box or inside a listed, dedicated enclosure. When mounting inside an enclosure with pre-stamped holes,
it may be easier to align the bottom screw hole first. It is not necessary to use
the module cover when mounting inside an enclosure.
EZ Walk Test Switch
(2-wire only)
S0331-00
FIGURE 2: MOUNTING
TABLE 1: OPERATION MODES
Operation
Mode
Normal (standby)
No power/
Non-operational
Green
LED
YelloW
LED
Red LED
Blue LED
Blink 5 Sec.
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Loop wiring fault
Blink 5 Sec.
ON
OFF
OFF
EZ Walk Test Mode
(2-wire only)
Blink 5 Sec.
Blink 5 Sec.
OFF
OFF
Alarm Smoke
Blink 5 Sec.
OFF
ON
OFF
Alarm CO
Blink 5 Sec.
OFF
OFF
ON
Alarm Smoke & CO
Blink 5 Sec.
OFF
ON
ON
Maintenance
(2-wire only)
Blink 5 Sec.
OFF
Blink 5 Sec.
OFF
Freeze Trouble (2wire only)
Blink 5 Sec.
OFF
Blink 10 Sec.
OFF
CO Trouble
Blink 5 Sec.
OFF
OFF
Blink 5 Sec.
HOLE FOR MOUNTING
TO VISTA ENCLOSURE
(No. 6x3/4 Type AB)
SLOT FOR MOUNTING
TO VISTA ENCLOSURE
(No. 6x5/16Type AB or Type F)
Normal (Standby)
The module is powered and detectors on the loop are operating normally.
SLOTS FOR MOUNTING
TO 4-11/16 JUNCTION BOX
0331-00
No Power/Non-operational
Power is not applied to the module or communication between the module
and the detectors on the loop is unsuccessful.
WIRING GUIDELINES
All wiring must be installed in compliance with the NFPA 70 standards, National Electrical Code, applicable state and local codes, and any special requirements at the local Authority Having Jurisdiction (AHJ).
Loop Wiring Fault
If an open circuit occurs on the loop, the module will indicate the condition
by illuminating the yellow LED. 2-wire units will then power the style-D terminals. When the wiring issue on the loop has been resolved, the module will
turn the yellow LED off.
The screw terminals in the mounting base will accept 14-22 gauge wire. Wire
connections are made by stripping approximately ¼” of insulation from the
end of the feed wire, inserting it into the proper base terminal, and tightening
the screw to secure the wire in place. Do not put wires more than 2 gauge
apart under the same clamping plate.
EZ Walk Test Mode
This indicates the module and detectors are in EZ Walk Test Mode. See “EZ Walk
Test” section for instructions on how to initiate and perform the EZ Walk test.
Note: The module must be installed in the same room and within 20 feet of
the panel and enclosed within conduit or equivalently protected against mechanical injury.
Alarm Smoke/Alarm CO/Alarm Smoke & CO
A smoke alarm will be indicated by the red LED. A CO alarm will be indicated
by the blue LED.
WARNING
Remove power from alarm control unit or initiating device circuits before installing detectors.
A smoke alarm is not self-restoring. Once a smoke alarm has been signaled,
the red LED will illuminate until the module is reset by removal of power.
Note: On some panels, resetting a smoke alarm may require additional steps
at the keypad to clear the trouble conditions on CO and smoke maintenance zones due to power loss to the module.
SS-500-004
2
I56-3871-001
FIGURE 3: COSMOD2W WIRING DIAGRAM
ALL CIRCUITS ARE SUPERVISED
(EXCEPT TRIGGERS) AND MUST
BE POWER LIMITED
SMOKE
AUXPOWER
Note: See Table 3 for dip
switch configurations
(resettable)
Panel
EOL
Resistors
SMOKE
ZONE
3.9k
RESISTOR
(supplied
with module)
CO
ZONE
MAINT.
ZONE
Panel
EOL
Resistor
BELL
LOOP STYLE D WIRING
COSMOD2W
COSMO-2W
OR
SMOKE
TRIGGER OUT
S0329-00
CO
TRIGGER
OUT
FIGURE 4: COSMOD4W WIRING DIAGRAM
ALL CIRCUITS ARE SUPERVISED
(EXCEPT TRIGGERS) AND MUST
BE POWER LIMITED
SMOKE
POWER
(resettable)
Panel
EOL
Resistors
SMOKE
ZONE
EOL
RELAY
#EOLR-1
3.9k
RESISTOR
(supplied
with module)
CO
ZONE
COSMO-4W
COSMOD4W
BELL
OR
S0330-00
SMOKE
TRIGGER OUT
CO
TRIGGER
OUT
FIGURE 5: Module Terminals
POWER IN +
POWER IN –
SMOKE ZONE EOL RESISTOR
(VALUE DEFINED BY PANEL)
CO ZONE EOL RESISTOR
(VALUE DEFINED BY PANEL)
SMOKE ALARM CONTACT
IDC +
IDC –
MAINTENANCE TROUBLE RELAY CONTACT
(COSMOD2W ONLY)
STYLE D + (4-WIRE DETECTOR POWER +)
CO ALARM CONTACT
STYLE D – (4-WIRE DETECTOR POWER –)
CO TRIGGER
SMOKE TRIGGER / BELL IN
S0334-00
SS-500-004
3
I56-3871-001
Freeze Trouble Inquiry
The module sends a freeze trouble inquiry to the detectors every four hours.
(Compatible i3 Series 2-wire smoke detectors only) If a response indicating a
freeze problem is received, the red LED on the module will blink once every
10 seconds and a smoke maintenance condition will be indicated to the panel.
WIRING DIAGRAMS
Install module wiring in accordance with appropriate wiring diagrams.
(Figure 3 and Figure 4)
The module relays have a maximum ON resistance of 25 ohms. This resistance plus the wiring resistance to the panel must be less than the maximum
zone wiring resistance stated in the panel manual.
TESTING
Modules must be tested after installation and following periodic maintenance.
Testing should be performed at least once per year.
INPUT TRIGGERS/SOUNDER ACTIVATION
Many panels can be programmed with triggers which are auxiliary relays that
activate upon an alarm condition. Two inputs are used to signal the module
to activate device sounders. The first is configurable by DIP switch to one of
two modes; bell in or smoke trigger. When in the bell mode, the module will
follow a valid coded signal from a Bell Out/NAC circuit consisting of high to
low, then low to high for less than 1.9 seconds each. In smoke trigger mode,
while the input is held high, the module will synchronize the detectors in a
Temporal 3 pattern.
NOTE: Before testing, notify the proper authorities that the system will be temporarily out of service. Disable the zone or system to prevent any unwanted
alarms.
EZ WALK TEST
The communication loop between the 2-wire modules and detectors can be
manually tested by putting the module and detectors into EZ Walk test mode.
This feature is for use with System Sensor detectors (i4 series model COSMO-2W
and i3 series model 2WTA-B) installed with the model COSMOD2W module.
The second input is for a CO trigger ; the CO trigger input allows a single module to have CO silence/hush capability and allows multiple module installations to have all sounders activated in Temporal 4 in the event of a CO alarm.
While the CO trigger is held high, the module will synchronize the detectors
in a Temporal 4 pattern. After 30 minutes in Temporal 4 alarm, the time period
between the Temporal 4 pulse will change from 5 seconds to 60 seconds.
The EZ Walk loop test verifies the initiating loop wiring and provides visual
status indication at each detector:
1.Ensure proper wiring and power is applied. Wait approximately 5 minutes from power-up before performing the EZ Walk test. The green LED
on the module must be blinking indicating the module is in ready/
standby mode to start the EZ Walk mode.
2.Locate the EZ Walk recessed test switch located behind the module cover
(See Figure 1). Depress the test switch with a small screwdriver. The yellow LED will blink showing that the module and detectors are in EZ Walk
mode for 5 minutes.
3.Observe the LEDs at each detector to make sure the green LED is double
blinking every 5 seconds as listed in Table 3.
4.At the end of the five minute period, the module will terminate EZ Walk
and the yellow LED will stop blinking. The EZ Walk test period can be
extended by pressing the test switch multiple times. Each press will add
5 minutes of additional time.
If a module or detector fails the test, its wiring should be checked. If the
module still fails, it should be replaced. Notify the proper authorities when all
testing has been completed.
Note: CO trigger may not be used with UL 864 panels. All detectors will sound
with no triggers connected, however, hush capability is not enabled.
TABLE 2: dip switch configurations
ON
(default)
OFF
dip switch # 1
dip switch # 2
dip switch # 3
Bell In
Smoke Maint on
Smoke Trouble and
Form-B Maint Relay
(COSMOD2W only)
Unused
Smoke Trigger
Smoke Maint on
Form-B Smoke maintenance Relay only
(COSMOD2W only)
Unused
POWER UP AND COMMUNICATIONS
Communications Check (2-Wire Only)
Upon power up, the module will send a request for communication check. All
compatible detectors on the loop that understand the communication protocol
will respond. If all detectors respond correctly, the green LED will blink once
every 5 seconds. If the module does not get a response, it will turn off the
green LED and continue to try every 2 minutes until a response is received.
NOTE: The EZ Walk loop test should not be used in lieu of functional testing
(alarm, trouble and other functional tests) of the system.
TABLE 3: ez walk test detector modes
Smoke Maintenance Inquiry
The module sends a smoke maintenance inquiry to the detectors every 24
hours. (Compatible 2-wire detectors only) If a response indicating a maintenance problem is received, the red LED on the module will blink once every 5
seconds and a smoke maintenance condition will be indicated to the panel. It
is likely that the detector needs to be cleaned or replaced, refer to the detector
instruction manual for maintenance instructions.
detector
green led
detector
red led
Double Blink 5 Seconds
OFF
Out of sensitiviy
OFF
Double Blink 5 Seconds
freeze condition
OFF
Double Blink 10 Seconds
proper operation
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
Three-Year Limited Warranty
System Sensor warrants its enclosed product to be free from defects in materials and
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
workmanship under normal use and service for a period of three years from date of
the malfunction and suspected cause of failure. The Company shall not be obligated to
manufacture. System Sensor makes no other express warranty for the enclosed product.
replace units which are found to be defective because of damage, unreasonable use,
No agent, representative, dealer, or employee of the Company has the authority to inmodifications, or alterations occurring after the date of manufacture. In no case shall the
crease or alter the obligations or limitations of this Warranty. The Company’s obligation
Company be liable for any consequential or incidental damages for breach of this or any
of this Warranty shall be limited to the replacement of any part of the product which
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
is found to be defective in materials or workmanship under normal use and service
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
during the three year period commencing with the date of manufacture. After phoning
incidental or consequential damages, so the above limitation or exclusion may not apply
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
to you. This Warranty gives you specific legal rights, and you may also have other rights
number, send defective units postage prepaid to: System Sensor, Returns Department, RA
which vary from state to state.
SS-500-004
4
I56-3871-001
©2012 System Sensor