i3 Series Loop Test/Maintenance Module MOD2W

I56-4001-000
INSTALLATION AND MAINTENANCE INSTRUCTIONS
i3 Series Loop Test/Maintenance Module
MOD2W
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6583
www.systemsensor.com
*For use with 2-Wire i3 series smoke detectors 2W-B, 2WT-B, and (one) 2WTR-B
SPECIFICATIONS
Electrical Specifications
Power Supply Voltage:
Device Power-up Time:
Max. Standby Current:
Max. Alarm Current:
Nom. Standby Current:
Alarm Contact Rating:
Maintenance Contact Rating:
Max. IDC Loop Wiring Resistance:
Min. Reset Time:
Initial Communication Cycle:
EZ Walk Test Availability:
Physical Specifications
Operating Temperature Range:
Operating Humidity Range:
Storage Temperature Range:
Height:
Width:
Depth:
Shipping Weight:
Wire Gauge Acceptance:
2-wire Compatibility Requirements
Min. Loop Voltage:
Max. Loop Voltage:
Max. Loop Resistance:
Max. Loop Ripple:
Max. Loading Capacitance:
Max. Alarm Current:
Max. Reset Voltage:
Alarm Delay:
Min. Alarm Reset Time:
Max. Normal Load Current:
Zone Type:
EOL Device:
Loop Style:
Compatibility Zone Identifier:
Detector Zone Identifier:
Max. Detectors Per Zone:
Resettable power; Min. 8.5 Volts DC (Power limited); Max. 35 Volts DC (Power limited);
200 milliseconds
60mA
185mA
38mA@12V, 20mA@24V
100 mA @ 36 Volts DC, resistive, 25 ohms
100 mA @ 36 Volts DC, resistive, 25 ohms
50 Ohms
300 milliseconds
6 minutes
6 minutes after power up or panel reset
0 - 50° C (32 - 122° F)
5 - 95% RH
-20 - 70° C (-4 - 158° F)
6.04 inches
6.04 inches
1.16 inches
0.6 lbs
Min: 22 AWG; Max: 14 AWG
12.6 Volts DC
14.52 Volts DC
50 Ohms
240 mVpp
0.01 mF
43.5 mA
0.30 Volts DC
n/a
0.3 seconds
1.2 mA
Standard
3.9k Ohms (+-5%)
B and D
A
A
(12) 2-wire i3 series model #2W-B, 2WT-B, (one) 2WTR-B
BEFORE INSTALLATION
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
module will be installed in an existing operational system, inform the operator
and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the module.
is used to indicate a loop wiring fault and will blink when it is in EZ Walk test
mode. The red LED signals smoke events; it blinks during smoke maintenance
events and lights constantly during smoke alarm events.
FIGURE 1: MODULE FRONT VIEW
Notice: This manual should be left with the owner/user of this equipment.
This product is intended for use in ordinary indoor locations.
GENERAL DESCRIPTION
The MOD2W allows a control panel to receive a “need for maintenance” signal from two–wire i3 series smoke detectors, model numbers 2W–B, 2WT–B
and one 2WTR-B. The module uses a form C zone relay to initiate “out of sensitivity” and “freeze trouble”, a form A zone alarm relay and a second form
A zone relay to indicate loop fault. An EZ Walk Test puts all detectors on the
loop into a Walk Test mode for easy verification of detector loop wiring. The
module allows 2-wire smoke detectors to be used on any compatible 4-wire
control panel and provides Style D wiring on the detector loop.
Green LED
Yellow LED
Red LED
EZ Walk Test Switch
VISIBLE ANNUNCIATON
The MOD2W has three visible LED’s: The green LED is a supervisory LED; it
blinks during power on, reset, and during normal operation. The yellow LED
SS-560-000
S0331-02
1
I56-4001-000
WIRING GUIDELINES
All wiring must be installed in compliance with the NFPA 70 standards, National Electrical Code, applicable state and local codes, and any special requirements at the local Authority Having Jurisdiction (AHJ).
TABLE 1: OPERATION MODES
OPERATION MODE
Normal (standby)
No power/Non-operational
GREEN
LED
YELLOW
LED
RED LED
Blink 5 Sec.
OFF
OFF
OFF
OFF
OFF
Loop wiring fault
Blink 5 Sec.
ON
OFF
EZ Walk Test Mode
Blink 5 Sec.
Blink 5 Sec.
OFF
Alarm Smoke
Blink 5 Sec.
OFF
ON
Maintenance
Blink 5 Sec.
OFF
Blink 5 Sec.
Freeze Trouble
Blink 5 Sec.
OFF
Blink 10 Sec.
The screw terminals in the mounting base will accept 14-22 gauge wire. Wire
connections are made by stripping approximately ¼” of insulation from the
end of the feed wire, inserting it into the proper base terminal, and tightening
the screw to secure the wire in place. Do not put wires more than 2 gauge
apart under the same clamping plate.
WARNING
Remove power from alarm control unit or initiating device circuits before installing detectors.
NORMAL (STANDBY)
The module is powered and detectors on the loop are operating normally.
WIRING DIAGRAMS
Install module wiring in accordance with appropriate wiring diagrams.
(Figure 3)
NO POWER/NON-OPERATIONAL
Power is not applied to the module or communication between the module
and the detectors on the loop is unsuccessful.
The module relays have a maximum ON resistance of 25 ohms. This resistance plus the wiring resistance to the panel must be less than the maximum
zone wiring resistance stated in the panel manual.
LOOP WIRING FAULT
If an open circuit occurs on the loop, the module will indicate the condition
by illuminating the yellow LED. 2-wire units will then power the style-D terminals. When the wiring issue on the loop has been resolved, the module will
turn the yellow LED off.
NOTE: If 2–wire i3 detectors are used in conjunction with a style D initiating circuit, the MOD2W must be used to provide that capability. Ground
fault on a module’s 2-wire loop can be indicated at a control panel if the
control panel is capable of ground fault detection on the power supply to the
module and meets NFPA 72 ground fault indication requirements for initiating
device circuits. The installer must verify that capability.
EZ WALK TEST MODE
This indicates the module and detectors are in EZ Walk Test Mode. See “EZ Walk
Test” section for instructions on how to initiate and perform the EZ Walk test.
ALARM SMOKE
A smoke alarm will be indicated by the red LED.
TABLE 2: DIP SWITCH CONFIGURATIONS
A smoke alarm is not self-restoring. Once a smoke alarm has been signaled,
the red LED will illuminate until the module is reset by removal of power.
MAINTENANCE
This condition means one or more detectors on the loop have a smoke maintenance issue. See “Smoke Maintenance Inquiry” section for further details.
FREEZE TROUBLE
This condition means one or more detectors on the loop are measuring the
ambient temperature is near the freezing point. See “Freeze Trouble Inquiry”
section for further details.
DIP SWITCH # 1
DIP SWITCH # 2
DIP SWITCH # 3
ON
(DEFAULT)
Unused
Smoke Maint on
Smoke Trouble and
Form-B Maint Relay
Unused
OFF
Unused
Smoke Maint on
Form-B Smoke maintenance Relay only
Unused
POWER UP AND COMMUNICATIONS
COMMUNICATIONS CHECK
Upon power up, the module will send a request for communication check. All
compatible detectors on the loop that understand the communication protocol
will respond. If all detectors respond correctly, the green LED will blink once
every 5 seconds. If the module does not get a response, it will turn off the
green LED and continue to try every 2 minutes until a response is received.
INSTALLATION
MOUNTING
The module can be mounted to a 4-11/16 inch back box or inside a listed, dedicated enclosure. When mounting inside an enclosure with pre-stamped holes,
it may be easier to align the bottom screw hole first. It is not necessary to use
the module cover when mounting inside an enclosure.
SMOKE MAINTENANCE INQUIRY
The module sends a smoke maintenance inquiry to the detectors every 24
hours. If a response indicating a maintenance problem is received, the red
LED on the module will blink once every 5 seconds and a smoke maintenance
condition will be indicated to the panel. It is likely that the detector needs to
be cleaned or replaced, refer to the detector instruction manual for maintenance instructions.
FIGURE 2: MOUNTING
HOLE FOR MOUNTING
TO VISTA ENCLOSURE
(No. 6x3/4 Type AB)
FREEZE TROUBLE INQUIRY
The module sends a freeze trouble inquiry to the detectors every four hours. If
a response indicating a freeze problem is received, the red LED on the module
will blink once every 10 seconds and a smoke maintenance condition will be
indicated to the panel.
SLOT FOR MOUNTING
TO VISTA ENCLOSURE
(No. 6x5/16Type AB or Type F)
SS-560-000
SLOTS FOR MOUNTING
TO 4-11/16 JUNCTION BOX
S0332-00
2
I56-4001-000
FIGURE 3: MOD2W WIRING DIAGRAM
ALL CIRCUITS ARE SUPERVISED
AND MUST BE POWER LIMITED
SMOKE
AUXPOWER
Note: See Table 2 for dip
switch configurations
(resettable)
Panel
EOL
Resistor
SMOKE
ZONE
3.9K EOL
RESISTOR
RA100Z
(5) RA –
(4) RA +
(3) – IN/OUT
(2) + OUT
(1) + IN
2W-B or
2WT-B
(5) RA –
(4) RA +
(3) – IN/OUT
(2) + OUT
MOD2W
Panel
EOL
Resistor
(1) + IN
MAINT.
ZONE
RA100Z
2W-B or
2WT-B
LOOP STYLE D / CLASS A WIRING
S0335-00
FIGURE 4: MODULE TERMINALS
POWER IN +
POWER IN –
SMOKE ZONE EOL RESISTOR
(VALUE DEFINED BY PANEL)
SMOKE ALARM CONTACT
UNUSED
IDC +
IDC –
MAINTENANCE TROUBLE RELAY CONTACT
STYLE D + /CLASS A
UNUSED
STYLE D – /CLASS A
UNUSED
UNUSED
S0334-03
SS-560-000
3
I56-4001-000
TABLE 3: EZ WALK TEST DETECTOR MODES
TESTING
Modules must be tested after installation and following periodic maintenance.
Testing should be performed at least once per year.
NOTE: Before testing, notify the proper authorities that the system will be
temporarily out of service. Disable the zone or system to prevent any unwanted alarms.
DETECTOR
GREEN LED
DETECTOR
RED LED
Double Blink 5 Seconds
OFF
OUT OF SENSITIVIY
OFF
Double Blink 5 Seconds
FREEZE CONDITION
OFF
Double Blink 10 Seconds
PROPER OPERATION
EZ WALK TEST
The communication loop between the module and detectors can be manually
tested by putting the module and detectors into EZ Walk test mode.
The EZ Walk loop test verifies the initiating loop wiring and provides visual
status indication at each detector:
1.Ensure proper wiring and power is applied. Wait approximately 5 minutes from power-up before performing the EZ Walk test. The green LED
on the module must be blinking indicating the module is in ready/
standby mode to start the EZ Walk mode.
2.Locate the EZ Walk recessed test switch located behind the module cover
(See Figure 1). Depress the test switch with a small screwdriver. The
yellow LED will blink showing that the module and detectors are in EZ
Walk mode for 5 minutes.
3.Observe the LEDs at each detector to make sure the green LED is double
blinking every 5 seconds as listed in Table 3.
4.At the end of the five minute period, the module will terminate EZ Walk
and the yellow LED will stop blinking. The EZ Walk test period can be
extended by pressing the test switch multiple times. Each press will add
5 minutes of additional time.
If a module or detector fails the test, its wiring should be checked. If the
module still fails, it should be replaced. Notify the proper authorities when all
testing has been completed.
NOTE: The EZ Walk loop test should not be used in lieu of functional testing
(alarm, trouble and other functional tests) of the system.
FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
THREE-YEAR LIMITED WARRANTY
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
System Sensor warrants its enclosed product to be free from defects in materials and
the malfunction and suspected cause of failure. The Company shall not be obligated to
workmanship under normal use and service for a period of three years from date of
replace units which are found to be defective because of damage, unreasonable use,
manufacture. System Sensor makes no other express warranty for the enclosed product.
modifications, or alterations occurring after the date of manufacture. In no case shall the
No agent, representative, dealer, or employee of the Company has the authority to inCompany be liable for any consequential or incidental damages for breach of this or any
crease or alter the obligations or limitations of this Warranty. The Company’s obligation
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
of this Warranty shall be limited to the replacement of any part of the product which
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
is found to be defective in materials or workmanship under normal use and service
incidental or consequential damages, so the above limitation or exclusion may not apply
during the three year period commencing with the date of manufacture. After phoning
to you. This Warranty gives you specific legal rights, and you may also have other rights
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
which vary from state to state.
number, send defective units postage prepaid to: System Sensor, Returns Department, RA
SS-560-000
4
I56-4001-000
©2013 System Sensor