PIDP-SS, PID-SS, CZI-SS, and DPID-SS Features PIDP-SS Monitor Modules with SmartScan™ Description Four different monitor modules are available for Gamewell intelligent controls with SmartScan™ to suit a variety of applications. Monitor modules are used to supervise an initiating device circuit of dry-contact input devices, such as conventional heat dePIDP-SS tectors and pull stations, or monitor and and power a circuit of two-wire smoke CZI-SS detectors (CZI-SS). PIDP-SS — is a standard-sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices. g2465mod.tif PID-SS — is a miniature monitor module (a mere 1.3" (3.302 cm) H x g2465duo.tif 2.75" (6.985 cm) W x 0.5" (1.270 cm) D) used to supervise a Style B (Class B) circuit. Its compact design allows detail of the PID-SS to often be mounted in a DPID-SS — single-gang box behind the device it’s note “ones” addresses are monitoring. 0, 2, 4, 6, 8 CZI-SS — is a standard-sized modonly ule used to monitor and supervise compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit. DPID-SS — is a standard-sized dual monitor module used to monitor and supervise two independent Style B (Class B) initiating device circuits (IDCs) at two separate, consecutive addresses in intelligent, two-wire systems. PIDP-SS Monitor Module The PIDP-SS Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. PIDP-SS Applications — Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. Maximum IDC loop length is 2,500 ft./762 m (20 ohms maximum). PIDP-SS Operation — Each PIDP-SS uses one of 99 available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06 Page 1 of 6 • Built-in type identification automatically identifies this device as a monitor module to the control panel. • Powered directly by two-wire SLC loop. No additional power required. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct-dial entry of address: 01 –99 • LED flashes green during normal operation (this is a programmable option) and latches on steady red to indicate alarm. • Built-in type identification automatically identifies this device as a monitor module to the panel. PID-SS • Powered directly by two-wire FACP. No additional power required. • High noise (EMF/RFI) immunity. • Tinned, stripped leads for ease of wiring. • Direct-dial entry of address: 01 – 99 CZI-SS • Supports compatible two-wire smoke detectors. • Supervises IDC wiring and connection of external power source. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct-dial entry of address: 01 – 99 • LED flashes during normal operation (this is a programmable option). • LED latches steady to indicate alarm on command from control panel. Listings Listings and approvals below apply to the basic PIDP-SS, PID-SS, CZI-SS and DPID-SS monitor modules. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest status. • UL Listed: file S521. • CSFM approved: file 7300-1288:170. PID-SS Mini Monitor Module The PID-SS Mini Monitor Module can be installed in a singlegang junction directly behind the monitored unit. Its small size and light weight g2465min.wmf allow it to be installed without rigid mounting. The PID-SS is intended for use in intelligent, twowire systems where the individual address of each module is selected using rotary switches. It provides a twowire initiating device circuit for normally-opencontact fire alarm and security devices. PID-SS Applications — Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the circuit. PID-SS Operation — Each PID-SS uses one of 99 available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/ normal/short) of its Initiating Device Circuit (IDC). CZI-SS Interface Module The CZI-SS Interface Module is intended for use in intelligent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two-wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with this module. CZI-SS Applications — Use the CZI-SS to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 ohms). Install ELR across terminals 8 and 9 for Style D application. CZI-SS Operation — Each CZI-SS uses one of 99 available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/ normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). Page 2 of 6 Specifications PIDP-SS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum operating current: 375 µA (LED flashing). EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. PID-SS Nominal operating voltage: 15 to 32 VDC. Maximum operating current: 375 µA. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.5" (1.270 cm) deep. Wire length: 6" (15.24 cm) minimum. CZI-SS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum operating current: 255 µA (LED flashing). EOL resistance: 3.9K ohms. External supply voltage (between Terminals T3 and T4): DC voltage: 18 to 28 volts power limited. Ripple voltage: 0.1 VRMS maximum. Current: 90 mA per module maximum. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. DPID-SS Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 5.7 mA (LED on). Maximum operating current: 750 µA (LED flashing). EOL resistance: 47K ohms. Maximum IDC wiring resistance: 1,500 ohms. Temperature range: 32° to 120°F (0° to 49°C). Humidity range: 10% to 93% (non-condensing). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 2.125" (5.398 cm) deep. PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06 DPID-SS Dual Monitor Module The DPID-SS Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent two-wire initiating device circuits (IDCs) at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices; or either normally open or normally closed security devices. The module has a single panelcontrolled LED. NOTE: The DPID-SS provides two Style B (Class B) IDC circuits ONLY. Style D (Class A) IDC circuits are NOT supported in any application. DPID-SS Applications — The DPID-SS automatically assigns itself to two addressable points, starting with the original address. For example, if the DPID-SS is set to address “56”, then it will automatically assign itself to addresses “56” and “57”. NOTE: “ones” addresses on the DPID-SS are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. Avoid duplicating addresses on the system. Mounting Diagram for standard-sized modules Installation PIDP-SS, DPID-SS, and CZI-SS modules mount directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installation instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regulations. These modules are intended for powerlimited wiring only. The PID-SS module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations. Product Line Information PIDP-SS Monitor module. PID-SS Monitor module, miniature. CZI-SS Monitor module, two-wire detectors DPID-SS Monitor module, dual, two independent Class B circuits. SMB500 Optional surface-mount backbox. g2465mt2.wmf PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06 Page 3 of 6 Wiring Diagrams The following wiring diagrams are included: 1) DPID-SS, typical dual two-wire Style B initiating device circuit configuration. 2) 3) PID-SS, typical two-wire Style B initiating device circuit configuration. PIDP-SS, typical two-wire initiating circuit configuration, NFPA Style B. 4) 5) 6) PIDP-SS, typical four-wire fault-tolerant initiating circuit configuration, NFPA Style D. PIDP-SS, typical two-wire initiating circuit configuration for security systems (with alarm versus short capability). CZI-SS, interface two-wire conventional detectors, NFPA Style B. 7) CZI-SS, interface two-wire conventional detectors, NFPA Style D. Fig. 1 DPID-SS: Typical dual two-wire Style B initiating device circuit configuration. WIRING DIAGRAM: DPID-SS g2465w1.wmf Fig. 2 PID-SS: Typical two-wire Style B initiating device circuit configuration. WIRING DIAGRAM: PID-SS g2465w2.wmf Page 4 of 6 PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06 WIRING DIAGRAMS THIS PAGE: PIDP-SS • • • • • Connect modules to listed compatible Gamewell control panels only. All wiring shown is supervised and power limited. Install contact closure devices per manufacturers’ installation instructions. Any number of UL-listed contact closure devices may be used. DO NOT MIX fire alarm initiating, supervisory, or security devices on the same circuit. Fig. 3 PIDP-SS: Typical two-wire initiating device circuit configuration, NFPA Style B. 6720wir2.wmf Fig. 4 PIDP-SS: Typical four-wire fault-tolerant initiating circuit configuration, NFPA Style D. 6720wir3.wmf Fig. 5 PIDP-SS: Typical two-wire initiating circuit configuration for security systems (with alarm versus short capability). 6720wir4.wmf PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06 Page 5 of 6 • • • • • • • Connect modules to listed compatible control panels only. Terminal wiring must be power limited. DO NOT MIX fire alarm initiating, supervisory, or security devices on the same circuit. DO NOT LOOP wire under terminals. Break wire run to provide supervision of connections. Detectors must be UL listed compatible with module. Install detectors per manufacturers’ installation instructions. Power to the interface module must be externally switched to reset the detectors. An RCE-SS relay control module can be used to switch power from a standard power supply. WIRING DIAGRAMS THIS PAGE: CZI-SS Fig. 6 CZI-SS: Interface two-wire conventional detectors, NFPA Style B. 6720wir5.wmf Fig. 7 CZI-SS: Interface two-wire conventional detectors, NFPA Style D. 6720wir6.wmf Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 Phone: 203-484-7161 Fax: 203-484-7118 www.gamewell-fci.com A Honeywell Company © 2006 Gamewell-FCI Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell-FCI assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the product shall always be used for actual installation. For more information, contact Gamewell-FCI. Page 6 of 6 PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06