3-Phase International Maintenance Bypass Planning Sheet

Tripp Lite 3-Breaker Maintenance Bypass Panel with Kirk Key Interlock
Bypass Panel
Model #
SU20KMBPK
SU30KMBPK
SU40KMBPK
SU60KMBPK
SU80KMBPK
SU40KMBPKX
SU60KMBPKX
SU80KMBPKX
Compatible UPS Systems
SU20K3/3, SU20K3/3XR5, SU20K3/3X, SU20KX
SU30K3/3, SU30K3/3XR5, SU30K3/3X
SU40K
SU60K
SU80K
SU40KX
SU60KX, SU60KTV
SU80KX, SU80KTV
B
Shipping
Dimensions (in)
24.87 x 9.75 x 38.2
24.87 x 9.75 x 38.2
30.87 x 12.5 x 43.2
30.87 x 12.5 x 43.2
36.87 x 12.5 x 62.0
24.87 x 9.75 x 38.2
30.87 x 12.5 x 43.2
30.87 x 12.5 x 43.2
Shipping
Weight
(lb)
130
130
225
225
375
130
225
225
A
Unit Dimensions (in)
[A]
24.12
24.12
30.12
30.12
36.10
24.12
30.12
30.12
[B]
9.00
9.00
11.75
11.75
11.75
9.00
11.75
11.75
[C]
37.36
37.36
42.36
42.36
61.25
37.36
42.36
42.36
[D]
20.00
20.00
26.00
26.00
32.00
20.00
26.00
26.00
[E]
33.25
33.25
38.25
38.25
57.12
33.25
38.25
38.25
Unit
Weight
(lb)
125
125
220
220
370
125
220
220
Voltage
240/415
240/415
up to 240
up to 240
up to 240
up to 480
up to 480
up to 480
Breaker
(Amps)
70
100
150
225
300
80
125
150
Breaker
KAIC
Rating
14/18
14/18
65
65
65
14
35
35
Kirk
Key
yes
yes
yes
yes
yes
yes
yes
yes
D
UTILITY FEED
SW1
BYPASS
INPUT
ISOLATION
SW2
C
E
MAINTENANCE
BYPASS
KEY INTERLOCK #1
SW3
SEQUENCE OF
OPERATION LABEL
(INSIDE DOOR - SEE
BELOW FOR DETAIL)
UPS
OUTPUT
ISOLATION
KEY INTERLOCK #2
TO LOAD
.4” DIAMETER
MOUNTING
HOLE (4)
LEFT SIDE VIEW
FRONT VIEW (DOOR REMOVED)
FRONT VIEW
SEQUENCE OF OPERATION LABEL DETAIL
BREAKER
OPEN
KEY TRAPPED
IN INTERLOCK
BREAKER
LOCKED
CLOSED
UPS IN NORMAL
OPERATION
BREAKER
LOCKED
CLOSED
KEY
REMOVED
BREAKER
LOCKED
CLOSED
SWITCHING TO
BYPASS
BREAKER
LOCKED
CLOSED
PANEL TYPE: NDP (UL 67 LISTED INTERIOR)
SERVICE: SEE TABLE ABOVE
ENCLOSURE TYPE: NEMA 1 (UL 50 LISTED ENCLOSURE)
BOX: 12 GAUGE PAINTED STEEL; NO KNOCKOUTS
TRIM: 12 GAUGE PAINTED STEEL; HELD TO BOX WITH
ADJUSTABLE TRIM CLAMPS – SURFACE MOUNTING
DOOR: EQUIPPED WITH CORBIN 15767 SNAP-LOCK
FINISH: ANSI 61 GRAY POLYESTER POWDER COAT APPLIED
TO SURFACES; TREATED WITH SEALER (IRON PHOSPHATE
AND CHROME FREE)
BUS: ELECTROLYTIC COPPER OF 98% CONDUCTIVITY, BASED
ON 1000 AMPS PER SQUARE INCH DENSITY
WIRE-BENDING GUTTER: MEETS OR EXCEEDS NEC TABLES
312-6(a), 312-6(b)
BREAKERS: CUTLER-HAMMER THERMAL-MAGNETIC, 3-POLE,
TRIP AS INDICATED; SEE TABLE ABOVE FOR AMPS AND KAIC
RATING
BREAKER TERMINAL LUG: (1) #14-1/0 PER PHASE
KEY INTERLOCK: KIRK TYPE F; BREAKERS ARE INTERLOCKED
SO AT LEAST ONE BREAKER IS ON AT ANY GIVEN TIME
DO NOT MISPLACE KEY – CHARGES WILL APPLY
KEY TRAPPED
IN INTERLOCK
For more information call
Tripp Lite Customer Service at
(773) 869-1234.
BREAKER
OPEN
UPS IN BYPASS
OPERATION
Tripp Lite has a policy of continuous improvement. Specifications are subject to
change without notice. Photos may differ slightly from actual product.
200806195