REDUNDANCY MODULE TSP-REM360 AND TSP

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600
Operating Instructions
Date: 06 April 2011
Jenatschstrasse 1 Tel: +41 43 311 4511 [email protected]
Fax: +41 43 311 4545 www.tracopower.com Issue: 3.0
CH-8002 Zürich
Page
Seite
1
Dimensions drawings:
TSP-REM360
Weight: 0.882lb
Gewicht: 0.40kg
Date: 06 April 2011
Jenatschstrasse 1 Tel: +41 43 311 4511 [email protected]
Fax: +41 43 311 4545 www.tracopower.com Issue: 3.0
CH-8002 Zürich
Page
Seite
2
Dimensions drawings:
TSP-REM600
Top view
Bottom view
Side view
Front view
Weight: 0.992lb
Gewicht: 0.45kg
Note
This instruction cannot claim all details of possible equipment variations, nor in particular can they provide for
every possible example of installation, operation or maintenance. Further information is available from your local
distributor office or from the TSP industrial power supply data sheet. Subject to change without prior notice.
In order to guarantee safe operation of the TSP-REM360 or TSP-REM600 in combination with the TSP
power supplies and to be able to make use of all the functions, please read these instructions thoroughly!
Date: 06 April 2011
Jenatschstrasse 1 Tel: +41 43 311 4511 [email protected]
Fax: +41 43 311 4545 www.tracopower.com Issue: 3.0
CH-8002 Zürich
Page
Seite
3
English
Warning
– POTENTIAL ELECTROSTATIC CHARGING HAZARD –
Prevent unintentional contact with a dry cloth.
Do NOT clean surfaces with a dry cloth!
Clean ONLY with a damp cloth
The TSP-REM360 and TSP-REM600 is designed and constructed in accordance with the safety requirements of IEC 60950-1,
EN 60950-1, UL 60950-1, Edition and is certified to IEC/EN/UL 60079-15 (protection type “n” Class I, Zone 2, AEx nA nC IIC
T4 Gc and Class I, Division 2, Group A,B,C,D.
The TSP-REM360 as well as the TSP-REM600 built-in modules are designed especially for use in process automation and
other industrial applications.
The power supply units are Unit Group II Category 3G components. They must be installed in an enclosure or cabinet rated
min. IP54. The enclosure / cabinet must comply with the requirements of EN60079-15:2005.
Components with dangerously high voltage and high stored energy are located in the device. However, these are inaccessible.
Failure to properly maintain the TSP-REM360 or TSR-REM600 can result in death, severe personal injury or substantial
property damage. The TSP-REM360 or TSPREM600 may only be installed and put into operation by qualified personnel.
The corresponding national regulations (e.g. UL, ANSI, VDE, DIN) must be observed. The successful and safe operation of
this module is dependent on proper storage, handling, installation and operation.
The potentiometer to adjust the output voltage is only allowed to be actuated using an insulated screwdriver, because
accidental contact may be made with parts inside the power supply carrying dangerous voltages.
Please observe following points before putting the device into operation:
 Read operating instructions thoroughly.
 That the input wiring is sufficiently dimensioned!
 That the output wiring is dimensioned according to the maximum output current or separately protected!
 Sufficient cooling is guaranteed!
 The temperature of the housing can become very high, depending on the ambient temperature and load.
Caution:
Risk of electrical shock and electrical discharge. The TSP-REM360 nor TSP-REM600 nor the power supply must not be
opened until at least 5 minutes after complete disconnection of the mains.
Electrostatic sensitive device. Qualified and trained personnel only may open the TSP-REM360 or TSP-REM600 or the
power supply.
Attention: In case of non-observance or exceeding the mentioned limiting value of the data sheet, the function and
electrical safety can be impaired and can destroy the TSP-REM360 or TSP-REM600 and/or the power supply.
Before installation ensure that the main switch is switched off and prevented from being switched
on again. In case of non-observance, touching of any live components or improper dealing with this
TSP-REM360 or TSP-REM600 or power supply can result in death or fatal injury.
Danger: Never work on the TSP-REM360 or TSP-REM600 or power supplies if power is applied!
1. Description and construction
With this TSP-REM modules and two power supplies of the TSP series (70, 90, 140, 180, 360 and 600 watt models) a highly reliable, true
redundant power system can be configured without any additional components. This module enforces the equivalent sharing of the output current
by each power supply. The system is fully redundant and provides the output power even if one power supply has completely failed e.g. by short
circuit on the output. In the event of either, one power supply failing or being disconnected, the second device will automatically supply the full
current to the load. The redundancy of the system is monitored and if lost, indicated by an alarm output. The inputs are hot swappable and can be
loaded up to 15A (TSP-REM360) or 25A (TSP-REM600) each. The output of the TSP-REM360 or TSP-REM600 should not be overloaded to
provide a proper n+1 redundancy system. The max output current is 15A (TSP-REM360) or 25A (TSP-REM600) as well.
Both TSP power supplies have to be adjusted to Vout = 24.00 – 24.05Vdc before connecting them to the TSP-REM360 or TSP-REM600.
Afterwards the connection between the TSP (TSP xxx-124) and Input 1 (see Fig 3.1; +Vin and –Vin; J1 pin 1 & pin 2 and chapter 2.2.1) as well as
Input 2 (see Fig 3.1; +Vin and –Vin; J1 pin 3 & pin 4 and chapter 2.2.1) and the remote sensing (see Fig. 3.1; J3 & J4) between these two devices
and the TSP-REM360 or TSP-REM600 using the wire supplied with the TSP-REM360 or TSP-REM600 modules can be made (see Fig. 2.1 and
Fig. 3.1, J4). Now the load can be connected to DC-Out (see Fig. 3.1, J2 pin 1, pin 2, pin 3 & pin 4 & chapter 2.2.2). The output voltage on the TSPREM360 or TSP-REM600 can be adjusted between 24 and 27Vdc using the potentiometer on the TSP-REM360 or TSP-REM600 (see Fig 3.1).
The TSP-REM360 and TSP-REM600 are built-in devices. The mounting position has to fulfil the requirements for fireproof case according to
UL60950-1, IEC/EN 60950-1 or other appropriate national standard. The relevant UL regulations or equivalent national regulations must be
observed during installation.
The TSP-REM360 and TSP-REM600 are designed for mounting on a DIN rail TS35 (DIN EN 50022-35x15/7.5).
The output voltage of the TSP-REM360 as well as of the TSP-REM600 is protected against short circuit and open circuit conditions.
2. Installation
A sufficiently strong DIN-rail has to be provided. The correct mounting position for optimal cooling performance must be observed. Above and
below the TSP-REMxxx modules a minimum free space of 80mm [3.15in] is required and on each side of the TSP-REMxxx modules a
minimum space of 50mm [1.97in] is required which allows air convection. The air temperature measured 10mm [0.39in] below the device must
not exceed the specified values in the data sheet. Observe same power derating above ambient temperatures of 40°C as specified for the
TSP power supplies.
Date: 06 April 2011
Jenatschstrasse 1 Tel: +41 43 311 4511 [email protected]
Fax: +41 43 311 4545 www.tracopower.com Issue: 3.0
CH-8002 Zürich
Page
Seite
4
English
2.1 Assembly
To fix device on the DIN-rail, hook top part of clip on DIN-rail, push down and inward until you hear a clipping sound.
To remove the device, pull the latch of the clip with the aid of an insulated flat head screwdriver. When clip has cleared bottom
DIN rail remove the screwdriver from recess. Lift the device off DIN-rail.
Wall mounting or chassis mounting can be achieved by use of optional mounting bracket TSP-WMK01 (1 bracket, see Fig. 4.1).
Remove the DIN-clips by removing the screw and place the mounting brackets in the same place as the DIN-clips. Use the
countersink screws, which are included with the wall mounting kit (1 countersink screw with TSP-WMK01) to fix the mounting
brackets on the TSP-REM360 or TSP-REM600 (tightening torque 0.8-0.9Nm).
2.2 Connecting cable
Only qualified personnel may carry out the installation. The device is equipped with COMBICON connector. This reliable
and easy-to-assemble connection method enables a fast connection of the device.
2.2.1 Input 1 and Input 2 (Fig. 3.1  Connector J1, pin 1, pin 2, pin 3 & pin 4):
The connection is made by using the –Vin and +Vin connections at Input 1 as well as at Input 2 and has to be carried out in
accordance with the local regulations. Sufficiently dimensioned wiring has to be ensured (see 2.2.1.1).
To achieve a reliable and shockproof connection strip the connecting ends according 2.2.1.1. If flexible wires are used the wires
have to be terminated. (e.g. by using ferrules)
2.2.1.1 Connections and terminal assignment
Device
TSP 090-124
TSP 180-124
TSP 360-124
TSP 600-124
Terminals
Function
–Vin & +Vin
–Vin & +Vin
+Vout & -Vout
Signal
–Vin & +Vin
–Vin & +Vin
+Vout & -Vout
Signal
–Vin & +Vin
–Vin & +Vin
+Vout & -Vout
Signal
Input 1 Input Voltage (24Vdc)
Input 2 Input Voltage (24Vdc)
Output Voltage (24Vdc)
Relay inputs and relay outputs
Input 1 Input Voltage (24Vdc)
Input 2 Input Voltage (24Vdc)
Output Voltage (24Vdc)
Relay inputs and relay outputs
Input 1 Input Voltage (24Vdc)
Input 2 Input Voltage (24Vdc)
Output Voltage (24Vdc)
Relay inputs and relay outputs
Solid or stranded wires
2
[mm ]
0.5 … 2.5
0.5 … 2.5
0.5 … 2.5
0.2 … 2.5
1.0 … 2.5
1.0 … 2.5
1.0 … 2.5
0.2 … 2.5
1.0 … 4.0
1.0 … 4.0
1.0 … 4.0
0.2 … 2.5
[AWG]
24 … 12
24 … 12
24 … 12
32 … 12
18 … 12
18 … 12
18 … 12
32 … 12
18 … 10
18 … 10
18 … 10
32 … 12
Torque
Stripping length
[Nm]
0.5 – 0.6
0.5 – 0.6
0.5 – 0.6
0.5 – 0.6
0.5 – 0.6
0.5 – 0.6
0.5 – 0.6
0.5 – 0.6
0.5 – 0.6
0.5 – 0.6
0.5 – 0.6
0.5 – 0.6
[mm]
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
2.2.2 Output (Fig. 3.1 Connector J2, pin 1, pin 2, pin 3 & pin 4):
The 24VDC connection is made using the “+Vout” and “-Vout“ connections. All output terminals should be connected to the load.
Make sure that all output lines are dimensioned according to the maximum output current (see 2.2.1.1) or are separately
protected! The wires on the secondary side should have large cross sections in order to keep the voltage drops on these lines
as low as possible.
To achieve a reliable and shockproof connection strip the connecting ends according 2.2.1.1. If flexible wires are used the wires
have to be terminated. (e.g. by using ferrules)
At the time of delivery, the output voltage is 24VDC. The output voltage can be set (using an insulated screwdriver) from 24 to
27VDC on the potentiometer (see Fig. 3.1).
The device is protected against overload and short circuit.
2.2.3 Signalling (Fig. 3.1 Connector J5, pin 1 & pin 2):
The DC OK outputs are for enabling monitoring of the functions of the two TSP power supplies. The floating DC OK signal
contacts (see Fig. 3.1  Connector J5, pin 1 & pin 2) is monitoring if the output voltage of the TSP power supplies, which are
connected to the TSP-REM360 Input 1 and Input 2 or TSP-REM600 Input 1 and Input 2, is present. If one of the devices is
disconnected or damaged, e.g. in the event of a power supplies internal short circuit, the alarm is generated. The contact on the
relay will switch off (relay contact  open). If both TSP power supplies provide at least an output voltage of 21.5Vdc the relay
contact is closed and signalise that both power supplies are in operation. If the output voltage of the TSP-REM360 or TSPREM600 is present the relay contact (30Vdc / 1A) is closed. It is detected by measuring the TSP-REM360 or TSP-REM600
input voltage at Input 1 as well as at Input 2.
2.2.4.1 Inputs-ON LED:
The Inputs-ON LED is a green colour LED that indicates the status of the TSP-REM360 or TSP-REM600 inputs and enables
visual evaluation of the function locally in the control cabinet. Inputs-ON LED green on – both TSP power supplies are supplying
the TSP-REM360 or TSP-REM600 with 24Vdc. Inputs-ON LED green off – one of the two or even both power supplies failed.
3. Function
3.1 Remote ON/OFF:
The TSP-REM360 as well as the TSP-REM600 devices provides an external remote on/off function by use of pin 3 & pin 4 at
connector J5 (see Fig. 3.1). To switch off the power supply and TSP-REM360 or power suply and TSP-REM600 a connection
between Connector J5 pin 3 and Connector J5, pin 4 by use of a switch or similar has to be made. At open connection between
J5 pin 3 and J5 pin 4 the device is providing the adjusted output voltage.
Date: 06 April 2011
Jenatschstrasse 1 Tel: +41 43 311 4511 [email protected]
Fax: +41 43 311 4545 www.tracopower.com Issue: 3.0
CH-8002 Zürich
Page
Seite
5
English
4. Compliance to UL508C
The TSP-REM360 is a is a built-in device and to comply with UL508C the device must be installed in a cabinet with minimum
dimensions of: 400mm (Width) x 500mm (Height) x 200mm (Depth)
4.1 Operating Temperature Ranges and load derating:
Depends on the TSP connected to the TSP-REM360. Please see operating temperature range and load derating at the TSP
power supplies datasheet or TSP operating instructions.
5. Technical Specifications
4.1 Input Specifications
Order code
Model
Input
max. Input Power
* Output Voltage
TSP-REM360
2 x 24 Vdc
2 x Control Input
2 x 360 Watt
24 Vdc
15.0 A
TSP-REM600
2 x 24 Vdc
2 x Control Input
2 x 600 Watt
24 Vdc
25.0 A
max. Output Current
* Output voltage adjustable
** Maximum current at Vout nom.
5.2 Output Specifications
Output Voltage adjustable Range with Potentiometer
Ripple and Noise (20MHz Bandwidth)
24 - 27 Vdc
at Vin nom und Iout max
Max. Capacitive Load
230mV pk-pk max
unlimited
5.3 General Specifications
Operating Temperature Range
Cooling
Storage Temperature Range
Load Derating above +40°C (104°F)
Humidity (non condensing)
Pollution Degree
Temperature Coefficient
Reliability, calculated MTBF
Remote ON/OFF
in accordance to IEC 61709
see Fig. 3.1
Alarm Relay Contact
Redundancy OK signal (Alarm)
Remote link cable (0.5m)
Case protection
in accordance to IEC 529
Isolation
Safety Standards
- Information Technology Equipment
according to
- Industrial Control Equipment
Electromagnetic compatibility
(EMC) Emissions
Electromagnetic compatibility
(EMC) Immunity
Environment
Vibration
Shock
Enclosure Material
Mounting
DIN-Rail mounting
Wall mounting
Connection
-25°C … +70°C
-13°F … +158°F
Convection cooling; no internal fan
-25°C … +85°C
-13°F … +185°F
According the load derating of TSP xxx-124 used
95% rel H max.
2
0.02%/K
>350'000 hours
2 pin connector (see Fig. 3.1; J5 pin 3 & pin 4)
connect via a switch  Contact closed = Device off
30Vdc / 1A
Trigger threshold at 18 - 22VDC,
Contact open if both inputs failed
2 cables included with TSP-REM360 module
IP20
See Safety Standards
IEC / UL / EN 60950-1
UL 508
in correspondence to connected units (no internal switching device
in correspondence to connected units (no internal switching device
IEC 60068-2-6
3 axis, sine sweep, 10 … 55Hz, 1g, 1oct/min.
IEC 60068-2-27
3 axis, 15g, half sine, 11ms
Aluminium (Chassis) / Zinc plated Steel (Cover)
For DIN-Rails as per EN 50022-35 x 15 / 7.5
(snap-on self-locking spring)
With wall mounting bracket
(see datasheet page 8)
Screw terminals
option TSP-WMK01
Date: 06 April 2011
Jenatschstrasse 1 Tel: +41 43 311 4511 [email protected]
Fax: +41 43 311 4545 www.tracopower.com Issue: 3.0
CH-8002 Zürich
Page
Seite
6
Block diagram TSP-REM360 and TSP-REM600
J1.2
J2.3
J2.4
J1.1
J2.1
J2.2
J3.1
J3.2
J1.4
J1.3
J4.1
J4.2
Fig.: 1.1
J5.1
J5.2
J5.3
J5.4
Connection of TSP-REM360 or TSP-REM600
Remote Link 2
Remote Link 1
Fig.: 2.1
Date: 06 April 2011
Jenatschstrasse 1 Tel: +41 43 311 4511 [email protected]
Fax: +41 43 311 4545 www.tracopower.com Issue: 3.0
CH-8002 Zürich
Page
Seite
7
Connectors of TSP-REM360 and TSP-REM600
Fig.: 3.1
J3
J4
Voltage control 1 Voltage control 2
for Input 1
for Input 2
J1
J2
Pin 1
Input 1 -Vin
GND (-)
S+
S+
DC-OK Signal
Pin 2
Input 1 +Vin
GND (-)
S-
S-
DC-OK Relay contact
Pin 3
Input 2 -Vin
Vout (+)
-
-
Remote ON/OFF
Pin 4
Input 2 +Vin
Vout (+)
-
-
Remote ON/OFF
J5
55.0 (2.16)
Wall mounting brackets (TSP-WMK01) for TSP-REM360
Fig.: 4.1
Date: 06 April 2011
Jenatschstrasse 1 Tel: +41 43 311 4511 [email protected]
Fax: +41 43 311 4545 www.tracopower.com Issue: 3.0
CH-8002 Zürich
Page
Seite
8