Power Supply, Primary Switch Mode for Universal Use QUINT-PS-100-240AC/12DC/10 QUINT POWER provides: • Preventive function monitoring through professional signaling • Global use due to a wide range input • A high level of operational safety even in complex global networks • Reliable startup of heavy loads due to POWER BOOST The reliability of a power supply determines the availability of individual components in a system and whether complex systems can function safely. The globalization of markets increases the demands placed on the power supply. A wide range input and a high level of availability are required. These requirements are met by Generation 2 QUINT POWER. 1. Short Description The QUINT POWER product range offers universal DC power supplies from 60 - 960 W. Depending on the type, regulated and adjustable output voltages of 12 V DC, 24 V DC or 48 V DC are available for output currents of 2.5 A, 5 A, 10 A, 20 A, 30 A, and 40 A. These devices, which are designed as primary switched-mode regulators, operate with a high level of efficiency so that the heat loss is kept to a minimum. The high level of operational safety is also ensured in complex global networks. QUINT POWER also operates in applications where static voltage dips, transient power supply failures or phase failure are common. Large capacitors ensure mains buffering of more than 20 ms at full load. All 3-phase QUINT POWER units provide the complete output power even in the event of a continuous phase failure. Reliable startup of heavy loads is ensured by a power reserve of up to 50% - the POWER BOOST. Preventive function monitoring diagnoses an impermissible operating state and minimizes downtimes in your system. An active transistor output and an electrically isolated relay contact are provided for remote monitoring of this state. This signal not only provides information on the device function, but also indicates a system overload at an early stage. 2. Area of Application QUINT POWER can be used globally due to the consistent provision of a wide range input. In this way, your entire system can be tested at any production location in the world and can be delivered to any location in the world without faulty switching of the input voltage. This reduces storage costs and logistical effort. An international approval package including CB Scheme, UL 60950 for IT equipment, and UL 508 for industrial control equipment enables the device to be used globally. Safe operation in adverse conditions is emphasized by the approval of all QUINT POWER units with 24 V output voltage by Germanischer Lloyd. Headquarters: © Phoenix Contact GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany Phone +49 - 52 35 - 30 0 • Fax +49 - 52 35 - 34 12 00 • www.phoenixcontact.com Local Contact: www.phoenixcontact.com/salesnetwork Power Supply, Primary Switch Mode for Universal Use – QUINT 12 V DC/10 A 3. Technical Data 125 mm (4.921 in.) L (+) 130 mm (5.118 in.) activ e PFC N (–) PE DC OK 13 14 85 mm (3.346 in.) QUINT 12 V DC/10 A 1 AC 7 Input Output Signal solid [mm2] flexible 0.2 - 2.5 0.2 - 2.5 0.2 - 2.5 0.2 - 2.5 0.2 - 2.5 0.2 - 2.5 AWG CB Schem U uB torque [Nm] [Ib in.] 25 - 14 0.5 - 0.6 4.4 - 5.3 25 - 14 0.5 - 0.6 4.4 - 5.3 25 - 14 0.5 - 0.6 4.4 - 5.3 Description Type Order No. Power Supply Primary switch mode for universal use QUINT-PS-100-240AC/12DC/10 29 38 81 1 Technical Data Input Data 1 Nominal input voltage Input voltage range Frequency Current consumption (for nominal values) Inrush current limiting/I2t (+25°C [+77°F]) Mains buffering for a nominal load (typical) Switch-on time after applying the mains voltage Transient surge voltage protection Input fuse, internal Recommended fuse 100 - 240 V AC (wide range input) 85 - 264 V AC 90 - 350 V DC 45 - 65 Hz 0 Hz 1.5 A (120 V AC)/0.6 A (230 V AC), approximately 15 A, approximately/1 A2s, approximately 50 ms <1s Varistor 6.3 AT (device protection) Circuit breaker 10 A or 16 A Characteristic B (EN 60 898) < 3.5 mA Discharge current for PE Output Data 2 Nominal output voltage UN/tolerance Setting range for the output voltage Output current (continuous) during convection cooling and nominal valuesPOWER BOOST IBOOST -25°C to +40°C (-13°F to +104°F) Nominal output current IN -25°C to +60°C (-13°F to +140°F) Derating Short-circuit current limit Startup of capacitive loads System deviation on: Load change static 10 - 90% Load change dynamic 10 - 90% Input voltage change ±10% Maximum power loss No load/nominal load Efficiency Response time UOUT (10% - 90%) Residual ripple/switching peaks (20 MHz) Can be connected in parallel Internal surge voltage protection Signal Output Data DC OK (active) 3 (Uout > 0.9 x UN = high signal) DC OK (electrically isolated) 4 (Uout > 0.9 x UN = contact closed) LED 6 (Uout < 0.9 x UN = LED flashing) 12 V DC ±1% 11.5 - 18.0 V DC 16 A (Uout = 18 V DC) 10 A (Uout = 18 V DC) From +60°C (+140°F), 2.5% per Kelvin IBOOST ≈ 16 A, approximately Unlimited < 1%, typical < 4%, typical < 0.1%, typical 4 W/22 W, approximately > 84% (for 230 V AC and nominal values) < 2 ms, typical < 100 mVpp (for nominal values) To increase redundancy and power Yes, limited to 25 V DC, approximately 25 V DC +12 V DC signal (with regard to the device weight) 40 mA, maximum 30 V AC/DC, maximum; 1 A, maximum Green LED PHOENIX CONTACT page 2 of 10 Pcs. Pkt. 1 Power Supply, Primary Switch Mode for Universal Use – QUINT 12 V DC/10 A General Data Insulation voltage: Input/output Input/PE Output/PE Approval package Electrical equipment of machines Safety transformers for switched-mode power supply units Electrical safety (of IT equipment) Industrial control equipment Equipping high voltage installations with electronic equipment Safety extra-low voltage Safe isolation Protection against electric shock Protection against dangerous shock currents, basic requirements for safe isolation in electrical equipment Limitation of harmonic line currents Mounting position Can be mounted with spacing LISTED EN 50 178 (VDE 0160) PELV (EN 60 204) SELV (EN 60 950) VDE 0100-410 DIN 57100-410 - Vertical Horizontal Degree of protection Class of protection MTBF Housing version Dimensions (W x H x D) + DIN rail Weight Climatic Data Ambient temperature Operation Storage Humidity Vibration Shock Degree of pollution Climatic category 4 kV AC (type test)/2 kV AC (routine test) 3.5 kV AC (type test)/2 kV AC (routine test) 500 V DC (routine test) CB Schem B EN 60 204 (Surge Voltage Category III) EN 61 558-2-17 EN 60950/VDE 0805, UL/C-UL Recognized UL 60 950 u UL/C-UL Listed UL 508 U according to IEC 68-2-6 according to IEC 68-2-27 DIN VDE 0106-101 According to EN 61000-3-2 On horizontal NS 35 DIN rail according to EN 50022 ≥ 5 cm (1.969 in.) 0 cm IP 20 Ι, with PE connection > 500 000 h according to IEC 1709 (SN 29 500) AluNox (AlMg1), closed Default upon delivery: Rotated 90°: (85 x 130 x 125 mm [3.346 x 5.118 x 4.921 in.])(122 x 130 x 88 mm [4.803 x 5.118 x 3.465 in.]) 1.3 kg, approximately -25°C to +70°C (-13°F to +158°F) (> +60°C [+140°F] derating) -40°C to +85°C (-40°F to +185°F) Up to 95% at +25°C (+77°F), no condensation < 15 Hz, amplitude ±2.5 mm/15 Hz - 150 Hz, 2.3 g, 90 minutes in resonant frequency 30 g all space directions 2 (according to EN 50 178) 3K3 (according to EN 60 721) c Conforms to the EMC Directive 89/336/EEC and the Low Voltage Directive 73/23/EEC EMC (Electromagnetic Compatibility) Noise Immunity According to EN 61000-6-2: 3) Electrostatic discharge (ESD) EN 61000-4-2 Housing Contact discharge: Air discharge: Electromagnetic HF field EN 61000-4-32) Fast transients (burst) EN 61000-4-43) Input: Output: Signal: Surge current loads EN 61000-4-53) Input: Housing Frequency: Field strength: Output: Signal: Conducted interference EN 61000-4-62) Voltage dips EN 61000-4-113) Simulation of radiophone EN 50204 I/O/S: Frequency: U0: Input: Frequency: Field strength: Requirements EN 61 000-6-2 QUINT-PS-100-240AC/12DC/10 4 kV 8 kV Level 4 8 kV 15 kV 80 - 1000 MHz 10 V/m Level 3 80 - 1000 MHz/1.4 - 2.0 GHz 10 V/m 2 kV 2 kV 1 kV asymmetrical5) asymmetrical5) asymmetrical5) 4 kV (Level 4) 2 kV (Level 3) 1 kV (Level 2) 2 kV 1 kV 0.5 kV 0.5 kV 1 kV asymmetrical5) symmetrical4) asymmetrical5) symmetrical4) asymmetrical5) 4 kV (Level 4) 2 kV (Level 4) 0.5 kV (Level 1) 0.5 kV (Level 1) 1 kV (Level 2) asymmetrical5) Level 3 0.15 - 80 MHz 10 V 0.15 - 80 MHz 10 V 30% reduction of the input voltage for 0.5 periods See input data: Mains buffering > 20 ms Not required 900 MHz/1800 MHz 20 V/m Noise Emission According to EN 50081-2: Radio interference EN 55011 Class A6) EN 55011 (EN 55022) Class B7) Radio interference EN 55011 Class A6) EN 55011 (EN 55022) Class B7) EN 55011 corresponds to CISPR11/EN 55022 corresponds to CISPR22 EN 61000 corresponds to IEC 1000 2) Criterion A: Normal operating characteristics within the specified limits. 3) Criterion B: Temporary adverse effects on the operating characteristics that the device corrects independently. 4) symmetrical: 5) Cable to cable asymmetrical: Cable to ground 6) Class 7) A: Class B: Industrial application Industrial and domestic applications PHOENIX CONTACT page 3 of 10 Power Supply, Primary Switch Mode for Universal Use – QUINT 12 V DC/10 A 4. Device View, Connections, and Control Elements 13 14 D OKC + + – – 13 1 D O 4 OC ut K 4 pu + tD C +– 1 2V – 10 A 7 3 DC QUINT POWER 2 13 13 O 14 D OKC + 14 D OC K ut pu + – – + tD +– C 1 2V DC O – 10 6 A K 11Adju .5- s 18 t V 5 AC In 1 pu L 00-2t 4 N 1 0V 5 Figure 04 1 AC input: Input voltage 85 - 264 V AC Frequency 45 - 65 Hz (0.2 mm2 to 2.5 mm2 solid) (0.2 mm2 to 2.5 mm2 flexible) (25 - 14 AWG) Internal fuse 6.3 AT Recommended fuse 10 A or 16 A c.b./Characteristic B 2 DC output: Output voltage 12 V DC (default), can be set from 11.5 -18.0 V DC using a potentiometer 5 (0.2 mm2 to 2.5 mm2 solid) (0.2 mm2 to 2.5 mm2 flexible) (25 - 14 AWG) The device is idling-proof and short-circuit-proof. 3 DC OK output active 4 DC OK output electrically isolated 5 Potentiometer (covered) 11.5 - 18.0 V DC 6 DC OK LED 7 Universal DIN rail adapter UTA 107 5. Safety and Warning Instructions QUINT POWER is a built-in device. Installation and startup must only be carried out by qualified personnel. The relevant country-specific regulations (e.g., VDE, DIN) must also be observed. Before startup it is particularly important to ensure that: • The mains have been connected correctly and protection is provided against electric shock. • The device can be switched off outside the power supply according to EN 60950 regulations (e.g., by the line protection on the primary side). • The protective conductor is connected. • All supply lines have sufficient fuse protection and are the correct size. • All output cables are the correct size for the maximum device output current or have separate fuse protection. • Sufficient convection is ensured. The housing temperature can reach high values depending on the ambient temperature and the load of the device. The device contains dangerous live components and high levels of stored energy. To ensure that the device can be operated safely and all functions can be used, please read these instructions carefully. Caution: Never carry out work when the power is turned on, this is highly dangerous. PHOENIX CONTACT page 4 of 10 Power Supply, Primary Switch Mode for Universal Use – QUINT 12 V DC/10 A 6. Installation 6.1. Mounting The power supply can be snapped onto all DIN rails according to EN 50022-35 and should be mounted horizontally (input terminal blocks facing downwards). 13 14 D OKC + + – – 13 1 D O 4 OC ut K pu tD + C +– 1 2V DC O – 10 A –2 K 11Adju .5-1 s 8Vt °C 60 + 40 °F 5…+1 -2 … 3 0 -1 95 4 5 L S RIA AL ST L OV DU RO NT PR AP U F IN NT ME COUIP EQKA 43 60 17 EN 60208-2EN 6155 EN 2 6000 1 61 1EN 5008 EN B ED ST LI in n ti o g ll a c ti n s ta e in o n n ad c R efo re be AC In 1 pu L 00-2t www.interface.phoenixcontact.com To ensure sufficient convection, we recommend a minimum spacing of 5 cm (1.969 in.) to other modules above and below the device. No minimum spacing to other modules at the sides is required for proper operation of the device. The housing temperature can reach high values depending on the ambient temperature and the load of the device. QUINT POWER Installation Dimensions ns ti o s u c in s tr m a to N 40V 5 Figure 05 Narrow mounting position: Installation depth 125 mm (4.921 in.) (+ DIN rail) 122 mm (4.803 in.) 50 mm (1.969 DC 13 14 OK ++– – Output DC 12V 10A DC OK Adjust 11.5-18V 130 mm (5.118 in.) QUINT POWER 230 mm (9.055 in.) 115 mm (4.528 in.) 85 mm (3.346 in.) Flat mounting position: Installation depth 88 mm (3.465 in.) (+ DIN rail) Input AC 100-240V L N 5 Figure 06 PHOENIX CONTACT page 5 of 10 Power Supply, Primary Switch Mode for Universal Use – QUINT 12 V DC/10 A 6.2. Narrow Mounting Position The device is supplied ex works for a narrow mounting position. Mounting: Place the module with the DIN rail guideway on the top edge of the DIN rail and then snap it downwards. Removal: Release the snap-on catch using a screwdriver and then detach the module from the bottom edge of the DIN rail. 6.3. Flat Mounting Position A flat mounting position can be achieved by mounting the module onto the DIN rail at a 90° angle. To do this, mount the DIN rail adapter (UTA 107) 7 as shown in Figure 08. No additional mounting material is required. Mounting screws: Torx T10 (torque 0.8 - 0.9 Nm/7 - 8 Ib in.). Mounting Removal Figure 07 Figure 08 PHOENIX CONTACT page 6 of 10 Power Supply, Primary Switch Mode for Universal Use – QUINT 12 V DC/10 A 6.4. Connection of Various Types of Network: 100 - 240 V AC Networks TN-S network TN-C network TT network L PEN L N PE L N QUINT MINI L N + – QUINT MINI MINI QUINT L N L + – L1 L2 L3 N PE N QUINT MINI + – L1 L2 L3 N L1 L2 L3 PEN L N MINI QUINT L1 L2 L3 PE L N L N +– IT network +– MINI QUINT L N +– MINI QUINT +– Figure 09 Connection Cable: The device is equipped with COMBICON connectors. This reliable user-friendly connection method enables quick device connection and safe isolation of the electrical connection, if required. Only operate connectors when the power is switched off. To maintain UL approvals, use copper cables, which are designed for operating temperatures of 75°C (167°F). 18 t V AC In 1 pu L 00-2t 4 The following cable cross sections can be connected: 1 Input: 2 Output: 3 Signal: Solid [mm2] 0.2 - 2.5 0.2 - 2.5 0.2 - 2.5 Flexible [mm2] 0.2 - 2.5 0.2 - 2.5 0.2 - 2.5 AWG Torque [Nm] [Ib in.] 25 - 14 0.5 - 0.6 4.4 - 5.3 25 - 14 0.5 - 0.6 4.4 - 5.3 25 - 14 0.5 - 0.6 4.4 - 5.3 To maintain EN 60950/UL60950, flexible cables require ferrules. 7 mm (0.28 in.) For reliable and safe-to-touch connection: Strip 7 mm (0.28 in.) from the connector ends. 6.5. Input (1, Figure 10) The 100 - 240 V AC connection is made using screw connections L and N. The device can be connected to single-phase AC networks or to two external conductors for three-phase networks (TN, TT or IT network according to VDE 0100 T300/IEC364-3) with nominal voltages of 100 - 240 V AC. Protecting the Primary Side The device must be installed according to the specifications of EN 60 950. It must be possible to switch off the device using a suitable disconnecting device outside the power supply. Note that an all-pole disconnecting device must be provided for two-phase operation using two external conductors for a three-phase network. For example, primary side line protection could be used. N 0V 5 Figure 10 Additional device protection is not required, as an internal fuse is present. Recommended Fuse: Circuit breaker 6 A or 10 A, Characteristic B (or equivalent). A suitable fuse must be fitted for DC applications. If the internal fuse is blown, this is most probably due to a device fault. In this case, the device should be checked in the factory. PHOENIX CONTACT page 7 of 10 Power Supply, Primary Switch Mode for Universal Use – QUINT 12 V DC/10 A Protecting the Secondary Side: The device is electronic short-circuit-proof and idlingproof. In the event of an error, the output voltage is limited to a maximum of 25 V DC. It should be ensured that all output cables are the correct size for the maximum output current or have separate fuse protection. The secondary side cables should have large cross sections to keep voltage drops on the cables to a minimum. 3 4 QUINT POWER 6.6. Output (Figure 11) The 12 V DC connection is made using the "+" and "–" screw connections on the screwconnection 2. The output voltage set upon delivery is 12 V DC. The output voltage can be adjusted from 11.5 to 18.0 V DC on the potentiometer 5. 13 14 D OKC + 2 + – – 13 1 D O 4 OC ut K pu + tD C +– 1 2V DC O – 10 A K 5 11Adj .5- us 18 t V P AP Signaling Both DC OK outputs are used for preventive function monitoring of the power supply. An electrically isolated signal contact 4 and an active DC OK signal 3 are available. In addition, the DC OK LED 6 can be used to evaluate the function of the power supply directly at the installation location. Active DC OK switching output (with reference to "-") Electrically isolated DC OK output ON Flashing OFF U = 12 V U = 0V U = 0V Closed Open Open Meaning Output voltage Output voltage No voltage at the greater than 90% less than 90% of output of the set voltage the set voltage Description Output voltage and current OK Output 12V DC 13 14 DC OK Green "DC OK" LED U Figure 11 + + – – DC OK QUINT POWER not operating, because: • No mains voltage present • Primary side fuse is blown • Device is faulty max. 30 VAC/DC, 1 A Figure 12 Electrically Isolated Contact (Figure 12) When opened, the electrically isolated signal contact indicates that the output voltage has fallen more than 10% below the set value. Signals and ohmic loads up to a maximum of 30 V and currents up to a maximum of 1 A can be switched. With heavy inductive loads, e.g., a relay, a suitable protective circuit (e.g., free-wheeling diode) is required. Active Signal Output (Figure 13) The 12 V DC signal is between the "DC OK" and "–" connection terminal blocks and can be loaded with 40 mA maximum. This signal output indicates that the output voltage has fallen more than 10% below the set value when "active high" changes to "low". The DC OK signal is isolated from the power output. This ensures that a separate supply does not enter from devices connected in parallel. The 12 V DC signal can be connected directly to a logic input for evaluation. Output 12V DC 13 14 12 V DC max. 40 mA PHOENIX CONTACT page 8 of 10 DC OK QUINT POWER operating, but: • Error at the load • Current consumption greater than IBOOST • Output short circuit + + – – DC OK Figure 13 Power Supply, Primary Switch Mode for Universal Use – QUINT 12 V DC/10 A Signal Loop (Figure 14) The two signal outputs mentioned above can be combined easily. DC OK LED The green DC OK LED enables local function evaluation in the control cabinet. LED ON LED flashing Normal operation of the power supply The output voltage has fallen by more than 10%. There is a secondary load short circuit or overload outside the POWER BOOST area. LED OFF No mains voltage is present or there is a device fault. Device 1 Device 2 13 14 Output 12V DC + + – – 12 V DC 40 mA 13 14 DC OK Output 12V DC DC OK Example: Monitoring two devices Use the active alarm output of device 1 and loop in the electrically isolated alarm output of device 2. In the event of an error, a group error message is generated. It is possible to loop any number of devices. This signal combination saves on wiring costs and logic inputs. + + – – DC OK Figure 14 7. Function 7.2. Temperature Response At an ambient temperature of up to +40°C (+104°F) the device continuously supplies an output current of 16 A. The device can supply a nominal output current of 10 A up to an ambient temperature of +60°C (+140°F). The output power must be decreased by 2.5% per Kelvin temperature increase for ambient temperatures above +60°C (+140°F). At ambient temperatures above +70°C (+158°F) or in the event of a thermal overload, the device does not switch off. The output power is decreased so low that device protection is provided. Once the device has cooled, the output power is increased again. UOUT [V] 240 W 360 W UN 12 < 60 °C < 40 °C 10 IN IOUT 16 IBOOST [A] Figure 15 UOUT = 12 V Output current [A] 7.1. Output Characteristic Curve At ambient temperatures Tamb < +40°C (+104°F), the device can continuously supply 16 A with a 12 V DC output voltage (Pout = 190 W). With heavy loads, the working point demonstrates the U/I characteristic curve shown in Figure 14. The output current is limited to IBOOST. The secondary voltage is reduced until the short circuit on the secondary side is removed. The U/I characteristic curve ensures that both heavy capacitive loads and devices with DC/DC converters can be supplied by QUINT POWER in the input circuit without any problems. Connected fuses are reliably tripped. The selectivity in your system configuration is ensured at all times. 16 10 0 0 20 40 60 Ambient temperature [°C] Figure 16 PHOENIX CONTACT page 9 of 10 Power Supply, Primary Switch Mode for Universal Use – QUINT 12 V DC/10 A 7.4. Redundancy Operation (Figure 17) Redundant connections are designed for supplying systems, which place particularly high requirements on operational safety. If a fault occurs in the primary circuit of device 1, device 2 automatically takes over the complete power supply without interruption and vice versa. For this purpose, the power supplies to be connected in parallel must be large enough that the total current requirements of all loads can be fully met by one power supply. External decoupling diodes are required for 100% redundancy. QUINT 10 A + – QUINT 10 A + – + – + – Σ = 10 A Figure 17 QUINT 10 A + – QUINT 10 A + – + – Σ = 20 A Figure 18 PHOENIX CONTACT 12/15/02 TNR: 5107830-00 7.5. Power Increase (Figure 18) The output current can be increased to n x IN where n is the number of devices connected in parallel. The parallel connection for power increase can be used to extend existing systems. A parallel connection is recommended if the power supply does not cover the current consumption of the most powerful load. Otherwise, the loads should be divided over independent individual devices. A maximum of five devices can be connected in parallel. + – http://www.phoenixcontact.com 7.3. Parallel Operation Devices of the same type can be connected in parallel to increase both redundancy and power. The default setting does not have to be adjusted. If the output voltage is adjusted, an even current distribution can be ensured by precisely setting all power supplies that are operated in parallel to the same output voltage. To ensure symmetrical current distribution we recommend that all cable connections from the power supply to the DIN rail are the same length and have the same cross section. Depending on the system, for parallel connection of more than two power supplies a protective circuit should be installed at each individual device output (e.g., decoupling diode or DC fuse). This means that in the event of a secondary device fault high return currents are avoided. PHOENIX CONTACT page 10 of 10