LPD70 Series - Teledyne Relays

LPD70 Series
250mA, 28Vdc Optically Isolated
Dual Relay
Part Number
Description
LPD70
250mA, 28Vdc dual solid-state relay
MECHANICAL SPECIFICATION
FEATURES/BENEFITS
• Current limiting output
• Thermal protection
• Automatic recovery
• Overload protection
• Dual output: Two relays in one package
• Low voltage drop
MAXIMUM
Figure 1 – LPD70 relay; dimensions in inches (mm)
Tolerances are +/- .005 inch (.127) unless otherwise
specified
INPUT (CONTROL) SPECIFICATIONS
(–40 to 85°C)
Min
Max
Units
Control Voltage Range
(See Note 1)
4.0
7.0
Vdc
Input Current @ 5 Vdc (See Fig 2)12
mA
Must Turn-On Voltage
Vdc
4
Must Turn-Off Voltage
0.8
Vdc
Must Turn-Off Current
50
µA
Reverse Voltage
–7
DESCRIPTION
The LPD70 is a dual-output 28Vdc plastic relay with
internal thermal protection. The relay utilizes optical
isolation to provide excellent input-to-output isolation.
The LPD70 offers a current limiting output to protect
itself and associated load circuits from transient current
overloads. During an overcurrent condition, the LPD70
clamps the current to a safe operating value. The
LPD70 also offers thermal protection. The thermal
protection is activated by junction temperature. In case
of an overload or shorted load condition, the thermal
protection limits the junction temperature. The LPD70
returns to normal operation automatically once the
overload is removed.
Vdc
)NPUT#URRENTM!
)NPUT6OLTAGE6DC
INPUT CURRENT VS. INPUT VOLTAGE
Figure 2
© 2007 TELEDYNE RELAYS
(800) 284-7007 • www.teledynerelays.com
Page 2DSLPD70 Rev. B
LPD70 Series
250mA, 28Vdc Optically Isolated
Dual Relay
OUTPUT (LOAD) SPECIFICATIONS
Min Max Units
Load Voltage Rating
33
Vdc
Load Current (See Fig 6)
0.25
A
Transient Voltage 80
Vdc
Transient Supply Voltage
with Load shorted (5 sec max)
46
Vdc
Output Capacitance @ 25Vdc
200
pF
On-State Voltage Drop (See Fig 4)
0.5
Vdc
On Resistance
2.0
Ohm
Off-State Leakage Current (33Vdc)10
µA
Turn-On Time
2.5
ms
Turn-Off Time1
ms
Overload Current Limit (See Fig 5)
0.9
2%,!9!
).
/54
n
0). 2%,!9"
n
).
/54
n
n
6DC
6
A
,OAD
!
6SUPPLY
6DC
4YPICAL
,OAD
"
6
OVERLOAD/THERMAL PROTECTION
SPECIFICATIONS (NOTE 8)
TYPICAL WIRING DIAGRAM
Figure 3
Min Typical Max Units
°C
Activation Time (See Fig. 7, Note7) 70
mArms
ms
,OAD#URRENT!
ENVIRONMENTAL SPECIFICATIONS
Min
Max
Units
Operating Temperature
–40
+85
°C
Storage Temperature
–55
+100
°C
Junction Temperature 100
°C
°C/W
Shock1500
g
Vibration100
g
500
Vac
Insulation Resistance
(@500 Vdc)109
Ohm
Resistance to
Soldering Heat
5
MIL STD 202, method 208
Thermal Shock
MIL STD 202, method 107
HAST
JEDEC Test Method A110
130°C 85% RH, no power applied, 50 hours
/UTPUT6OLTAGE$ROP6
LOAD CURRENT VS. OUTPUT VOLTAGE DROP
OVER TEMPERATURE
Figure 4
pF
Solder Dip, 10 seconds at +260°C
MIL STD 202, method 210
Solderability
/VERLOAD#URRENT,IMIT!
Isolation
Thermal Resistance
(Junction to Ambient) each relay120
Dielectric Strength
o#
6
0
Output Current (after 120 sec)
Vdc
o#
33
Junction Activation150
Temperature
o#
Output Load Voltage
n
n n n n !MBIENT4EMPERATURE #
TYPICAL OVERLOAD CURRENT VS. TEMPERATURE
Figure 5
Page Specifications UNDER REVISION CONTROL
© 2007 TELEDYNE RELAYS
2DSLPD70 Rev. B
LPD70 Series
250mA, 28Vdc Optically Isolated
Dual Relay
THEORY OF OPERATION
LPD70 relays operate with 0.25 amp loads from –40° to +85°C.
Overloads are current-limited to about 0.6 amps. A temperature
sense circuit in intimate contact with the output power switch
opens the switch at elevated junction temperatures. This thermal
shutdown results in a periodic cycling of the output switch, with
the overload current decaying over time. Once the overload is
removed, the relay returns to normal operation. The LPD70 relay
survives overloads, including shorted loads, at load voltages up
to 33Vdc.
,OAD#URRENT!
n
n
!MBIENT4EMPERATURE #
LOAD CURRENT VS. AMBIENT TEMPERATURE
Figure 6
/UTPUT#URRENTWITH,OAD3HORTED
!MPS
SECONDS
Activation Time
-ILLISECONDS
TYPICAL OVERLOAD CURRENT VS. TIME
Figure 7
).
).054WITH
,%$
n).
/PTICAL
)SOLATION
$ETECTION
#IRCUIT
NOTES
1.For input voltages greater than 7 volts, use an external
resistor in series with the relay input. Rext. = (Vin–7 Vdc)/0.012
Amps
2.Relay input voltage transitions should be less than 1.0
millisecond.
3.Above approximately 0.6 Amps load (overload), the relay
becomes current limited. In this mode of operation, the
voltage across the relay contacts is: Vcontact ≅ Vsupply – [(0.6
Amp) (Rload)]
The relay will limit current in an overload condition until the
overload is removed.
4.Maximum load current ratings are with the relay in free air
and soldered to a printed circuit board.
5.Loads may be attached to either the positive or negative
output terminal.
6.Timing is measured from the input voltage transition to the
10% or 90% points on the output voltage transition.
7.Activation time is the time for the thermal protection circuit to
take effect.
8.The LPD70 relay withstands shorted Loads at 33 Vdc
Max supply voltage indefinitely, and survives shorted load
conditions at 46 Vdc Max Supply Voltage for 5 seconds Max.
4URN/FF
4IMING
#IRCUIT
/UTPUT3WITCH
-/3&%4
WITH#URRENT
,IMIT
/54
n/54
4EMPERATURE
3ENSE
FUNCTIONAL BLOCK DIAGRAM
Figure 8
© 2007 TELEDYNE RELAYS
(800) 284-7007 • www.teledynerelays.com
Page 2DSLPD70 Rev. B