RUC industrial relays of small dimensions with adaptor (H) Number and type of contacts Contact material Rated / max. switching voltage AC Min. switching voltage Rated load AC1 DC1 Min. switching current Max. inrush current Rated current Max. breaking capacity AC1 Min. breaking capacity Contact resistance Max. operating frequency • at rated load AC1 • no load 2 CO, 3 CO, 2 NO, 3 NO 2 NO, 3 NO with contact gap 3 mm AgCdO, AgNi 400 V / 440 V 230 V / 250 V ❶ 5 V AgNi, 10 V AgCdO 16 A / 250 V AC or 10 A / 400 V AC 16 A / 250 V AC ❶ 16 A / 24 V DC (see Fig. 3) 5 mA AgNi, 10 mA AgCdO 40 A 16 A 4 000 VA 0,3 W AgNi, 1 W AgCdO 100 m Rated voltage AC DC Must release voltage Operating range of supply voltage Rated power consumption AC DC 6 ... 240 V 50/60 Hz 6 ... 220 V AC: 0,15 Un see Tables 1, 2, 3, 4 2,8 VA 50 Hz 1,5 W Insulation rated voltage Rated surge voltage Overvoltage category Insulation pollution degree Dielectric strength contacts Contact - coil distance 400 V AC 4 000 V 1,2 / 50 µs III 2 2 500 V AC type of insulation: basic 1 500 V AC type of clearance: micro-disconnection 2 500 V AC with contact gap 3 mm, type of clearance: full-disconnection 2 500 V AC type of insulation: basic 5 mm 2 CO, 2 NO 4 mm 3 CO, 3 NO 8 mm 2 CO, 2 NO 5 mm 3 CO, 3 NO Coil data Insulation according to PN-EN 60664-1 General data • between coil and • contact clearance • pole - pole • clearance • creepage Operating / release time (typical values) Electrical life • resistive AC1 • cos Mechanical life (cycles) Motor load according to UL 508 Dimensions (L x W x H) Weight Ambient temperature Cover protection category Shock / vibration resistance Solder bath temperature Soldering time • storage • operating 1 200 cykli/h 12 000 cykli/h 6 ... 400 V 50 Hz ❶ DC: 0,1 Un 2,5 VA 60 Hz 1,7 W with contact gap 3 mm 20 ms / 15 ms > 105 16 A, 250 V AC > 105 10 A, 400 V AC see Fig. 2 > 107 2 CO: 0,33 HP 120 V AC, single-phase motor 0,5 HP 240 V AC, single-phase motor 3 CO: 0,33 HP 120 V AC, single-phase motor 0,5 HP 240 V AC, single-phase motor 3 CO: 0,5 HP 240 V AC, three-phase motor RUC faston 4,8 x 0,5 ❷ RUC faston 6,3 x 0,8 ❸ 80 g ❹ 85 g ❺ -40...+85 oC AC: -40...+55 oC 3 CO, 3 NO / 16 A(+70 oC 2 CO, 2 NO / 16 A) DC: -40...+55 oC 3 CO, 3 NO / 16 A(+70oC3CO,3NO/10A;2CO,2NO/16A) IP 00 PN-EN 60529 10 g / 5 g 10...150 Hz max. 270 oC max. 5 s The data in bold type pertain to the standard versions of the relays. ❶ For RUC faston 4,8 x 0,5 with GUC11 socket, max. switching voltages and coil voltages of relays are limited to 250 V AC / DC. ❷ For plug-in sockets version: 36,1 x 38,6 x 45,5 mm. For version: with (V) adaptor: 58,75 x 38,6 x 45,9 mm; with (H) adaptor: 46,8 x 38,6 x 62,45 mm. For version with mounting flange: 66,3 x 38,6 x 36,1 mm. For PCB version: 36,1 x 38,6 x 52,5 mm. ❸ For version: with (V) adaptor: 62,4 x 38,6 x 45,9 mm; with (H) adaptor: 46,8 x 38,6 x 66,1 mm. For version with mounting flange: 66,3 x 38,6 x 36,1 mm. ❹ Weight of plug-in sockets version and PCB version (RUC faston 4,8 x 0,5). ❺ Weight of version with (V) or (H) adaptor, and version with mounting flange. Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected] www.relpol.com.pl 28.01.2014 with adaptor (V) Contact data • Power relays of general application • AC and DC coils • Mounting: in sockets; 35 mm rail mount acc. to PN-EN 60715; on panel; PCB • Versions: faston 187 (4,8 x 0,5 mm); faston 250 (6,3 x 0,8 mm) • 3 mm contact gap (option - only in versions with normally open contacts) • Additional features: K - test button; L - light indicator (LED) • Applications: control of electromagnets; systems of heating, cooling, ventillation, air conditioning; control with single-phase and three-phase motors; catering industry machines and equipment; automation systems; photoelectric systems; etc. • Recognitions, certifications, directives: RoHS, 1 RUC industrial relays of small dimensions Coil data - DC voltage version Coil code Table 1 Rated voltage V DC Coil resistance at 20 °C Acceptable resistance Coil operating range V DC min. (at 20 °C) max. (at 55 °C) 1006 6 28 ± 10% 4,8 6,6 1012 12 110 ± 10% 9,6 13,2 1024 24 430 ± 10% 19,2 26,4 1042 42 1 340 ± 10% 33,6 46,2 1048 48 1 750 ± 10% 38,4 52,8 1060 60 2 700 ± 10% 48,0 66,0 1110 110 9 200 ± 10% 88,0 121,0 1120 120 11 000 ± 10% 96,0 132,0 1220 220 37 000 ± 10% 176,0 242,0 The data in bold type pertain to the standard versions of the relays. Coil data - DC voltage version, reinforced Coil code ❻ Rated voltage V DC W012 12 W024 W048 Table 2 Coil resistance at 20 °C Acceptable resistance Coil operating range V DC min. (at 20 °C) max. (at 55 °C) 85 ± 10% 9,6 13,2 24 345 ± 10% 19,2 26,4 48 1 370 ± 10% 38,4 52,8 W110 110 7 300 ± 10% 88,0 121,0 W220 220 30 000 ± 10% 176,0 242,0 ❻ For version with contact gap 3 mm. Coil data - AC 50/60 Hz voltage version, basic Rated voltage V AC Coil resistance at 20 °C Acceptable resistance Coil operating range V AC min. (at 20 °C) max. (at 55 °C) 5006 6 4,3 ± 10% 4,8 6,6 5012 12 18,5 ± 10% 9,6 13,2 5024 24 75 ± 10% 19,2 26,4 5115 115 1 840 ± 10% 92,0 126,5 5120 120 1 910 ± 10% 96,0 132,0 5220 220 6 980 ± 10% 176,0 242,0 5230 230 7 080 ± 10% 184,0 253,0 5240 240 7 760 ± 10% 192,0 264,0 Coil data - AC 50 Hz voltage version, special Coil code Rated voltage V AC Table 4 Coil resistance at 20 °C Acceptable resistance Coil operating range V AC min. (at 20 °C) max. (at 55 °C) 3006 6 4,8 ± 15% 4,8 6,6 3012 12 20 ± 15% 9,6 13,2 3024 24 72 ± 15% 19,2 26,4 3115 115 2 100 ± 15% 92,0 126,5 3120 120 2 300 ± 15% 96,0 132,0 3220 220 7 000 ± 15% 176,0 242,0 3230 230 7 900 ± 15% 184,0 253,0 3240 240 8 300 ± 15% 192,0 264,0 3400 400 21 500 ± 10% 320,0 440,0 28.01.2014 Coil code Table 3 2 Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected] www.relpol.com.pl RUC industrial relays of small dimensions Fig. 1 Electrical life reduction factor at AC inductive load Fig. 2 Reduction factor Number of cycles N Electrical life at AC resistive load. Switching frequency: 1 200 cycles/hour Breaking capacity [kVA] DC current [A] Max. DC breaking capacity A -resistive load DC1 B -inductive load L/R = 40 ms DC voltage [V] Fig. 3 Connection diagrams (pin side view) 2 CO 2 NO 3 CO 3 NO Dimensions - RUC faston 4,8 x 0,5 - PCB version 28.01.2014 11 52,5 Dimensions - RUC faston 4,8 x 0,5 - plug-in version (standard) Power factor N - electrical life at AC1 3 Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected] www.relpol.com.pl RUC industrial relays of small dimensions Dimensions - RUC faston 4,8 x 0,5 - version with vertical adaptor (V) Dimensions - RUC faston 4,8 x 0,5 - version with horizontal adaptor (H) 9,8 46,8 12 1,6 34,8 8,5 35,5 9,8 9,8 6,1 12 4,9 55,3 34,8 1,6 Dimensions - RUC faston 6,3 x 0,8 - version with vertical adaptor (V) Dimensions - RUC faston 6,3 x 0,8 - version with horizontal adaptor (H) Dimensions - RUC faston 4,8 x 0,5 (faston 6,3 x 0,8) - version with mounting flange in the wall of the cover Mounting 4,8 x 0,5 * (6,3 x 0,8) 7,15 (10,8) * 66,3 60,7 * - dimensions RUC faston 6,3 x 0,8 Relays RUC are offered in versions: • standard, for screw terminals plug-in sockets GUC11 ❶ with clip MBA, 35 mm rail mount acc. to PN-EN 60715 or on panel mounting with two M3 screws • with mounting flange in the wall of the cover, on panel mounting with two M4 screws, flat insert connectors - faston 187 (4,8 x 0,5 mm) or faston 250 (6,3 x 0,8 mm) • with vertical (V) or horizontal (H) adaptors for direct mounting on 35 mm rail mount acc. to PN-EN 60715, flat insert connectors - faston 187 (4,8 x 0,5 mm) or faston 250 (6,3 x 0,8 mm) • for direct PCB mounting ❼. ❼ Relays unavailable with (V) or (H) adaptor, and cover with mounting flange. ❶ For RUC faston 4,8 x 0,5 with GUC11 socket, max. switching voltages and coil voltages of relays are limited to 250 V AC / DC. Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected] www.relpol.com.pl 28.01.2014 8,2 4 RUC industrial relays of small dimensions Ordering codes Cover protection category Type Contact material Number and type of contacts R U C — Connection mode — Coil code — Additional features — Contact material 10 - AgCdO 20 - AgNi see Tables 1, 2, 3, 4 page 2 Number and type of contacts 12 - 2 CO 13 - 3 CO 22 - 2 NO 23 - 3 NO 52 - 2 NO, contact gap 3 mm ❽ 53 - 3 NO, contact gap 3 mm ❽ Cover protection category 2 - in cover, IP 00 version ❾ 4 - in cover with mounting flange, IP 00 version V - in cover with vertical adaptor, IP 00 version H - in cover with horizontal adaptor, IP 00 version Connection mode 5 - for PCB 6 - for flat insert connectors - faston 187 (4,8 x 0,5 mm) and for plug-in sockets A - for flat insert connectors - faston 250 (6,3 x 0,8 mm) Additional features without marks - without additional features K - test button without block function ❿ L - light indicator (LED diode) KL - test button without block function + light indicator (LED diode) ❿ ❽For versions with reinforced DC coils: W012, W024, W048, W110, W220 and with AC coils. ❾For relays RUC: for plug-in sockets; for PCB. ❿Additional features is not available in versions of relays with contact gap 3 mm. Examples of ordering codes: relay RUC, faston 187 (4,8 x 0,5 mm), with contact gap 3 mm, for plug-in sockets GUC11, three normally open contacts, contact material AgNi, reinforced coil voltage 24 V DC, in cover IP 00 RUC-2013-V6-3400-KL relay RUC, faston 187 (4,8 x 0,5 mm), for flat insert connectors, with vertical adaptor (V), three changeover contacts, contact material AgNi, coil voltage 400 V AC 50 Hz, with test button without block function and light indicator (LED diode), in cover IP 00 RUC-2052-HA-W220-Lrelay RUC, faston 250 (6,3 x 0,8 mm), for flat insert connectors, with contact gap 3 mm, with horizontal adaptor (H), two normally open contacts, contact material AgNi, reinforced coil voltage 220 V DC, with light indicator (LED diode), in cover IP 00 RUC-1022-25-5024relay RUC, for PCB, two normally open contacts, contact material AgCdO, coil voltage 24 V AC 50/60 Hz, in cover IP 00 28.01.2014 RUC-2053-26-W024 5 Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected] www.relpol.com.pl Plug-in sockets and accessories GUC11 ❽ Connection diagram Dimensions For RUC faston 4,8 x0,5, RUC-M Screw terminals Max. tightening moment for the terminal: 0,7 Nm 35 mm rail mount acc. to PN-EN 60715 or on panel mounting 82 x 42,2 x 26,5 mm Three poles 16 A, 250 V AC Accessories MBA ❽For RUC faston 4,8 x 0,5 and RUC-M, with GUC11 socket, max. switching voltages and coil voltages of relays are limited to 250 V AC / DC. GUC11 PRECAUTIONS: 1. Ensure that the parameters of the product described in its specification provide a safety margin for the appropriate operation of the device or system and never use the product in circumstances which exceed the parameters of the product. 2. Never touch any live parts of the device. 3. Ensure that the product has been connected correctly. An incorrect connection may cause malfunction, excessive heating or risk of fire. 4. In case of any risk of any serious material loss or death or injuries of humans or animals, the devices or systems shall be designed so to equip them with double safety system to guarantee their reliable operation. 28.01.2014 Screw terminals plug-in sockets for RUC faston 4,8x0,5, RUC-M 6 Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected] www.relpol.com.pl