RUC-M

RUC-M
industrial relays for DC loads
140
with adaptor (V)
with adaptor (H)
Contact data
Number and type of contacts
Contact material
Rated / max. switching voltage
Min. switching voltage
Rated load (capacity)
DC1
DC L/R=40 ms
AC1
Min. switching current
Max. inrush current
Rated current
Min. breaking capacity
Contact resistance
Max. operating frequency
• at rated load
• no load
• Magnetic blow-out relays for high DC load with the contact plate
with permanent magnet whose magnetic field blows out the
electric arc between the contacts • AC and DC coils • Mounting:
in sockets; 35 mm rail mount acc. to PN-EN 60715; on panel; PCB •
Version: faston 187 (4,8 x 0,5 mm) • Contact gap: 3 mm (version 2 NO);
6 mm (version 1 NO) • Additional features: L - light indicator (LED)
• Applications: control of electromagnets; systems of heating, cooling,
ventillation, air conditioning; control with single-phase and three-phase
motors; catering industry machines and equipment; automation systems;
etc. • Recognitions, certifications, directives: RoHS,
1 NO (double-break)
2 NO
AgCdO
250 V DC, AC / 350 V DC; 440 V AC ❶
10 V
16 A / 24 V DC; 14 A / 110 V DC
16 A / 24 V DC; 10,5 A / 110 V DC
12 A / 220 V DC
4,5 A / 220 V DC
16 A / 24 V DC; 5,4 A / 110 V DC 16 A / 24 V DC; 1,35 A / 110 V DC
3 A / 220 V DC
0,45 A / 220 V DC
16 A / 250 V AC
16 A / 250 V AC
10 mA
40 A 20 ms
16 A
1W
≤ 100 mΩ
AC1
1 200 cycles/hour
12 000 cycles/hour
AC
DC
12 ... 240 V 50/60 Hz
12 ... 220 V
AC: ≥ 0,15 Un
AC: 0,85...1,1 Un
2,8 VA
1,7 W
Coil data
Rated voltage
Must release voltage
Operating range of supply voltage
Rated power consumption
AC
DC
DC: ≥
0,1 Un
DC: 0,8...1,1
Un
see Tables 1, 2
Insulation according to PN-EN 60664-1
Insulation rated voltage
Rated surge voltage
Overvoltage category
Insulation pollution degree
Dielectric strength • between coil and contacts
• contact clearance
• pole - pole
Contact - coil distance
• clearance
• creepage
400 V AC
4 000 V
1,2 / 50 µs
III
3
2 500 V AC type of insulation: reinforced
4 000 V AC type of clearance: full-disconnection
2 500 V AC contacts 2 NO, type of insulation: basic
≥ 6,3 mm
≥ 8 mm
General data
Operating / release time (typical values)
Electrical life
• resistive DC1
• DC L/R=40 ms
Mechanical life (cycles)
Dimensions (L x W x H)
Weight
Ambient temperature
• storage
• operating
Cover protection category
Shock resistance
Vibration resistance
Solder bath temperature
Soldering time
20 ms / 15 ms
≥ 2 x 105 12 A, 220 V DC
≥ 2 x 105 3 A, 220 V DC
≥ 2 x 107
36,1 x 38,6 x 45,5 mm ❷
80 g ❸
85 g ❹
-40...+85 oC
-40...+70 oC
IP 00
PN-EN 60529
10 g
5 g 10...150 Hz
max. 270 oC
max. 5 s
≥ 2 x 105 4,5 A, 220 V DC
≥ 2 x 105 0,45 A, 220 V DC
The data in bold type pertain to the standard versions of the relays.
❶ For RUC-M with GUC11 socket, max. switching voltages and coil voltages of relays are limited to 250 V AC/DC.
❷ For plug-in sockets version. For version: with (V) adaptor: 58,75 x 38,6 x 45,9 mm; with (H) adaptor: 46,8 x 38,6 x 62,45 mm.
For version with mounting flange: 66,3 x 38,6 x 36,1 mm. For PCB version: 36,1 x 38,6 x 52,5 mm.
❸ Weight of plug-in sockets version and PCB version. ❹ Weight of version with (V) or (H) adaptor, and version with mounting flange.
www.relpol.com.pl
Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900
RUC-M
industrial relays for DC loads
141
Coil data - DC voltage version, reinforced
Coil code
Rated voltage
V DC
Table 1
Coil resistance
±10% at 20°C
Ω
Coil operating range
V DC
min. (at 20°C)
max. (at 55°C)
W012
12
85
9,6
W024
24
345
19,2
13,2
26,4
W048
48
1 370
38,4
52,8
W110
110
7 300
88,0
121,0
W220
220
30 000
176,0
242,0
Coil data - AC 50/60 Hz voltage version
Coil code
Rated voltage
V AC
Table 2
Coil resistance
±10% at 20°C
Ω
Coil operating range
V AC
min. (at 20°C)
max. (at 55°C)
5012
12
18,5
9,6
13,2
5024
24
75,0
19,2
26,4
5115
115
1 840,0
92,0
126,5
5120
120
1 910,0
96,0
132,0
5230
230
7 080,0
184,0
253,0
5240
240
7 760,0
192,0
264,0
1 NO
1 NO
2 NO
2 NO
Design
Permanent magnet
fixed in the contact
plate to perform the
function of the so-called
”magnetic blow-out”.
Its magnetic field
is directed to the contact
set and blows out
the electric arc which
appears at switching
off the DC load.
Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900
www.relpol.com.pl
RUC-M
industrial relays for DC loads
142
1 NO
2 NO
1 NO
2 NO
1 NO
2 NO
1 NO
2 NO
Mounting
Relays RUC-M are offered in versions: • standard, for screw terminals plug-in sockets GUC11 ❶ with clip MBA,
35 mm rail mount acc. to PN-EN 60715 or on panel mounting with two M3 screws • with mounting flange in the wall
of the cover, on panel mounting, flat insert connectors - faston 187 (4,8 x 0,5 mm) • with vertical (V) or horizontal (H)
adaptors for direct mounting on 35 mm rail mount acc. to PN-EN 60715, flat insert connectors - faston 187 (4,8 x 0,5 mm)
• for direct PCB mounting ❺.
❺ Relays are not available with (V) or (H) adaptor, and cover with mounting flange.
❶ For RUC-M with GUC11 socket, max. switching voltages and coil voltages of relays are limited to 250 V AC/DC.
www.relpol.com.pl
Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900
RUC-M
industrial relays for DC loads
143
AC1
Ordering codes
Cover protection
category
Type
Contact
material
R U C – M —
Number and type
of contacts
Connection
mode
—
Coil code
Additional
features
—
—
Contact material
10 - AgCdO
Number and type of contacts
51 - 1 NO (double-break), contact gap ≥ 6 mm (3 +3)
52 - 2 NO, contact gap ≥ 3 mm
see Tables 1, 2 page 141
Cover protection category
24VH-
in cover, IP 00 version
in cover with mounting flange, IP 00 version
in cover with vertical adaptor, IP 00 version
in cover with horizontal adaptor, IP 00 version
Connection mode
5 - for PCB
6 - for flat insert connectors - faston 187 (4,8 x 0,5 mm)
and plug-in sockets
Additional features
without marks - without additional features
L - light indicator (LED diode)
Examples of ordering codes:
RUC-M-1051-26-W024
relay RUC-M, faston 187 (4,8 x 0,5 mm), contact material AgCdO, with one normally open
contact (double-break), with contact gap ≥ 6 mm (3+3), in cover IP 00, for plug-in sockets
GUC11, voltage version 24 V DC - reinforced coil
RUC-M-1052-V6-5230-L
relay RUC-M, faston 187 (4,8 x 0,5 mm), contact material AgCdO, with two normally open
contacts, with contact gap ≥ 3 mm, in cover IP 00, with vertical adaptor (V), for flat insert
connectors, voltage version 230 V AC 50/60 Hz, with light indicator (LED diode)
RUC-M-1051-25-5024
relay RUC-M, contact material AgCdO, with one normally open contact (double-break),
with contact gap ≥ 6 mm (3+3), in cover IP 00, for PCB, voltage version 24 V AC 50/60 Hz
Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900
www.relpol.com.pl
Plug-in sockets and accessories
for relays RUC, RUC-M
34
24
14
32
22
12
35,5
26,5
11
25,5
6,1
A2
21
11
41
7,6
31
A1
35
82
Screw terminals
Maximum screw torgue: 0,7 Nm
35 mm rail mount acc. to PN-EN 60715
or on panel mounting
82 x 42,2 x 26,5 mm
Three poles
16 A, 250 V AC
8,3
For RUC faston 4,8x 0,5, RUC-M
Dimensions
41
Connection diagram
4,2
GUC11 ❾
11
Accessories
11
42,2
MBA
❾ For RUC faston 4,8 x 0,5 and RUC-M, with GUC11 socket, max. switching voltages and coil voltages of relays are limited to 250 V AC/DC.
GUC11
Screw terminals
plug-in socket
with RUC faston 4,8 x 0,5 mm
relay.
Export Sales Department Phone +48 68 47 90 832 • Marketing Department Phone +48 68 47 90 900