FSVPLC Inline Flow Switch for connection to PLC Signal level output for PLC 0.6 l/min or 3.0 l/min turn on flow rate Automatic shut down on flow stop Volt free contact for output to PLC 1”BSP pipe connections Technical Specification Flow Tube Material Start up flow rate Max flow rate Max Pressure Max Temperature Pipe connections The FSVPLC can be used to control some other equipment or process via a PLC. If used in a pumped system, the device has to be fitted in the pipe above the pump. FSVPLC06 FSVPLC30 Brass Q. min Q max P max T max l/min l/min bar °C BSP Electrical Specification Output Max voltage Switching Current Max Vac mA Standard Parts FSVPLC06 FSVPLC30 On flow rate 0.6l/min 3.0 l/min 0.6 3.0 80 8 85 1” SPNO volt free contact <5 <1 90 The FSVPLC gives a signal to the PLC once the flow rate through the device exceeds 0.6 l/min, or 3 l/min depending on version. 82 A flow of less than 0.6 l/min , or 3.0 l/min depending on version, whether due to a lack of supply (e.g. tank empty) or to a decrease in demand(e.g. tap closing), will turn the signal to the control circuit off again. Cynergy3 Components Ltd. 7 Cobham Road Ferndown Industrial Estate Wimborne, Dorset BH21 7PE Telephone +44 (0) 1202 897969 Email:[email protected] ISO9001 C E R T I F I E D www.cynergy3.com © 2014 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited. FSVPLC Inline Flow Switch for connection to PLC Installation information The flow switch must be mounted vertically with the flow direction upwards. Pipe connection is G1” (1”BSP). The device relies on the flow of liquid working in opposition to gravity to operate the switch. The liquid flow moves a plunger inside the brass flow tube, when the flow increases beyond the minimum specified level. A magnet inside the plunger closes a magnetic switch in the control circuit to the PLC. The output will open, if the flow drops below the specified level and the plunger has returned to the lower position Flow Direction The output switch will be closed if the test button is pushed. The output is a SPNO switch with contacts rated to 1mA/5Vac. Cynergy3 Components Ltd. 7 Cobham Road Ferndown Industrial Estate Wimborne, Dorset BH21 7PE Telephone +44 (0) 1202 897969 Email:[email protected] ISO9001 C E R T I F I E D www.cynergy3.com © 2012 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.