FCHM

FCHM
cynergycomponents
Hydromatic Pump Control Module
Use
To maintain and control water pressure, within a pumped system, for
the supply to industrial processes and heating systems. Ensures
constant flow and pressure to allow optimum performance of gas
boilers or heaters, while preventing cycling and consequent
temperature variations in the various appliances.
Description
A compact unit, which combines all the functions of a complete
pressurising system, ie. Pressure Switch, Dry Running cut-out, Control
Panel, Pressure Reservoir and Non-return Valve. The system employs a
hydraulic chamber, equipped with a damping system to protect against
water hammer, and a patented electromechanical control board, to be
connected to 240Vac power source, with an internal 24V secondary
circuit.
Compared with conventional systems this is not only more compact,
but easier and quicker to install, and makes for significant energy
savings and reduced pump wear. It is also maintenance free, as the
pressurisation unit does not require precharging with air.
This system combines the versatility and control of conventional
pressure switches with the advantages of pressure/flow switches.
Avoids the need for pressure reservoirs, along with their associated
maintenance costs.
• Start up pressure
1-3.5 bar, adjustable
• Dry running cut out
and foot valve
• Visual Indication and
manual reset for
water circuit faults
• Pressure gauge for
easy set up
• Auxiliary fuse to
protect pump
control circuit
SPECIFICATION
Supply voltage
240Vac 50-60Hz
Max operating power
2HP
IP Rating
65
Max pressure
10 bar
Max flow rate
100 l/min
Max fluid temperature
60°C
Max ambient temperature
60°C
Minimum start-up pressure adjustable
1 - 3.5 bar
Pump shutdown Flowrate
1.5L/min.
Minimum output pressure(Pump max pressure) > = start-up
ISO 9001C E R T I F IED
Cynergy3 Components Ltd
7 Cobham Road
Ferndown Industrial Estate
Wimborne
Dorset BH21 7PE
Tel: +44 (0) 1202 897969
[email protected]
www.cynergy3.com
www.cynergy3.com
© 2013 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
page 1
FCHM
Hydromatic Pressure Regulator
cynergycomponents
WITHOUT FCHM
Pressure Vessel
Press Switch Min. Press
Control Panel
Dry Running
Foot Valve
WITH FCHM
from
Submersible
pump
ISO 9001C E R T I F IED
www.cynergy3.com
© 2013 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
page 2
FCHM
cynergycomponents
Hydromatic Pump Control Module
Setting start up
pressure
Always install a pump that
develops a maximum output
pressure that is at least 1 bar
greater than the required
minimum start up pressure.
If the head to be pumped is greater
than 15m, it is necessary to
increase the start up pressure
setting e.g. 20m head requires at
least 2.5 bar start up pressure, 25m
head requires at least 3 bar start up
pressure.
To increase the start up pressure
setting:
Wiring for 1phase pumps up to 2HP
Cynergy3 Components Ltd
7 Cobham Road
Ferndown Industrial Estate
Wimborne
Dorset BH21 7PE
Tel: +44 (0) 1202 897969
[email protected]
www.cynergy3.com
ISO 9001C E R T I F IED
www.cynergy3.com
© 2013 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
page 3
FCHM
cynergycomponents
Hydromatic Pump Control Module
Wiring for 1phase pumps over 2HP
Wiring for 3phase pumps
Cynergy3 Components Ltd
7 Cobham Road
Ferndown Industrial Estate
Wimborne
Dorset BH21 7PE
Tel: +44 (0) 1202 897969
[email protected]
www.cynergy3.com
ISO 9001C E R T I F IED
www.cynergy3.com
© 2013 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
page 4