Am Buschgarten 17 59469 Ense-Höingen Postfach 1060 59469 Ense Telefon (+49 2938) 97 30 - 0 Telefax (+49 2938) 97 30 - 29 INOTEC Sicherheitstechnik GmbH · Am Buschgarten 17 ·59469 Ense Herrn J. Cierpinski OSRAM GmbH EC D/CE – M Hellabrunner Straße 1 Ense, 22.01.2009 81543 München Technical requirements for electronic control gears (ECGs) for connection at INOTEC Central Battery Systems Operating voltage AC: 230V ± 10% Operating voltage DC: 186V – 260V Types of voltage: AC DC Joker-voltage (half-wave rectified AC-voltage) Switch over time AC to DC: 150ms – 1000ms Switch over time DC to AC: 150ms – 1000ms No-load current of ECGs: (without or faulty lamp) in DC-operation < 10mA < 45mA < 8mA < 45mA < 10mA Shutdown ECG: (with faulty lamp) Within 3s Max. inrush current per ECG: Max. total inrush current: per circuit: at J-SV-Modul/S at J-SV-Modul.2/S at J-SV-Modul.3/S at J-SV-Modul.4/S at J-SV-Modul.L/S (5 – 120W) (20 – 300W) (2 – 30W) (18 – 120W) (5 – 120W) 80A / 500µs at J-SV-modules /S (all types) 250A / 500µs 250A / 500µs 250A / 500µs 250A / 500µs at change over module 2x3A at change over module 1x6A at change over module 4x2A at change over module 2x4A With best regards INOTEC Sicherheitstechnik GmbH p.p. Frank Totzeck _______________________________________________________________________________________________________________________________________________________________________________________ Geschäftsführung: Klaus Blankenagel Wilfried Klaas Karl-Heinz Malzahn Volksbank Arnsberg-Sundern eG Kto. Nr. 500 310 400 BLZ 466 600 22 Sparkasse Werl Kto. Nr. 7 043 581 BLZ 414 517 50 Sitz der Gesellschaft: Ense Amtsgericht Werl HRB 1847 Ust-IdNr.: DE 811852626