pdf - Osram

Am Buschgarten 17
59469 Ense-Höingen
Postfach 1060
59469 Ense
Telefon (+49 2938) 97 30 - 0
Telefax (+49 2938) 97 30 - 29
INOTEC Sicherheitstechnik GmbH · Am Buschgarten 17 ·59469 Ense
Herrn
J. Cierpinski
OSRAM GmbH
EC D/CE – M
Hellabrunner Straße 1
Ense, 22.01.2009
81543 München
Technical requirements for electronic control gears (ECGs) for connection at
INOTEC Central Battery Systems
Operating voltage AC:
230V ± 10%
Operating voltage DC:
186V – 260V
Types of voltage:
AC
DC
Joker-voltage (half-wave rectified AC-voltage)
Switch over time AC to DC:
150ms – 1000ms
Switch over time DC to AC:
150ms – 1000ms
No-load current of ECGs:
(without or faulty lamp) in
DC-operation
< 10mA
< 45mA
< 8mA
< 45mA
< 10mA
Shutdown ECG:
(with faulty lamp)
Within 3s
Max. inrush current per ECG:
Max. total inrush current:
per circuit:
at J-SV-Modul/S
at J-SV-Modul.2/S
at J-SV-Modul.3/S
at J-SV-Modul.4/S
at J-SV-Modul.L/S
(5 – 120W)
(20 – 300W)
(2 – 30W)
(18 – 120W)
(5 – 120W)
80A / 500µs
at J-SV-modules /S
(all types)
250A / 500µs
250A / 500µs
250A / 500µs
250A / 500µs
at change over module 2x3A
at change over module 1x6A
at change over module 4x2A
at change over module 2x4A
With best regards
INOTEC Sicherheitstechnik GmbH
p.p.
Frank Totzeck
_______________________________________________________________________________________________________________________________________________________________________________________
Geschäftsführung:
Klaus Blankenagel
Wilfried Klaas
Karl-Heinz Malzahn
Volksbank Arnsberg-Sundern eG
Kto. Nr. 500 310 400
BLZ 466 600 22
Sparkasse Werl
Kto. Nr. 7 043 581
BLZ 414 517 50
Sitz der Gesellschaft: Ense
Amtsgericht Werl HRB 1847
Ust-IdNr.: DE 811852626