ALLEN-BRADLEY MSR230P

Safety Relays
Modular Monitoring Safety Relays
Minotaur MSR230P
Specifications
Description
The MSR230P is an output expansion module for the modular
Minotaur MSR200 family of monitoring safety relays. It can be
connected to either the MSR210P or MSR211P base unit to provide
additional outputs.
Up to 2 MSR230P output modules can be connected to one base
unit by simply removing the terminator, included with each base
unit, and connecting the ribbon cables of the neighboring module.
The connecting ribbon cable provides power to the MSR230P as
well as a check on its status. The terminators must be inserted into
the final output module.
Standards
EN 954-1, ISO 13849-1, IEC/EN
60204-1, IEC 60947-4-1, IEC
60947-5-1, ANSI B11.19, AS4024.1
Approvals
C-Tick, CE marked for all
applicable directives, cULus, & TÜV
Category
Cat. 4 per EN954-1 (ISO13849-1)
Power Supply
24V DC from the base unit
Power Consumption
1.5W
Fuses Output (external)
6A Slow Blow or 10A Quick Blow
Outputs
4 N.O. Safety
Output Utilization per
IEC60947-4-1 (Resistive)
AC-1: 6A/250V AC
DC-1: 6A/24V DC
➊ Output Utilization per IEC
60947-5-1 (Inductive)
B300, AC-15
3A/250V AC, 3A/125VAC
P300, DC-13
2.5A/24V DC
Thermal Current (non switching)
1x6A, 2x4A
Output, Solid State
20mA @ 30V DC
Min. Switched Current/Voltage
10ma/10V DC
Contact Material
AgSnO2 + 2µAu
Response Time
Does not add additional response
time to base module
Indication LEDs
Green = CH1 Output Active
Green = CH2 Output Active
Impulse Withstand Voltage
2500V
The MSR230P has four safety rated outputs that work in parallel
with the safety outputs of the base unit. When the output of the base
unit is activated, the outputs of the MSR230P are also activated.
Pollution Degree
2
Operating Temperature
-5°C to +55°C (+23°F to 131°F)
Humidity
90% RH
The outputs are 4 normally open safety rated outputs. The safety
outputs have independent and redundant internal contacts to help
ensure the safety function.
Enclosure Protection
IP40 (NEMA 1)
Terminal Protection
IP20
Conductor Size
0.2–4mm2 (24–12 AWG)
Features
Torque Settings—term. screws
0.4–0.5 Nm (3.54–4.43lb•in)
Case Material
Polyamide PA 6.6
• 4 N.O. safety outputs
• 2 Diagnostic LEDs
• Removable terminals
Mounting
35mm DIN rail
Weight
215g (0.47lbs)
Electrical Life
222V AC/4A/880VA cosϕ=0.35
220V AC/1.7A/375VA cosϕ=0.6
30V DC/2A/60W
10V DC/0.01A/0.1W
100,000 operations
500,000 operations
1,000,000 operations
2,000,000 operations
Mechanical Life
2,000,000 cycles
Vibration
10-55 Hz, 0.35mm
Shock
10g, 16ms, 100 shocks
➊ See Output Ratings on page 1-29 for details. Consult factory for ratings not
shown.
4-80
Safety Relays
Modular Monitoring Safety Relays
Minotaur MSR230P
Product Selection
Safety Outputs
Catalogue Number
4 N.O.
440R-H23180
Dimensions—mm (inches) Block Diagram
22.5 (0.88)
99 (3.89)
13
23
43
33
13 23 33 43
Ch1
MSR230P
114.5
(4.5)
Ch2
14 24 34 44
14
24
34
44
Typical Wiring Diagrams
Closed
13 23 33 43
Y31 Y40 Y41 Y42 13 23 31
MSR230P
Termination
Fuses
A1 S41 S12 S22 S32 S51
Termination or
Expansion Cable
Safety Gate
+24V DC
13 23 33 43
MSR230P
L1 L2 L3
K1
MSR210P
K2
A2 S11 S42 S52 S62 S21 Y30 Y32 Y33 S34 Y1 Y2 14 24 32
K1 K2
E-Stop
14 24 34 44
14 24 34 44
K3 K4
K7 K8
K5 K6
M
K3 K10
Reset
Ground
Relays, contactors
solenoids, valves, etc.
Output Inputs
Active Closed
Dual Channel Safety Gate and E-Stop,
Monitored Manual Reset, Monitored Output
Termination or
Expansion Cable
Light Curtain
Out 1 Out 2
A1 S12
S32
Fuses
Y31 Y40 Y41 Y42 13 23 31
13 23 33 43
MSR230P
13 23 33 43
MSR230P
Termination
+24V DC
L1 L2 L3
K1
MSR211P
K2
A2 S42 S62
Y30 Y32 Y33 S34 Y1 Y2 14 24 32
K1 K2
E-Stop
14 24 34 44
14 24 34 44
K3 K4
K7 K8
K5 K6
Reset
Ground
Output Inputs
Active Closed
K3 K10
M
Relays, contactors
solenoids, valves, etc.
Light Curtain and Dual Channel E-Stop,
Monitored Manual Reset, Monitored Output
4-81