DIM SA - Osram

Description
Function and application
The signal amplifier DIM SA in combination with 1...10V control
units is used for the control of electronic ballasts (ECG) with a
1...10V interface.
DIM SA
The following applications are available, depending on the connection (see the connection diagram):
• Increase in the number of electronic ballasts and luminaires
that can be connected to the control unit.
• Increase in the permissible control line length.
• Configuration of lighting with daylight-dependent control or
daylight- and motion-dependent control (in combination with
a suitable light sensor or light and motion sensor).
A
B
Connections
The signal amplifier has the following connections:
• Power supply (A)
• 1…10V input (B)
• 1…10V output (C)
Signal amplifier
Fitting instructions
C
Installation
Safety instructions
The signal amplifier must only be installed and put into operation by a qualified electrician. The applicable safety regulations
and accident prevention regulations must be observed.
WARNING!
Exposed, live cables.
Danger of electric shock!
• Only work on the signal amplifier when it is
de-energised.
CAUTION!
Destruction of the signal amplifier and other devices
through incorrect mounting!
• Do not connect the control outputs of multiple
signal amplifiers in parallel.
• Only use ballasts with a 1...10V interface.
• Do not exceed the maximum number of connectable components.
• Only supply signal amplifiers with an AC operating voltage, especially in networks with UPS
systems.
D
Connecting the signal amplifier
L
N
PE
H
1...10V
DIM SA
1...10V
~ 230V
~ 50-60Hz
+
-
-
in +
1...10V out
-
+
~ 230V /
~ 50Hz
DIM SA
1...10V
~ 230V
~ 50-60Hz
-
in +
1...10V out
+
.
.
.
1...10V EVG
- 1...10V
+
.
.
.
~ 230V /
~ 50Hz
1...10V EVG
- 1...10V
+
DIncrease in the number of electronic ballasts and luminaires that can be connected to the control unit (H)
–– Connect the control output of the control unit with the
1...10V inputs of the signal amplifier.
–– Connect the 1...10V outputs of the signal amplifier with
the 1...10V control inputs of the electronic ballast.
Note:
Ensure that the configuration is „symmetric“:
–– As far as possible, distribute the number of electronic
ballasts evenly among the signal amplifiers.
–– Connect all electronic ballasts to the signal amplifiers if
possible. If some of the electronic ballasts are connected
directly to the control unit, dim settings and dim speeds
may vary within the system.
.
.
.
Page 1 of 2
Installation (cont.)
E
L
N
PE
H
1...10V
max. 300 m
DIM SA
1...10V
~ 230V
~ 50-60Hz
max. 300 m
+
-
-
in +
1...10V out
~ 230V /
~ 50Hz
-
+
1...10V
~ 230V
~ 50-60Hz
in
+
1...10V out
1...10V EVG
- 1...10V
+
DIM SA
F
EIncrease in the permissible control line length of the
control unit (H)
–– Maximum line length between the distributors of the
signal amplifiers: 300 m.
.
.
.
~ 230V /
~ 50Hz
-
+
1...10V EVG
- 1...10V
+
.
.
.
.
.
.
L
N
PE
DIM
MICO
DIM SA
~ 230V
~ 50-60Hz
1...10V
FConfiguration of lighting with daylight-dependent control
–– Suitable light sensor: DIM MICO
+
-
-
in +
~ 230V /
~ 50Hz
1...10V out
+
1...10V EVG
- 1...10V
+
~ 230V /
~ 50Hz
1...10V EVG
- 1...10V
+
G
L
N
PE
.
.
.
GConfiguration of lighting with daylight- and motiondependent control
–– Suitable light and motion combination sensor: DIM MULTI
N
L
DIM
MULTI
+
-
DIM SA
~ 230V
~ 50-60Hz
1...10V
in
1...10V
1...10V out
+
-
+
~ 230V /
~ 50Hz
1...10V EVG
- 1...10V
+
~ 230V /
~ 50Hz
1...10V EVG
- 1...10V
+
Appendix
.
.
.
Technical data
Operating voltage
230 V; 50-60 Hz (no DC operation)
Supply connection
L, N, PE
Power consumption
Approx. 2 W
Load capacity
• 1…10V input:
max. 1.5 mA
• 1…10V output:
max. 100 mA or 100 OSRAM
1…10V ECG
IV 2009
DIM_SA_ma0904en_we1.01.indd
Protection class
I
Protection type
IP 20
Operating temperature
0 °C … +50 °C
Dimensions
(L x W x H)
189 x 30 x 28 mm
Hole distance for
mounting
180 mm
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 - 200
(kostenpflichtig / charges apply)
Fax.: +49 (0) 1803 677 - 202
www.osram.com
www.osram.de
40083210970958
4008321097095
The EMC requirements to EN 61547, EN 61347-11 and
EN 55015 are fulfilled.
Conformity with the relevant EU directives is
confirmed by the CE symbol.
Page 2 of 2