OPTOTRONIC® OT 240/220-240/24 P Constant Voltage LED Power supply for 24V LED - Modules 1. Technical Data Nominal Voltage Input Voltage Line Current, nominal Mains Frequency Power Factor Interface IP Rating Max Output Power 220 – 240 Vac 198 – 264 Vac 1,1A@230Vac 50 / 60 Hz = 0.95 @ 230 Vac None IP 67 240 Watt Output Voltage Efficiency Ambient Temperature Max. Case Temperature at tc Max. Cable Length Max load per circuit breaker B10 Max load per circuit breaker B16 Max load per circuit breaker C10 24 Vdc (-0,5 V/+0,9 V) 93% @230Vac -25°C to +55°C + 80°C 10m 5 8 7 2. Connection schemes a. Non – Dim operation (+) 24V (-) GND red black LED Module (+) 24V a) b) c) (-) GND OT 240/220-240/24 P 3 red black LED Module Ensure proper insulation of not connected wire terminals. 2 Output channels for optional splitting of the load (1 channel use also possible) Ensure that the complete Load is not connected to one channel. Maximum output current is limited by the cross section of the cable (7.5A per channel – 180 Watt). It is possible to join the two output cables together, in parallel, to drive one module at max power. b. Non – Dim operation 3 wires LED module (+) 24V (-) GND 220 – 240V AC 3 a) b) c) OT 240/220-240/24 P (+) 24V (-) GND red LED Module black red LED Module black Ensure proper insulation of not connected wire terminals. 2 Output channels for optional splitting of the load (1 channel use also possible) Ensure that the complete Load is not connected to one channel. Maximum output current is limited by the cross section of the cable (7.5A per channel – 180 Watt). It is possible to join the two output cables together, in parallel, to drive one module at max power. 3. Safety + + 3 OT 240/220-240/24 P LED Module 240 Watt 3 OT 240/220-240/24 P 220 – 240V AC 3 OT 240/220-240/24 P + + - LED Module 240 Watt 3 OT 240/220-240/24 P Power supplies can be connected in parallel on the primary side, but not on the secondary side OSRAM AG www.osram.com 2013-03-05 AA328430055 Steinerne Furt 62, 86167 Augsburg, Germany No. 1, North Industrial Road 528000 Foshan Guangdong, P.R. China LED Module 480 Watt OPTOTRONIC® OT 240/220-240/24 P Constant Voltage LED Power supply for 24V LED - Modules L N PE L N PE ~ ~ ~ ~ ~ ~ + OT 240/220-240/24 P ~ ~ LED Module + OT 240/220-240/24 P ~ ~ LED Module + OT 240/220-240/24 P ~ ~ LED Module + OT 240/220-240/24 P LED Module + OT 240/220-240/24 P LED Module + OT 240/220-240/24 P LED Module The installation of two ore more OPTOTRONIC® OT 240/220-240/24 P Power supplies with common “-“ or “+” wiring is forbidden. Wiring and Connection Ensure that the LED module load is within the range of rated voltage, current and power (see Technical data) Maximum output cable length is limited by EMI and cross diameter Use output cable sections adequate to the load demand The luminaire manufacturer is responsible for providing the required clearances and creepage distances and also for protection against electrical shock, especially for the line and load wires Please avoid direct exposure of sunlight and in case of exposure to UV rays, protect the cables with suitable silicone sheath. Not used output cables have to be insulated separately Earth Connection Protective earth connection of OT 240/24 P is mandatory for safety and EMI reasons The ground connection has to be done via the input cable Mounting and Environmental protection The control gear is a built in type for luminaire integration Maximum permissible ambient temperature must not be exceeded. Make sure there is adequate space to avoid a build-up of heat. In critical installations the temperature at tc has to be controlled General Note Power supplies must be installed by a qualified electrician Disconnected from mains supplies before wiring work For further information see also “OPTOTRONIC – Technical guide” at www.osram.com OSRAM AG www.osram.com 2013-03-05 AA328430055 Steinerne Furt 62, 86167 Augsburg, Germany No. 1, North Industrial Road 528000 Foshan Guangdong, P.R. China