FMBC BOOK STYLE - 3-Phase AC Filters / DC Filters

FMBC BOOK STYLE
3-Phase AC Filters / DC Filters
www.schurter.com/PG80
Compact 2-stage bookform filter
Description
Applications
-Very compact and slim filter design
-High symmetrical and asymmetrical attenuation
-In the frequency range from 10kHz up to 300MHz
-Voltage rating 480 VAC for world wide acceptance
-Especially designed for industrial applications such as: Frequency Converters, Stepper Motor Drives, UPS-Systems, Inverters
-Suitable for use in equipment according to IEC/UL 60950
Standards
Weblinks
-IEC 60939
-VDE Certificate Number: 40004666
-UL File Number: E72928
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, e-Shop,
SCHURTER-Stock-Check, Distributor-Stock-Check, Detailed request for
product
Technical Data
Approvals
Rated Current
Rated voltage
Approval for
Overload Current
Leakage Current
Dielectric Strength
10 - 115 A @ Ta 40 °C
480 VAC 50/60 Hz
10 - 115 A @ Ta 40 °C / 480 VAC; 50 Hz
1.5 x Ir
industrial < 5 mA (440 V / 50 Hz)
480 VAC:
2.25 kVDC between L-L
3 kVDC between L-PE
Test voltage (2 sec)
2-stage
1.9 - 7.25 kg
Metal UL 94V-0 Number of Filter Stages
Weight
Material: Housing
Sealing Compound
Mounting
Terminal
Operating Temperature [°C]
Climatic Category
Degree of Protection
Protection Class
MTBF
Screw-on mounting on chassis, from
top
Screw clamps / flexible wires -25 °C to 100 °C
25/100/21 acc. to IEC 60068-1
IP 20 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
> 200'000 h acc. to MIL-HB-217 F
Dimension
Case 58
276 max.
55 max.
(11)
(20)
(11)
(20)
1)
2)
M5
M5
(117)
(86)
142 max.
0.6...0.8 Nm
2...2.5 Nm
305 max.
305 max.
+1
6.5 ±0.3
30 ±0.3
290 -2
1) Line
2) Load
EMC Products
1
FMBC BOOK STYLE
3-Phase AC Filters / DC Filters
www.schurter.com/PG80
Case 60
355 max.
305 max.
60 max.
(30)
(30)
(25)
(25)
M5
1)
2)
(117)
(94)
150 max.
M5
1.5...1.8 Nm
2...2.5 Nm
6.5 ±0.3
35 ±0.3
335 max.
+1
320 -2
Case 62
80 max.
375 max.
300 max.
(38)
(40)
(38)
(40)
M5
1)
(136)
(107)
M5
185 max.
4...4.5 Nm
2)
3...4 Nm
329 max.
+1
6.5 ±0.3
55 ±0.3
314 -2
Case 64
90 max.
(52)
434 max.
348 max.
(43)
(52)
(43)
2)
EMC Products
+1
364 -2
379 max.
M10
M10
65 ±0.3
1) Line
2) Load
2
1)
10...17 Nm
6.5 ±0.3
(169)
(124)
220 max.
6...8 Nm
FMBC BOOK STYLE
3-Phase AC Filters / DC Filters
www.schurter.com/PG80
Case 67
50 max.
(20)
226 max.
(52)
(11)
(11)
2.0...2.5 Nm
(105)
2)
(74)
1)
M5
M5
(105)
(74)
127 max.
6...8 Nm
254 max.
254 max.
+1
6.5 ±0.3
25 ±0.3
240 -2
Case 58C
M5
0.6...0.8 Nm
2)
14 AWG
2...2.5 Nm
(86)
(117)
1)
(300)
(9)
(117)
276 max.
(11)
(100)
142 max.
55 max.
(20)
30 ±0.3
6.5 ±0.3
305 max.
305 max.
+1
290 -2
Case 60C
(400)
305 max.
1.5...1.8 Nm
(9)
1)
2)
(120)
10 AWG
(94)
2...2.5 Nm
(117)
M5
(11)
(104)
150 max.
60 max.
(30)
346 max.
6.5 ±0.3
35 ±0.3
335 max.
+1
320 -2
1) Line
2) Load
EMC Products
3
FMBC BOOK STYLE
3-Phase AC Filters / DC Filters
www.schurter.com/PG80
Case 62C
4...4.5 Nm
AWG 6
3...4 Nm
(136)
2)
1)
(142)
(124)
M5
185 max.
(500)
(12)
300 max.
(107)
(38)
80 max.
(40)
353 max.
6.5 ±0.3
329 max.
+1
55 ±0.3
314 -2
Case 67C
AWG 16
2...2.5 Nm
(105)
2)
1)
(74)
M5
0.6...0.8 Nm
(9)
(11)
(88)
(105)
127 max.
(300)
226 max.
50 max.
(20)
6.5 ±0.3
25 ±0.3
254 max.
254 max.
+1
240 -2
1) Line
2) Load
Technical data to the filter components
Rated Current [A]
10
Terminal
Screw-on terminals on line- and loadside
L1
[mH]
L2
[mH]
C1 [μF]
C2 [μF]
C3 [nF]
C4 [nF]
C5 [μF]
3
1.5
1.5
1.0
1.5
-
1.5
R1 [MΩ] R2 [MΩ] R3 [MΩ]
-
-
1
115
Screw-on terminals on line- and loadside
0.7
0.2
2.2
2.2
2.2
100
2.2
-
1
1
20
Screw-on terminals on line- and loadside
1.8
2
2.2
1.5
2.2
-
1.5
-
-
1
36
Screw-on terminals on line- and loadside
1.5
0.5
2.2
2.2
2.2
-
2.2
-
-
1
66
Screw-on terminals on line- and loadside
0.65
0.45
2.2
2.2
2.2
100
2.2
-
1
1
Diagrams
1)
1) Line
4
EMC Products
FMBC BOOK STYLE
3-Phase AC Filters / DC Filters
www.schurter.com/PG80
Attenuation Loss
- - - - differential mode _____ common mode
Industrial version
10 A
20 A
36 A
66 A
115 A
All Variants
Rated Current
[A]
Terminal
Leakage Current [mA] @ 440V,
60Hz 1)
Tripped
Power Dissipation [W]
Contact Resistance [mΩ]
Weight
[kg]
Clamps [mm2]
Housing
Order Number
10
Screw-on terminals on line- and loadside
4.6
9.45
31.5
1.9 kg
4
67
FMBC-0967-1010
10
Screw-on terminals on lineside, wires on
loadside
4.6
9.45
31.5
1.65 kg
4
67C
FMBC-0967-1060
115
Screw-on terminals on line- and loadside
7.1
48
1.33
7.25 kg
50
64
FMBC-0964-H110
20
Screw-on terminals on line- and loadside
4.6
17.5
14.6
2.15 kg
4
58
FMBC-0958-2010
20
Screw-on terminals on lineside, wires on
loadside
4.6
17.5
14.6
2.3 kg
4
58C
FMBC-0958-2060
36
Screw-on terminals on line- and loadside
6.7
25.7
6.6
2.9 kg
10
60
FMBC-0960-3610
36
Screw-on terminals on lineside, wires on
loadside
6.7
25.7
6.6
3.1 kg
10
60C
FMBC-0960-3660
66
Screw-on terminals on line- and loadside
7.1
43
3.3
4.4 kg
25
62
FMBC-0962-6610
66
Screw-on terminals on lineside, wires on
loadside
7.1
43
3.3
4.41 kg
25
62C
FMBC-0962-6660
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
1) Nominal leakage current acc. to IEC60950 - 5.2.5. under normal operating conditions. Note: worst case leakage current acc. to IEC60950 - Annex G4 (situation with two
interrupted lines) can be much higher.
1 Pcs 02.09.2015
Packaging unit The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
EMC Products
5