FMBD NEO - 3-Phase AC Filters / DC Filters

FMBD NEO
3-Phase AC Filters / DC Filters
www.schurter.com/PG80
2-stage filter for 3-phase systems with neutral conductor
Description
-Terminals for three phases, neutral conductor and ground
-High symmetrical and asymmetrical attenuation
-In the frequency range from 10kHz up to 300MHz
Standards
-IEC 60939
-UL 1283, Edition 5, CSA 22.2 No. 8-M1986, @ Ta 75 °C
Applications
-Voltage rating 520 VAC for world wide acceptance
-Protection against interference voltage from the mains
-Especially designed for industrial applications such as: Frequency Converters, Stepper Motor Drives, UPS-Systems, Inverters
Weblinks
-VDE Certificate Number: 40031052
-UL File Number: E72928
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, e-Shop,
SCHURTER-Stock-Check, Distributor-Stock-Check, Detailed request for
product
Technical Data
Approvals
Rated Current
Rated voltage
Approval for
Overload Current
Dielectric Strength
Number of Filter Stages
Weight
Material: Housing
Sealing Compound
8 - 200 A
300/520 VAC, 50/60 Hz
8 - 200 A @ 50 (75) °C / 300/520 VAC;
50/60 Hz
1.5 x Ir
300/520 VAC:
2.25 kVDC between L-L
1.7 kVDC between L-N
2.75 kVDC between L-PE
2.75 kVDC between N-PE
Test voltage 2 sec
2-stage
1.1 - 8.6 kg
Metal UL 94V-0 Mounting
Terminal
Operating Temperature [°C]
Climatic Category
Degree of Protection
Protection Class
MTBF
Screw-on mounting on chassis Screw clamps -25 °C to 100 °C
25/100/21 acc. to IEC 60068-1
IP 20 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
> 200'000 h acc. to MIL-HB-217 F
EMC Products
1
FMBD NEO
3-Phase AC Filters / DC Filters
www.schurter.com/PG80
Dimension
Case 2A
max. 155
max. 115
3x11.5=(34.5)
M6x14; 3-4 Nm
35
54.5
max. 80
(120)
14
80 ±0.3
6.5±0.3
(4x)
0
127.5–2
max. 145
4mm 2 ; 0.5-0.6 Nm
1)
2)
1) Line
2) Load
Case 2B
(130)
3x23=(69)
89
max. 125
max. 115
max. 165
50
M6x14; 3-4 Nm
14
90 ±0.3
6.5
(4x)
0
137.5 –2
max. 155
10mm 2 ; 1.5-1.8 Nm
1)
1) Line
2) Load
2
EMC Products
2)
FMBD NEO
3-Phase AC Filters / DC Filters
www.schurter.com/PG80
Case 2C
3x25=(75)
94
max. 125
(160)
max. 125
max. 220
55
M10; 10-17 Nm
18
100 ±0.3
6.5 ±0.3
(4x)
0
137.5 –2
max. 155
25mm 2 ; 2-2.2 Nm
1)
2)
1) Line
2) Load
Case 2D
max. 135
(230)
3x28=(84)
40
83
max. 125
max. 315
M10; 10-17 Nm
24
120 ±0.3
6.5 ±0.3
(4x)
0
147.5 –2
max. 165
50mm2 ; 6-8 Nm
1)
2)
1) Line
2) Load
EMC Products
3
FMBD NEO
3-Phase AC Filters / DC Filters
www.schurter.com/PG80
Case 2E
3x30=(90)
max. 140
max. 140
(250)
98
max. 335
55
M10; 10-17 Nm
18
200 ±0.3
6.5 ±0.3
(4x)
0
152.5 –2
max. 170
50mm 2 ; 6-8 Nm
1)
2)
1) Line
2) Load
Case 2F
max. 140
(280)
3x30=(90)
106.5
max. 170
max. 380
45
M10; 10-17 Nm
24
230 ±0.3
6.5 ±0.3
(4x)
0
152.5 –2
max. 170
95mm 2 ; 15-20 Nm
1)
2)
1) Line
2) Load
4
EMC Products
FMBD NEO
3-Phase AC Filters / DC Filters
www.schurter.com/PG80
Technical data to the filter components
L1
[mH]
Rated Current @ Ta 50°C (75°C) [A]
L2
[μH]
C1 [μF]
C2 [μF]
C3 [μF]
R1 [MΩ] R2 [MΩ] R3 [MΩ]
8 (5)
2
4
2.2
2.2
3.4
-
1
2
16 (11)
1.3
12
2.2
2.2
3.4
-
1
2
25 (16)
1.6
12
4.7
4.7
3.4
1
1
2
36 (21)
1
12
4.7
4.7
3.4
1
1
2
64 (40)
0.7
7.5
4.7
4.7
3.4
1
1
2
80 (50)
0.6
9
8.2
8.2
3.4
1
1
2
120 (96)
0.6
9
13.6
13.6
3.4
0.5
0.5
2
160 (100)
0.4
9
13.6
13.6
3.4
0.5
0.5
2
200 (140)
0.3
9
13.6
13.6
3.4
0.5
0.5
2
Diagrams
C1/R1
L1
L2
1) L3
L1
C2/R2
C1/R1
L2
L1'
C2/R2
C1/R1
L2'
C2/R2
L3' 2)
N
N'
PE
PE
C3/R3
1) Line
2) Load
Derating Curves
Admissible operating current in % of In
Permissible Working Current as a Function of Ambient Temperature
100
80
60
UL Listed
40
20
0
0
20
Ambient air temperature Ta °C
40
60
75
100
EMC Products
5
FMBD NEO
Attenuation Loss
3-Phase AC Filters / DC Filters
www.schurter.com/PG80
. . . . . 0.1/100Ω differential mode
........... 100/0.1Ω differential mode
- - - - differential mode _____ common mode
Industrial version
8A
16A
25A
36A
64A
80A
120A
160A
200A
All Variants
Rated Current @ Ta 50°C (75°C) [A]
Tripped Power Dissipation [W]
Contact Resistance
[mΩ]
Leakage Current [mA] @ 440V,
60Hz 1)
Weight
[kg]
Screw
clamps
[mm2] 2)
Housing
Packaging
unit [PCS]
Order Number
3.2
12.5
11.1
1.1 kg
4
2A
2
FMBD-B92A-0812
█
16 (11)
7
6.8
11.1
1.2 kg
4
2A
2
FMBD-B92A-1612
█
25 (16)
9.5
3.8
12.7
1.8 kg
10
2B
2
FMBD-B92B-2512
█
36 (21)
12.5
2.4
12.7
2 kg
10
2B
2
FMBD-B92B-3612
█
64 (40)
21.3
1.3
12.7
2.8 kg
25
2C
1
FMBD-B92C-6412
█
FMBD-B92D-8012
8 (5)
80 (50)
22.6
0.88
13.2
5.7 kg
50
2D
1
120 (96)
43.2
0.75
13.6
6.3 kg
50
2E
1
FMBD-B92E-J212
160 (100)
37.9
0.37
13.6
8 kg
95
2F
1
FMBD-B92F-J612
200 (140)
41.6
0.26
13.6
8.6 kg
95
2F
1
FMBD-B92F-K012
█ Most Popular.
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
1) Maximum leakage current under normal operating conditions, assuming that all three phases and the neutral conductor are connected to the supply and the consumer.
Under this condition, the current will mainly return through the neutral line, not as earth leakage.
03.03.2015
2) Maximum conductor cross section (wire gauge) to be used; a comparative table for AWG and mm² values can be found in the general product information www.schurter.
com/emc_info
6
EMC Products
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.