17. DC Input Power System (ComPAC/MI-ComPAC Family)

17. DC Input Power System (ComPAC / MI-ComPAC Family)
Design Guide & Applications Manual
For VI-200 and VI-J00 Family DC-DC Converters and Configurable Power Supplies
OVERVIEW
The ComPAC is a low profile, highly efficient, high density
configurable DC-DC power solution with EMC filtering,
transient protection and reverse polarity protection. It has
an isolated master disable input for remote shutdown, and
provides outputs from 1 – 95 Vdc and power-up to 600 W.
There are five input voltages available which comply with
telecommunication and industrial control EMC specifications.
Refer to data sheet for applicable standards at vicorpower.com.
Nominal
Input Voltage
24 V
24 V (wide)
48 V
48 V (wide)
300 V
Input
Designator
1
W
3
N
6
Input Voltage
Range
21.7 – 32
18.7 – 36
42 – 60
36 – 76
200 – 400
There are two military input voltages available which comply
with military EMC specifications and the transient and spike
specifications. Refer to data sheet for applicable standards
at vicorpower.com.
Nominal
Input Voltage
28 V
270 V
Input
Designator
2
6
Input Voltage
Range
18 – 50
125 – 400
ComPACs can be configured in 1-up, 2-up or 3-up
packages with total output power limited to the
maximum power of individual VI-200 or MI-200 series
converters. Output voltages may be trimmed by the user.
Output Power. The maximum total power which is
delivered from the ComPAC is:
Nominal
Input Voltage
24 V and 24 V (wide)
28 V, 270 V (military)
48 V and 48 V (wide), 300 V
Total Output Power
1-Up
2-Up
3-Up
150 W
300 W
450 W
100 W
200 W
300 W
200 W
400 W
600 W
EMC Performance, Conducted EMC. The ComPAC will
conform to the following conducted EMC specifications
on the input power leads:
• Telecom (24 V, 48 V inputs): Bellcore TR-TSY-000513,
Issue 2 July 1987 and Rev. 1, December 1988.
British Telecom Document BTR2511, Issue 2.
• Commercial (300 V input): FCC Pt. 15 Subpt. J,
Class A / VDE 0871 Class A.
• Military (28 V, 270 V): MIL-STD-461C
Conducted Emissions: CE01, CE03, CE07
Conducted Susceptibility: CS01, CS02, CS06
Radiated EMC. The ComPAC will conform to the
following radiated specifications:
• Military: Radiated Emissions: RE02; Radiated
Susceptibility: MIL-STD-461C, RS02, RS03.
Input Transient Protection. The input transient
protection will suppress short term transients appearing
on the input line. Refer to data sheet for applicable
standards at vicorpower.com.
Input Surge Withstand. The 24 V, 48 V and 300 V input
ComPAC shall withstand, without damage or interruption
of power, an input line surge shown below for a duration
of 100 ms from a source impedance of 500 milliohms.
Extended Input OV Shut Down. Surge protection shall
also shut down the ComPAC in the presence of sustained
input surges (100 – 1,000 ms) which would cause
excessive dissipation or damage. The ComPAC will auto
restart when the input overvoltage is removed.
Input Reverse Polarity Protection. The ComPAC’s input
is protected against reverse polarity. No damage will occur
provided that external current limiting is present (i.e., fuse).
Output Short Circuit Protection. Output short circuit
protection is provided by the current limiting of the Vicor
DC-DC converters.
Undervoltage Lockout. The ComPAC incorporates an
undervoltage lockout which will inhibit the output of all
converters until the input line exceeds the brownout
voltage specified for the converter input range.
Weight.
1-Up: 1.2 lbs (540 g)
2-Up: 2.4 lbs (1,080 g)
3-Up: 3.6 lbs (1,630 g)
Nominal
Input Voltage
24 V
24 V (wide)
28 V (military)
48 V
48 V (wide)
270 V (military)
300 V
Operating Case Temperature.
E-Grade: –10˚C to +85˚C
C-Grade: –25˚C to +85°C
I-Grade: –40˚C to +85°C
M-Grade: –55˚C to +85°C
Overall Efficiency. The overall efficiency of the ComPAC is
approximately 1% less than the efficiency of the Vicor
DC-DC converters (typical efficiencies: 77% for 2 V output,
81% for 5 V output and 83% for 12 – 48 V output).
VI-200 and VI-J00 Family Design Guide
Page 52 of 98
UV Lockout
(Vdc, Typical)
19
17
17
41
35
121
188
Following startup, the undervoltage lockout will inhibit the
converter output(s) should the input drop roughly
8 – 10 V below the UV lockout limits stated above.
Rev 3.5
Apps. Eng. 800 927.9474
vicorpower.com
800 735.6200
17. DC Input Power System (ComPAC / MI-ComPAC Family)
Design Guide & Applications Manual
For VI-200 and VI-J00 Family DC-DC Converters and Configurable Power Supplies
RECOMMENDED INPUT LINE FUSING
DISABLE CURRENT
The ComPAC must be fused externally. The table below
lists the fuse ratings for one, two and three-up units
(maximum output 200, 400 and 600 W).
• 4 mA DC minimum for 1-up ComPAC
• 8 mA DC minimum for 2-up ComPAC
• 12 mA DC minimum for 3-up ComPAC
Nominal
Input Voltage
24 V
24 V (wide)
28 V (military)
48 V
48 V (wide)
270 V (military)
300 V
1-Up
10 A / 32 V
12 A / 32 V
10 A / 250 V
8 A / 60 V
6 A / 100 V
2 A / 250 V
2 A / 250 V
Fuse Rating
2-Up
3-Up
20 A / 32 V
30 A / 32 V
20 A / 32 V
30 A / 32 V
20 A / 250 V
30 A / 125 V
15 A / 60 V
25 A / 60 V
15 A / 100 V
25 A / 100 V
4 A / 250 V
6 A / 250 V
4 A /250 V
6 A / 250 V
RECOMMENDED INPUT WIRING AND TORQUE
1-Up
2-Up
#16 AWG
#14 AWG
10 in-lb
15 in-lb
TRIMMING
The nominal output voltage of the ComPAC can be
adjusted from 110% to 50% of nominal voltage. Refer to
Output Voltage Trimming, Section 5, for external resistor
values. DO NOT trim the outputs higher than 110% of
their nominal output power (output overvoltage protection
may trigger). When the output is trimmed up, do not
exceed its maximum rated output power.
NOTE: 10 V, 12 V, and 15 V outputs, standard trim
range ±10%, 3.3 V output trim range 2.20 to 3.63 V.
RECOMMENDED OUTPUT WIRING
REMOTE SENSING
Use the output wire gauge that corresponds to the output
current of the ComPAC unit:
+SENSE and –SENSE must be connected locally or remotely.
105 A – 160 A: #4 26 A – 40 A: #10 7 A – 10 A: #16
66 A – 104 A: #6 16 A – 25 A: #12 4 A – 6 A: #18
41 A – 65 A: #8 11 A – 15 A: #14 0 A – 3 A: #20
OUTPUT TERMINAL CONNECTIONS
Long cable runs, or wires in large bundles will require
heavier cable to avoid excessive voltage drops or overheating.
GROUNDING
A hardware kit with parts for output terminal connections is
provided with each ComPAC unit. The following drawing
shows the assembly of those parts for the proper
connection of metal power terminals. Assembly for PCB
power terminals is the same except that they do not require
an external tooth lockwasher. See Figure 17–2 for the
recommended torque level for each stud size.
For safe operation, the ComPAC unit must be grounded.
Connect a ground lead to the terminal marked (GND). Use
the same wire gauge as that specified for your ComPAC
unit’s input voltage connections.
#10 TERMINAL
RETAINING NUT
EXTERNAL TOOTH
LOCKWASHER
TERMINAL COVER
NEGATIVE
MASTER DISABLE
HELICAL
LOCKWASHER
(FITS WITHIN
OPENING PROVIDED)
The ComPAC incorporates an optically isolated Master
Disable input which will shut down the ComPAC output
when a current is driven through the disable terminals.
20 mA Max.
V
+
Figure 17–1 — ComPAC module disable
VI-200 and VI-J00 Family Design Guide
Page 53 of 98
Disable
DIS+
DIS–
USER OUTPUT
TERMINALS
#10 NUT PLATE
#10 BRASS STUD
Terminal and
Terminal
Product Model
Style
–OUT, +OUT Terminals
LC, PC, RC Series
PCB
MC and NC Series
Metal
PCB
QC Series
Metal
Stud
Size
8-32 UNC
10-32 UNC
8-32 UNC
10-32 UNC
Recommended
Torque
10
15
10
15
in-lbs
in-lbs
in-lbs
in-lbs
(1.1 N-m)
(1. 7 N-m)
(1.1 N-m)
(1.7 N-m)
+ / – SENSE, TRIM Terminals
All Models
Sized to accept Amp Faston© insulated
receptacle #2-520184-2.
Figure 17–2 — Output terminal connections
Rev 3.5
Apps. Eng. 800 927.9474
vicorpower.com
800 735.6200
17. DC Input Power System (ComPAC / MI-ComPAC Family)
Design Guide & Applications Manual
For VI-200 and VI-J00 Family DC-DC Converters and Configurable Power Supplies
THERMAL DATA
Operating Ambient Temperature. Depends on factors
such as output power, availability of forced air, and
mounting technique. DO NOT allow the ComPAC to
exceed its maximum operating temperature, which is
reached when the case is 85˚C. Temperature measured at
center of heat sink. (Full power can be delivered up to this
temperature.) Refer to Section 20, Thermal Curves, to
determine the maximum ambient temperature for your
application.
Thermal Impedance, Free Convection.
Thermal resistance baseplate to air (˚C/W):
Type of
Mounting
Vertical
Horizontal
1-Up
2.44
3.60
2-Up
1.17
1.70
3-Up
0.76
1.35
Forced Convection. Thermal resistance baseplate to air
(horizontal mount):
NOTE: To ensure proper heat transfer from the
internal module(s) to the heat sink, the mounting
holes through the heat sink must be properly
torqued at all times during operation. If the unit is
operated unmounted, insert a #6 or metric M3.5
flathead screw through each hole from below and
secure with a nut on top, torqued to 6 lb-in (0.83 N-m).
1-Up
3.6
2.7
2.3
1.6
1.15
0.9
0.78
Thermal Resistance (°C / W)
2-Up
1.7
1.4
1.3
0.97
0.70
0.54
0.45
3-Up
1.35
1.26
1.11
0.82
0.58
0.46
0.38
Airflow (LFM)
0
50
100
250
500
750
1,000
NOTE: A 1.37" (34,8 mm) heat sink, option H1,
is also available.
VI-200 and VI-J00 Family Design Guide
Page 54 of 98
Rev 3.5
Apps. Eng. 800 927.9474
vicorpower.com
800 735.6200