Power supplies and
DC/DC converters
SFB (selective fuse breaking) technology:
• Six times the nominal current for 12 ms
• Reliably switches off faulty current paths in the event of
a short circuit
• Important system parts remain in operation without any
interruption
For more information, refer to page 6 and onwards.
2
PHOENIX CONTACT
Contents
Overview of power supplies
Page 4 – 5
Power supplies
SFB technology
Page 6 – 7
QUINT POWER
Page 8 – 10
QUINT POWER for
extreme requirements
TRIO POWER
Page 12 – 13
UNO POWER
Page 14 – 15
MINI POWER
Redundancy modules
Page 16 – 17
STEP POWER
Page 18 – 19
ACM (auto current balancing) technology:
• Even distribution of the load for redundant power supplies
DC/DC converters
Page 20 – 23
• Low thermal load for both power supplies
• Service life of the redundant solution is doubled
For more information, refer to page 26 and onwards.
Page 11
Power supplies
for frequency inverters
Redundancy modules
Page 24 – 25
Page 26 – 29
Uninterruptible power supplies (UPS)
IQ technology
Page 30 – 33
QUINT UPS
Page 34 – 35
Power storage for QUINT UPS
Selection guide for QUINT UPS
Signaling and configuration
IQ
Communication
Page 36 – 37
Page 38 – 41
Page 42 – 43
Page 44 – 45
UPS with integrated
power storage
Page 46 – 47
Uninterruptible power supplies
UPS with integrated
power supply
Page 48 – 49
IQ technology:
Accessories
Page 50
• Intelligent battery management
• Optimizes and keeps you informed of the remaining runtime,
state of charge, and service life of the power storage
Standards and approvals
Page 51 – 55
• Optimized charging characteristic for maximum service life
• Communication with higher-level controllers
For more information, refer to page 30 and onwards.
PHOENIX CONTACT
3
Power supplies –
a comparison of the advantages
The product ranges differ with regard to
their design, performance, and functionality.
Select the ideal solution based on your
requirements:
Functionality
• QUINT POWER
Maximum functionality
• TRIO POWER
Robust standard functionality
• UNO POWER
Compact basic functionality
The product range is supplemented with
types tailor-made for specific applications:
• MINI POWER for measurement and
control technology
• STEP POWER for installation distributors
4
PHOENIX CONTACT
Power/current
STEP POWER
MINI POWER
UNO POWER
TRIO POWER
QUINT POWER
•
•
•
•
•
Worldwide use
thanks to the wide range input and
international approval package
•
•
•
•
•
Maximum operating time
thanks to high MTBF > 500,000 h at 40°C
•
•
•
•
•
Can be switched in parallel
for increased performance and redundancy
•
•
•
•
•
Outdoor installation permitted
thanks to wide temperature range from
- 25°C ... +70°C
•
•
Three-phase devices
error-free operation, even if one phase fails
permanently
•
•
Active function monitoring
by means of switching output for remote diagnostics
•
Quick installation
thanks to tool-free push-in connection
•
•
•
Reliable starting of difficult loads
with the dynamic power reserve
•
Easy system extension
with the POWER BOOST static power reserve
•
Preventive function monitoring
indicates critical operating states before
errors occur
•
Fast tripping of circuit breakers
thanks to SFB technology
PHOENIX CONTACT
5
QUINT POWER power supplies for
superior system availability thanks to
SFB technology
Compact power supplies and DC/DC
converters from the QUINT POWER range
maximize the availability of your system.
Even standard circuit breakers can be
tripped reliably and quickly with SFB
(selective fuse breaking) technology and
six times the nominal current for 12 ms.
Faulty current paths are switched off
selectively, the fault is located, and
important system parts remain in
operation.
Comprehensive diagnostics are provided
through constant monitoring of the output
voltage and output current. This preventive
function monitoring visualizes critical
operating states and indicates them to the
controller before errors can occur.
QUINT POWER guarantees superior
system availability.
6
PHOENIX CONTACT
Cost-effective selective protection with SFB technology
In order to trip standard circuit breakers
magnetically and therefore quickly, power
supplies must be able to supply several
times the nominal current for a short
period. With SFB technology, which
supplies up to six times the nominal
current for 12 ms, a dynamic power
reserve is available.
Example: frayed display cable – the
fuse trips, the lower-level display is dark.
The controller, sensors, and actuators
continue to operate without
interruption – production continues.
The maximum cable lengths are described
in the configuration matrix, which is
available as a free download on the
Phoenix Contact website under “Power
supplies with maximum functionality”.
In addition, tailor-made thermomagnetic
circuit breakers, which trip even with
extremely long cables, are designed
specifically for SFB technology.
PHOENIX CONTACT
7
QUINT POWER power supplies –
maximum functionality
The unique SFB technology and preventive
function monitoring of the QUINT
POWER power supply increase the
availability of your application.
• Worldwide use
thanks to the wide range input and
international approval package
• High operational reliability
thanks to high MTBF > 500,000 h,
long mains buffering times > 20 ms,
high electric strength of single-phase
devices of up to 300 V AC
• Three-phase devices
enable error-free operation, even in the
event of a permanent phase failure,
high surge resistance of up to 6 kV thanks
to integrated gas-filled surge arrester
• Comprehensive approvals,
e.g., semiconductor production:
SEMI F47-0706
Shipbuilding:
GL, ABS, BV, LR, NK, DNV, RINA
Medical standard: IEC 60601
DeviceNet™
ATEX
8
PHOENIX CONTACT
Your advantages
Fast tripping of standard circuit breakers
• Dynamic power reserve with SFB technology with
up to six times the nominal current for 12 ms
Preventive function monitoring
• Indicates critical operating states before errors
occur, thanks to permanent monitoring of the
output voltage and output current
• Remote monitoring using active switching
outputs and floating relay contact
Reliable starting of difficult loads and
easy system extension
• POWER BOOST static power reserve with up to
1.5 times the nominal current permanently
Easy-maintenance connection technology
• Coded COMBICON connectors
(up to and including 10 A)
Minimize installation costs
• Third negative terminal block for grounding on the
secondary side
Compensation of voltage drops
• Output voltage can be set on the front
• A voltage range of 5 … 56 V DC can be covered
with three power supplies with output voltages of
12, 24, and 48 V DC
Saves over 50% space in the control cabinet
• Slim design, e.g., 40 A output current in 96 mm wide
housing
Robust design
• Metal housing and wide temperature range
from -25°C to +70°C
• Device startup at -40°C (type-tested)
• Devices with protective coating from -40°C to +70°C
PHOENIX CONTACT
9
QUINT POWER 1˜
Input: 1-phase, 85 ... 264 V AC, 90 ... 350 V DC, for 24 V/40 A and 48 V/20 A: 90 ... 300 V DC
125
125
130
130
130
130
125
130
125
125
180
32
90
60
40
24 V / 3.5 A
24 V / 5 A
24 V / 10 A
24 V / 20 A
24 V / 40 A
QUINT-PS/1AC/24DC/3.5
2866747
QUINT-PS/1AC/24DC/5
2866750
QUINT-PS/1AC/24DC/10
2866763
QUINT-PS/1AC/24DC/20
2866776
QUINT-PS/1AC/24DC/40
2866789
48 V / 5 A
48 V / 10 A
48 V / 20 A
QUINT-PS/1AC/48DC/5
2866679
QUINT-PS/1AC/48DC/10
2866682
QUINT-PS/1AC/48DC/20
2866695
12 V / 15 A
12 V / 20 A
QUINT-PS/1AC/12DC/15
2866718
QUINT-PS/1AC/12DC/20
2866721
QUINT POWER 3˜
Input: 3-phase, 3 x 320 ... 575 V AC, 450 ... 800 V DC
125
60
130
130
130
40
176
125
130
125
69
96
24 V / 5 A
24 V / 10 A
24 V / 20 A
24 V / 40 A
QUINT-PS/3AC/24DC/5
2866734
QUINT-PS/3AC/24DC/10
2866705
QUINT-PS/3AC/24DC/20
2866792
QUINT-PS/3AC/24DC/40
2866802
48 V / 20 A
QUINT-PS/3AC/48DC/20
2320827
Accessories
Fan for QUINT, QUINT-PS/FAN/4
2320076
With the standard power supply mounting position, the temperature range
increases by 10 K (max. ambient temperature of 70°C); when the mounting
position is rotated, position-dependent derating no longer applies. Tool-free
mounting.
10
PHOENIX CONTACT
Thermomagnetic circuit breakers for QUINT
Device circuit breakers with the SFB tripping characteristic provide
maximum overcurrent protection – even in large systems with long
cable paths. The comprehensive product range can be found on the
Phoenix Contact website under “Products/Protective devices”.
QUINT POWER power supplies for
extreme requirements
These power supplies in the QUINT series
satisfy the most stringent requirements of
sensitive loads. DC/DC converters with the
same properties can be found on page 23.
For extreme ambient conditions:
• Coating on the PCB protects against
dust, corrosive gases, and 100%
humidity as well as failure caused by
corrosion-related creepage currents and
electrochemical migration
• Wide temperature range from
-40°C to +70°C
Inaccessible parts of the PCB are
protected by the coating, e.g.,
wired components (coated areas
appear blue).
For sensitive loads, e.g., in process
technology: OVP (Over Voltage
Protection) limits surge voltages to 32 V,
also useful in redundant operation with
QUINT ORING (see page 26).
QUINT POWER, coated
Input: 1-phase: 85 ... 264 V AC, 90 ... 410 V DC, for 1 AC / 24 V / 20 A: 90 ... 350 V DC / 3-phase: 3 x 320 ... 575 V AC, 450 ... 800 V DC
125
40
125
130
130
130
125
60
130
125
90
69
1 AC / 24 V / 5 A
1 AC / 24 V / 10 A
1 AC / 24 V / 20 A
3 AC / 24 V / 20 A
QUINT-PS/1AC/24DC/5/CO
2320908
QUINT-PS/1AC/24DC/10/CO
2320911
QUINT-PS/1AC/24DC/20/CO
2320898
QUINT-PS/3AC/24DC/20/CO
2320924
PHOENIX CONTACT
11
TRIO POWER power supplies –
robust standard functionality
The TRIO POWER power supplies are
perfect for use in machine building. All
functions and the space-saving design
are tailored to the high requirements in
this field. The power supply units, which
feature an extremely robust electrical
and mechanical design, ensure the reliable
supply of all loads even under harsh
ambient conditions.
Save time thanks to quick and easy installation
with push-in connection
Your advantages for TRIO
POWER with push-in connection
Very cost-effective
• Quick installation, thanks to tool-free push-in
connection
• Slim design
Reliable starting of difficult loads
• Dynamic power reserve with 150% of the
nominal current for 5 s
Robust design
• Robust electrical design with high
electric strength of single-phase devices
up to 300 V AC, error-free function of
the three-phase modules, even if one
phase fails permanently
• Robust mechanical design with vibration
resistance up to 4g and shock resistance
up to 30g
• High MTBF > 1 million hours
• Metal housing from 10 A and wide
temperature range from -25°C to +70°C
• Device startup at -40°C (from 10 A,
type-tested)
12
PHOENIX CONTACT
TRIO POWER push-in connection 1˜
Input: 1-phase, 85 ... 264 V AC, 99 ... 275 V DC
130
35
30
160
160
130
130
115
130
115
68
42
24 V / 3 A
24 DC / 5 A
24 DC / 10 A
24 DC / 20 A
TRIO-PS-2G/1AC/24DC/3/C2LPS
2903147
TRIO-PS-2G/1AC/24DC/5
2903148
TRIO-PS-2G/1AC/24DC/10
2903149
TRIO-PS-2G/1AC/24DC/20
2903151
Certified according to UL 1310/508
Listed Class 2
TRIO POWER push-in connection 3˜
Accessories
Input: 3-phase, 3 x 320 ... 575 V AC, 2 x 360 ... 575 V AC, 450 ... 780 V DC
121
130
160
130
130
160
35
130
115
Electronic device circuit breakers
65
42
41
24 V / 5 A
24 DC / 10 A
24 DC / 20 A
4-channel
TRIO-PS-2G/3AC/24DC/5
2903153
TRIO-PS-2G/3AC/24DC/10
2903154
TRIO-PS-2G/3AC/24DC/20
2903155
CBM E4 24DC/0,5-10A NO-R
2905743
8-channel
CBM E8 24DC/0,5-10A NO-R
2905744
TRIO POWER screw connection 1˜
… 3˜
Input: 1-phase, 85 ... 264 V AC
3-phase, 3 x 320 ... 575 V AC
130
130
130
130
32
40
190
152.5
152.5
60
130
115
115
115
139
12 V / 5 A
12 V / 10 A
48 V / 5 A
48 V / 10 A
24 V / 40 A
TRIO-PS/1AC/12DC/5
2866475
TRIO-PS/1AC/12DC/10
2866488
TRIO-PS/1AC/48DC/5
2866491
TRIO-PS/1AC/48DC/10
2866501
TRIO-PS/3AC/24DC/40
2866404
PHOENIX CONTACT
13
UNO POWER power supplies –
compact basic functionality
Thanks to their high power density,
UNO POWER power supplies offer the
ideal solution for loads up to 240 W,
particularly in compact control boxes.
The wide range of products covers all
common voltage levels.
With nominal voltages from 5 V DC to 48 V DC, UNO POWER
covers all the typical voltage levels used in the industry
Your advantages
Maximum energy efficiency
• Save energy, thanks to high efficiency of up to 94%
• Save energy, thanks to extremely low idling losses
below 0.3 W
Extremely compact
• Save space in the control cabinet, thanks to the
extremely high power density of 325 W/dm³,
e.g., 240 W power in narrow 45 mm housing
• Housing depth of just 84 mm up to 100 W,
tailored to all popular 120 mm control boxes
Outdoor installation
• Wide temperature range from -25°C to +70°C
SAVE ENERGY
14
PHOENIX CONTACT
UNO POWER 1~
Input: 1-phase, 85 ... 264 V AC
125
125
84
84
35
22.5
24 DC / 30 W
130
90
90
90
130
84
24 DC / 60 W
UNO-PS/1AC/24DC/30W UNO-PS/1AC/24DC/60W
2902991
2902992
55
24 DC / 100 W
UNO-PS/1AC/24DC/100W
2902993
37
24 DC / 150 W
45
24 DC / 240 W
UNO-PS/1AC/24DC/150W UNO-PS/1AC/24DC/240W
2904376
2904372
24 DC / 90 W *
UNO-PS/1AC/24DC/90W/C2LPS
2902994
48 DC / 60 W
48 DC / 100 W
UNO-PS/1AC/48DC/60W
2902995
UNO-PS/1AC/48DC/100W
2902996
15 DC / 55 W
15 DC / 100 W
15 DC / 30 W
UNO-PS/1AC/15DC/30W UNO-PS/1AC/15DC/55W
2903000
2903001
12 DC / 30 W
12 DC / 55 W
UNO-PS/1AC/12DC/30W UNO-PS/1AC/12DC/55W
2902998
2902999
5 DC / 25 W
5 DC / 40 W
UNO-PS/1AC/5DC/25W
2904374
UNO-PS/1AC/5DC/40W
2904375
UNO-PS/1AC/15DC/100W
2903002
12 DC / 100 W
UNO-PS/1AC/12DC/100W
2902997
UNO POWER 2~
Input: 2-phase, 264 ... 575 V AC
90
84
55
24 DC / 90 W *
UNO-PS/2AC/24DC/90W/C2LPS
2904371
* Certified according to UL 1310/508 Listed Class 2
PHOENIX CONTACT
15
MINI POWER power supplies
for measurement and control technology
Modular electronics housing is used as
standard in measurement and control
technology. MINI POWER is the ideal
power supply for this type of application.
Your advantages
Easy-maintenance connection technology
• Coded COMBICON connectors
Flexible
• Numerous output voltages and versions
available
Function monitoring
• Active function monitoring via the switching
output for remote monitoring of the output
voltage
16
PHOENIX CONTACT
MINI POWER 1˜
Input: 1-phase, 85 ... 264 V AC, 90 ... 350 V DC
107
107
99
99
99
107
22.5
45
45
24 V / 1.3 A
24 V / 2 A
±15 V / 1 A
MINI-PS-100-240AC/24DC/1.3
2866446
MINI-PS-100-240AC/24DC/2
2938730
MINI-PS-100-240AC/2x15DC/1
2938743
5V/3A
10 ... 15 V / 2 A
MINI-PS-100-240AC/5DC/3
2938714
MINI-PS-100-240AC/10-15DC/2
2938756
Input: 1-phase, 85 ... 264 V AC, 90 ... 350 V DC
Input: 1-phase, 85 ... 264 V AC
107
99
95
99
99
107
67.5
67.5
35
24 V / 4 A
24 V / 100 W
24 V / 1.5 A
MINI-PS-100-240AC/24DC/4
2938837
MINI-PS-100-240AC/24DC/C2LPS
2866336
MINI-SYS-PS-100-240AC/24DC/1.5
2866983
10 ... 15 V / 8 A
MINI-PS-100-240AC/10-15DC/8
2866297
Certified according to UL 1310/508 Listed Class 2
24 V / 1.5 A
MINI-PS-100-240AC/24DC/1.5/EX
2866653
Accessories for 24 V / 1.5 A
DIN rail connector
ME 17,5 TBUS 1.5/5-ST-3,82 GN
2709561
Optional, 2 required per power supply
(24 V/1.5 A)
PHOENIX CONTACT
17
STEP POWER power supplies
for installation distributors
STEP POWER power supplies are ideal
for installation distributors and flat control
panels. The low idling losses and the high
degree of efficiency ensure maximum
energy efficiency in its class.
When mounting on level surfaces: lugs integrated
in the housing eliminate the need for additional
mounting material
Your advantages
Flexible mounting
• Snap onto the DIN rail or screw on a level surface
Reliable supply
• High MTBF > 500,000 h
• U/I characteristic curve for supplying capacitive
loads
Outdoor installation
• Wide temperature range from -25°C to +70°C
Use in domestic installation
• All 18 W devices meet standard EN 60335-1
for household appliances and are suitable for
installation in ventilation systems, for example
Save energy
• Maximum energy efficiency
and incredibly low idling
losses
18
PHOENIX CONTACT
SAVE ENERGY
STEP POWER 1˜
Input: 1-phase, 85 ... 264 V AC, 95 ... 250 V DC
43
61
61
Flat
design
90
90
90
90
61
54
36
36
18
24 V / 0.5 A
24 V / 0.75 A FL
STEP-PS/1AC/24DC/0.5
2868596
STEP-PS/1AC/24DC/0.75/FL
2868622
STEP-PS/1AC/24DC/0.75
2868635
24 V / 0.75 A
STEP-PS/1AC/24DC/1.75
2868648
24 V / 1.75 A
12 V / 1 A
12 V / 1.5 A FL
12 V / 1.5 A
12 V / 3 A
STEP-PS/1AC/12DC/1
2868538
STEP-PS/1AC/12DC/1.5/FL
2868554
STEP-PS/1AC/12DC/1.5
2868567
STEP-PS/1AC/12DC/3
2868570
5V/2A
STEP-PS/1AC/5DC/2
2320513
61
61
61
72
90
90
90
90
61
72
90
90
24 V / 2.5 A
5 V / 6.5 A
24 V / 4.2 A
24 V / 100 W
STEP-PS/1AC/24DC/2.5
2868651
STEP-PS/1AC/5DC/6.5
2868541
STEP-PS/1AC/24DC/4.2
2868664
STEP-PS/1AC/24DC/3.8/C2LPS
2868677
12 V / 5 A
15 V / 4 A
48 V / 2 A
Certified according to UL 1310/508
Listed Class 2
STEP-PS/1AC/12DC/5
2868583
STEP-PS/1AC/15DC/4
2868619
STEP-PS/1AC/48DC/2
2868680
STEP for 48 V AC
STEP for 277 V AC
Input: 1-phase,
43 ... 52 V AC, 60 ... 80 V DC
Input: 1-phase,
85 ... 305 V AC, 95 ... 250 V DC
61
90
90
61
18
90
48 V AC / 24 DC / 0.5 A
277 V AC / 24 DC / 3.5 A
STEP-PS/48AC/24DC/0.5
2868716
STEP-PS/277AC/24DC/3.5
2904945
PHOENIX CONTACT
19
DC/DC converters
adapt voltages
QUINT and MINI DC/DC converters alter
the voltage level, regenerate the voltage
at the end of long cables or enable the
creation of independent supply systems by
means of electrical isolation.
Your advantages
Regeneration of the output voltage
• Constant voltage, even at the end of long cables
• Wide input voltage range
- 24 V: 18 ... 32 V DC,
from 14 ... 32 V DC during operation
- 12 V: 9 ... 18 V DC
- 48 V: 30 ... 60 V DC
- 42 ... 96 V DC and 67 ... 154 V DC
wide range inputs
Fast tripping of standard circuit breakers
• Dynamic power reserve with SFB technology with
up to six times the nominal current for 12 ms
(for details on SFB technology, see pages 6/7)
Preventive function monitoring
• Indicates critical operating states before errors
occur, thanks to permanent monitoring of the
input voltage, output voltage, and output current
• Remote monitoring using active switching output
and floating relay contact
Reliable starting of difficult loads and easy
system extension
• POWER BOOST static power reserve with up to
1.25 times the nominal current permanently
20
PHOENIX CONTACT
QUINT DC/DC converters
High degree of flexibility thanks to wide
input voltage ranges, e.g., for railway
applications or power generation.
QUINT DC/DC converters
All common input and output voltages
in performance classes up to 480 W
for all industries as well as devices with
approvals for the process industry.
MINI DC/DC converters
All common input and output voltages
in performance classes up to 24 W for
measurement and control technology.
Voltage levels
Input
Input
Output
12 V DC
(9 ... 18 V DC)
Output
Input
Output
12 V DC
(5 ... 18 V DC)
12 - 24 V DC
(10 ... 32 V DC)
5 - 15 V DC
(5 ... 15 V DC)
24 V DC
(18 ... 32 V DC)
24 V DC
(18 ... 29.5 V DC)
12 - 24 V DC
(10 ... 32 V DC)
24 V DC
(22.5 ... 28.5 V DC)
48 V DC
(30 ... 60 V DC)
48 V DC
(30 ... 56 V DC)
48 - 60 V DC
(36 ... 75 V DC)
48 V DC
(30 ... 56 V DC)
60 ... 72 V DC
(42 ... 96 V DC)
24 V DC
(18 ... 29.5 V DC)
96 ... 110 V DC
(67.2 ... 154 V DC)
PHOENIX CONTACT
21
QUINT DC/DC converters
Input: 1-phase, 18 ... 32 V DC
125
32
82
48
24 DC / 24 DC / 5 A
24 DC / 24 DC / 10 A
24 DC / 24 DC / 20 A
QUINT-PS/24DC/24DC/5
2320034
QUINT-PS/24DC/24DC/10
2320092
QUINT-PS/24DC/24DC/20
2320102
24 DC / 12 DC / 8 A
24 DC / 48 DC / 5 A
QUINT-PS/24DC/12DC/8
2320115
QUINT-PS/24DC/48DC/5
2320128
Input: 1-phase, 30 ... 60 V DC
125
130
130
125
Input: 1-phase, 30 ... 60 V DC
32
125
130
Input: 1-phase, 9 ... 18 V DC
32
48
12 DC / 24 DC / 5 A
48 DC / 24 DC / 5 A
48 DC / 48 DC / 5 A
QUINT-PS/12DC/24DC/5
2320131
QUINT-PS/48DC/24DC/5
2320144
QUINT-PS/48DC/48DC/5
2905008
12 DC / 12 DC / 8 A
QUINT-PS/12DC/12DC/8
2905007
Input: 1-phase, 42 ... 96 V DC
Input: 1-phase, 67.2 ... 154 V DC
125
130
130
125
48
22
125
130
130
130
125
48
60 ... 72 DC / 24 DC / 10 A
96 ... 110 DC / 24 DC / 10 A
QUINT-PS/60-72DC/24DC/10
2905009
QUINT-PS/96-110DC/24DC/10
2905010
PHOENIX CONTACT
QUINT DC/DC converters, coated
Input: 1-phase, 18 ... 32 V DC
125
125
130
130
130
125
32
82
48
24 V / 24 V / 5 A
24 V / 24 V / 10 A
24 V / 24 V / 20 A
QUINT-PS/24DC/24DC/5/CO
2320542
QUINT-PS/24DC/24DC/10/CO
2320555
QUINT-PS/24DC/24DC/20/CO
2320568
For details on protective coating, see page 11.
Input: 1-phase, 42 ... 96 V DC
Input: 1-phase, 67.2 ... 154 V DC
130
125
130
125
48
48
60 ... 72 DC / 24 DC / 10 A
96 ... 110 DC / 24 DC / 10 A
QUINT-PS/60-72DC/24DC/10/CO
2905011
QUINT-PS/96-110DC/24DC/10/CO
2905012
MINI DC/DC converters
Accessories
Input: 1-phase, 10 ... 32 V DC, 36 ... 75 V DC
107
107
107
99
107
99
99
99
107
99
Input: 1-phase, 10 ... 42 V AC
22.5
22.5
12 ... 24 DC / 24 DC / 1 A
48 ... 60 DC / 24 DC / 1 A
MINI-PS-12-24DC/24DC/1
2866284
MINI-PS-48-60DC/24DC/1
2866271
22.5
22.5
12 ... 24 DC / 5 ... 15 DC / 2 A 12 ... 24 DC / 48 DC / 0.7 A
MINI-PS-12-24DC/5-15DC/2
2320018
MINI-PS-12-24DC/48DC/0.7
2320021
22.5
10 ... 42 V AC / 15 ... 60 V DC / 3 A
MINI-PS-10-42AC/15-60DC/3
2320199
• AC power terminal
• AC voltage of a transformer is
rectified and filtered
PHOENIX CONTACT
23
Power supplies for
frequency inverters
These power supplies are specifically
designed for connection to frequency
inverters. In the event of mains failure,
the DC intermediate circuit voltage of the
inverter continues to supply all connected
24 V loads without interruption.
Your advantages
Compact buffer solution
• Maintenance-free buffer solution: controlled
machine stop in the event of mains failure by using
the existing capacity in the frequency inverter
• Compact solution in one housing: parallel
operation on two-phase AC mains and a DC
intermediate circuit
Fast tripping of standard circuit breakers
• Dynamic power reserve with SFB technology with
120 A for 20 ms (for details on SFB technology,
see pages 6/7)
Preventive function monitoring
• Indicates critical operating states before errors
occur, thanks to permanent monitoring of the
output voltage and output current
• Remote monitoring using active switching output
and floating relay contact
Reliable starting of difficult loads and easy
system extension
• POWER BOOST static power reserve supplies
26 A permanently
24
PHOENIX CONTACT
DCIN
OK
I<
IN
DC OK
13
14
ILC 191 ME/AN
Order-No.: 2700074
HW/FW: 00/100
MAC Addr. 8Block:
xx. xx. xx. xx
RDY
FAIL
E
I1
UL
FF
I3
I4
US
SF
Q1
Q2
I5
I6
P1
P2
UM
SF
Q3
Q4
I7
I8
D1
D2
FR
AUTOMATIONWORX
Output
I2
PF
BSA
S1
TxD
S5
O1
O2
RxD
Boost
X1
DC OK
MRESET
STOP
RESET
RUN/PROG
QUINT POWER for
frequency inverters
18-29.5V
PRG
ACT
Input
X2.1
DCIN OK
LNK
Input 2AC 400-500V
L1 L2
X2.2
LNK
Function
Voltage
X1
Power In
24 V
X2
dig. Out
24 V
X3
dig. In
24 V
X4
PWM / PTO
X5
ACT
Output DC 24 V 20 A
Input DC 600V
Nr.
PWR
5V
RS485/422
X6
analog In
0 - 10 V
X7
analog Out
0 - 10 V
Controller
18 ... 29.5 V DC
2 x 360 ... 575 V AC
450 ... 840 V DC
+
L1
L2
L3
Motor
controller
Supply unit
QUINT POWER is connected to two outer
conductors of the three-phase system and to a
DC voltage. This can be the DC intermediate
circuit voltage of a frequency inverter or, as in this
example, a supply unit. In the event of mains failure,
the controller continues to be supplied by using the
kinetic energy of the motors. This enables a controlled
machine stop. Quick and error-free restart of the
machine is therefore ensured when the supply voltage
is restored.
Motor
TRIO POWER, 1 DC
QUINT POWER, 2 AC / 1 DC
Input: 450 V DC ... 840 V DC
Input: 2 x 360 ... 575 V AC, 450 ... 840 V DC
152.5
130
130
125
115
120
24 V / 20 A
24 V / 20 A
TRIO-PS/600DC/24DC/20
2866530
QUINT-PS/2AC/1DC/24DC/20
2320830
PHOENIX CONTACT
25
Active redundancy module for
superior system availability
thanks to ACB technology
The ACB (auto current balancing)
technology of the QUINT ORING modules
doubles the service life of redundantly
operated power supplies by utilizing both
power supply units to an equal degree.
The load current is automatically
distributed symmetrically.
Two QUINT POWER power supplies
combined with QUINT ORING limit the
voltage to a maximum of 32 V DC even in
the event of two faults. In this way, loads
are reliably protected against permanent
surge voltages and dangerous states.
50%
power
ACB technology doubles the service life
In applications with the highest demands regarding
operational reliability, redundant power supply solutions are
implemented to ensure that the failure of a power supply unit
does not result in system downtime.
As a result of asymmetries, the load is often supplied by one
power supply unit, while the other runs in no-load operation.
This results in a thermal load on the working power supply
unit and therefore rapid aging. If the power supply unit is
operated at half the nominal current, it remains significantly
cooler.
The ACB technology of the QUINT ORING modules ensures
symmetrical loading of the power supplies and thereby up to
double the service life of the redundant system.
26
PHOENIX CONTACT
50%
power
Your advantages
Preventive function monitoring
• Permanent monitoring of the input voltage, output
current, and decoupling section
Consistent redundancy
• Redundant wiring up to the load with two positive
output terminal blocks
Double the service life
• Thanks to even load distribution
70% energy saving
• Decoupling is implemented with MOSFETs instead
of diodes
OVP (Over Voltage Protection)
• Surge voltages are limited to 32 V
• Doubly failsafe with:
2 x QUINT POWER and 1 x QUINT ORING
Robust design
• Protective coating for extreme requirements
• Approvals for use in potentially explosive areas
PHOENIX CONTACT
27
Decoupling, monitoring, and
controlling redundancy modules
A redundant power supply system is the
result of the parallel connection of two
power supply units. In order to increase
system availability, the power supplies must
be decoupled and the redundancy must
be monitored. The following are ideal
solutions:
Decoupling, monitoring, and control
Decoupling with active redundancy module + monitoring of
the power supply unit voltages, the wiring, decoupling, and the
load current.
Power supply 1
• Decoupling, monitoring, and control
Load
Power supply 2
• Decoupling and monitoring
• Decoupling
Decoupling and monitoring
Decoupling with redundancy module + monitoring of
the power supply unit voltages and the wiring.
Power supply 1
Load
Power supply 2
Decoupling
Decoupling with diode.
Power supply 1
Load
Monitored
Not monitored
28
PHOENIX CONTACT
Power supply 2
QUINT ORING
Input: 18 ... 28 V DC
125
125
130
130
130
125
66
38
32
24 V / 2 x 10 A / 1 x 20 A
24 V / 2 x 20 A / 1 x 40 A
24 V / 2 x 40 A / 1 x 80 A
QUINT-ORING/24DC/2x10/1x20
2320173
QUINT-ORING/24DC/2x20/1x40
2320186
QUINT-ORING/24DC/2x40/1x80
2902879
TRIO DIODE
Input: 10 ... 30 V DC, 30 ... 56 V DC
115
130
130
115
32
32
12 ... 24 V / 2 x 10 A / 1 x 20 A
48 V / 2 x 10 A / 1 x 20 A
TRIO-DIODE/12-24DC/2x10/1x20
2866514
TRIO-DIODE/48DC/2x10/1x20
2866527
QUINT DIODE
UNO DIODE
STEP DIODE
Input: 10 ... 30 V DC, 30 ... 56 V DC
Input: 4.5 V ... 30 V DC
Input: 4.5 V ... 30 V DC
125
90
90
130
50
61
84
130
125
50
22.5
18
12 ... 24 V / 2 x 20 A / 1 x 40 A
48 V / 2 x 20 A / 1 x 40 A
5 ... 24 V DC
5 ... 24 V / 2 x 5 A / 1 x 10 A
QUINT-DIODE/12-24DC/2x20/1x40
2320157
QUINT-DIODE/48DC/2x20/1x40
2320160
UNO-DIODE/5-24DC/2x10/1x20
2905489
STEP-DIODE/5-24DC/2x5/1x10
2868606
Intelligent UPS system for
superior system availability
thanks to IQ technology
Uninterruptible power supplies (UPS)
continue to deliver power even in the event
of mains failure. With our IQ technology,
you are one step ahead:
• You know the state of charge and
remaining runtime of your power storage
• You are warned about failures at an early
stage and have time to prevent them
• You can maximize the service life of the
power storage
• You can transfer all relevant information
to your computer and higher-level
controllers
30
PHOENIX CONTACT
IQ
Intelligence for superior system availability
Task: an industrial PC must be
continuously supplied with 24 V DC.
Previous solution: the UPS with
3.4 Ah buffers 24 V DC/5 A for
20 minutes under optimum conditions.
Can the power storage actually bridge
this time? State of charge, performance,
and remaining runtime of the power
storage are unknown.
Solution with QUINT UPS: the
intelligent UPS determines all relevant
power storage states. This ensures the
transparency required to guarantee the
stability of the supply and optimum use
of the power storage at all times.
The intelligent battery management
detects the current state of charge of
the connected power storage and uses
this to calculate the remaining runtime.
The QUINT UPS also indicates whether
the buffer time is actually 20 minutes.
As soon as an adjustable threshold value
is reached, a warning message is sent via
the floating relay contact, the software
or directly to higher-level controllers.
The IPC continues working for as long
as possible and is shut down before the
battery voltage runs out.
PHOENIX CONTACT
31
Intelligence in
any combination
Create your own individual solution –
tailored to your application.
1. Choose your power supply:
Compact QUINT POWER power supplies
ensure superior system availability.
2. Choose your UPS module:
The intelligent QUINT UPS actively informs
you when necessary.
•
•
•
•
32
•
QUINT UPS
QUINT BUFFER
TRIO UPS
UNO UPS
MINI UPS
STEP UPS
3. Choose your power storage:
• UPS-CAP for maximum service life
• UPS-BAT/LI-ION for long service life with
long buffer times
• UPS-BAT/VRLA and VRLA-WTR
for maximum buffer times
•
IQ technology
•
Flexible thanks to various
power storage technologies
•
Communication-capable
•
Configurable
•
UPS modules with integrated
power storage
•
PHOENIX CONTACT
UPS modules with integrated
power supply
~
Power supply
+
~
–
~
UPS module
+
–
+
–
Power storage
IQ
The IQ technology is intuitive
and provides you with
information as soon as it is
required.
Intelligent battery management
SOC (state of charge) – current state
of charge and remaining runtime of the
power storage.
SOH (state of health) – remaining life
expectancy of the power storage, warns
of failure at an early stage.
Intelligent battery control
Detects the connected battery type
automatically and maximizes the
remaining service life of the power
storage by means of an optimally
adapted charging characteristic.
Intelligent charging
Adapts the charging current, thereby
ensuring the fastest possible recharging
and availability.
Data port
Used for communication between
the UPS module and PC/higher-level
controller.
PHOENIX CONTACT
33
UPS modules for
DC applications
The UPS module for 24 V DC with output
currents ranging from 5 to 40 A allows you
to create a custom solution combining a
power supply, UPS module, and
power storage.
IQ
Your advantages
Optimum use of the buffer time and
preventive monitoring of the power storage
• Detects the current state of charge of the power
storage and calculates the remaining runtime
• Calculates the current life expectancy of the
power storage
Rapid battery charging
• Adaptive current management charges the battery
twice as fast as before, while simultaneously
providing sufficient energy for the loads
Comprehensive signaling and
parameterization
• Floating relay contacts
• Data port
• Parameterization with memory module
Substantial power reserve
• For mains and battery operation
• POWER BOOST static power reserve
• Dynamic power reserve with SFB
(selective fuse breaking) technology
~
+
–
Power supply UPS module Power storage
34
PHOENIX CONTACT
UPS module for
AC applications
The UPS module for 120 V AC/230 V AC
delivers a pure sine curve at the output.
For 400 W/500 VA of power, only one
power storage is required, the power
supply is already integrated.
IQ
Your advantages
Optimum use of the buffer time and
preventive monitoring of the power storage
• Detects the current state of charge of the power
storage and calculates the remaining runtime
• Calculates the current life expectancy of the
power storage
Worldwide use
• Input voltages from 102 … 264 V AC
• Pure sine curve: the sine generated in battery
operation is synchronous with the mains
previously used for supply
• In the event of mains failure, the output is
automatically supplied with 120 V AC/60 Hz or
230 V AC/50 Hz
• Manual voltage pre-selection possible
Maximum efficiency
• Offline operation: 98% efficiency with charged
power storage
Comprehensive signaling and
parameterization
• Switching outputs
• USB interface
• Data port
• Parameterization with memory module
Simplified startup
• The UPS can be switched on without a power
supply network (isolated operation)
Power supply UPS module Power storage
PHOENIX CONTACT
35
QUINT UPS
power storage
You can always find the ideal solution
for superior system availability with the
modular system for uninterruptible power
supplies.
Type
Buffer time
(typical)
Temperature
The various storage media feature a
wide range of different properties: long
service life or very long buffer time, no
UPS-CAP…
< 5 min.
-40 ... +60°C
UPS-BAT/LI-ION…
> 40 min.
-20 ... +58°C
UPS-BAT/VRLA-WTR…
>5h
-25 ... +60°C
maintenance or use at extreme ambient
temperatures.
UPS-BAT/VRLA…
>8h
0 ... +40°C
Whatever your requirements, we offer the
ideal power storage.
UPS-BAT/VRLA...
(Valve Regulated Lead Acid)
• Maximum buffer times
• Lead AGM (Absorbed Glass Mat) technology
36
PHOENIX CONTACT
UPS-BAT/VRLA-WTR...
(Valve Regulated Lead Acid/
Wide Temperature Range)
• Maximum buffer times at
extreme temperatures
• Pure lead AGM (Absorbed
Glass Mat) technology
Your advantages
Fast installation
• Automatic detection of the power storage by
QUINT UPS
• Tool-free replacement during operation
Maximum availability
• Constant communication with QUINT UPS for
continuous monitoring and intelligent management
Service life
at 20°C
Service life
at 50°C
Charging
cycles
at 20°C
Weight
(standardized)
> 20 years
8 years
> 500,000
0.4 kg
15 years
2 years
7000
0.45 kg
12 years
1.5 years
300
1.3 kg
6 ... 9 years
1 year
250
1 kg
UPS-BAT/LI-ION...
• Long service life with long buffer
times
• Lithium-ion technology
+
~
Power supply
UPS module
Extremely long service life
• Optimum charging characteristic according to the
technology and ambient conditions
Immediate availability
• All power storage devices leave our warehouse
fully charged
UPS-CAP (Capacitor)
• Maximum service life
• Maintenance-free double-layer capacitors
–
Power storage
PHOENIX CONTACT
37
Selection guide for QUINT UPS
and CAP, LI-ION, VRLA-WTR
IQ
Buffer times for DC UPS modules
Select your UPS-BAT and UPS-CAP for 24 V DC applications here.
Example: 20 A needs to be buffered for 6 minutes
QUINT-DC-UPS/24DC/20A and UPS-BAT/LI-ION/24DC/120WH
Load current
1A
2A
3A
5A
7A
10 A
15 A
20 A
25 A
30 A
35 A
40 A
Buffer time
Seconds
0.2 0.4 1
2
8
16 30
Minutes
1 2 3
5
6
7
8
9
10 20 30 40 45 50
Hours
1 2
3
5
8
10 15 20 40
1+1
1+1 1+1
1+1 1+1
1+1 1+1
1+1
1+1
1+1
1+1
1+1
1+1 1+1
1+1 1+1 1+1 1+1
1+1 1+1 1+1
IQ
Buffer times for AC UPS module
Select your UPS-BAT and UPS-CAP for 120 V AC/230 V AC applications here.
Example: 125 W needs to be buffered for one hour
QUINT-UPS/1AC/1AC/500VA and UPS-BAT/VRLA-WTR/24DC/13AH
Buffer time
Seconds
0.2 0.4 2
Power
15
35
55
90
125
180
275
400
8
15
20
40
Minutes
1
2
3
5
6
7
8
9
W
W
W
W
W
W
W
W
1+1 … Two power storage devices of the same capacity are required in this case.
The data is based on an ambient temperature of 20°C.
38
PHOENIX CONTACT
10
20
30
40
45
50
Hours
1
2
3
5
8
10
15
20
1+1
1+1 1+1
1+1 1+1
1+1
1+1
1+1
1+1
1+1
DC UPS modules
Dual output
125
130
130
130
130
35
125
125
130
125
125
47
40
35
35
24 V / 5 A
24 V / 10 A
24 V / 20 A
24 V / 40 A
12 V / 5 A, 24 V / 10 A
QUINT-UPS/
24DC/24DC/5
2320212
QUINT-UPS/
24DC/24DC/10
2320225
QUINT-UPS/
24DC/24DC/20
2320238
QUINT-UPS/
24DC/24DC/40
2320241
QUINT-UPS/
24DC/12DC/5/24DC/10
2320461
Recommended:
UPS-CAP
UPS-BAT/VRLA-WTR
UPS-BAT/LI-ION
Recommended:
UPS-CAP
UPS-BAT/VRLA-WTR
UPS-BAT/LI-ION
Recommended:
UPS-CAP 20 A
UPS-BAT/VRLA-WTR
UPS-BAT/LI-ION
Recommended:
UPS-BAT/VRLA-WTR
Recommended:
UPS-CAP
UPS-BAT/VRLA-WTR
UPS-BAT/LI-ION
AC UPS module
130
125
125
400 W / 500 VA
QUINT-UPS/
1AC/1AC/500VA
2320270
Recommended:
UPS-CAP 20 A
UPS-BAT/VRLA-WTR
UPS-BAT/LI-ION
UPS-CAP
UPS-BAT/LI-ION
126
UPS-BAT/VRLA-WTR
110
176
178
126
174
177
202
130
130
169
358
150
135
172
10 A / 10 kJ
20 A / 20 kJ
120 WH
13 Ah
26 Ah
UPS-CAP/
24DC/10A/10KJ
2320377
UPS-CAP/
24DC/20A/20KJ
2320380
UPS-BAT/LI-ION/
24DC/120WH
2320351
UPS-BAT/VRLA-WTR/
24DC/13AH
2320416
UPS-BAT/VRLA-WTR/
24DC/26AH
2320429
PHOENIX CONTACT
39
Selection guide for QUINT UPS
and VRLA
IQ
Buffer times for DC UPS modules
Select your UPS-BAT for 24 V DC applications here.
Example: 20 A needs to be buffered for 10 minutes
QUINT-DC-UPS/24DC/20A and UPS-BAT/VRLA/24DC/7.2AH
Load current
1A
2A
3A
5A
7A
10 A
15 A
20 A
25 A
30 A
35 A
40 A
Buffer time
Seconds
0.2 0.4 2
8
Minutes
2
3
5
6
7
8
9
10
20
30
40
45
50
Hours
1
2
3
5
8
1+1
1+1 1+1
1+1 1+1
1+1
1+1 1+1
1+1 1+1 1+1
1+1 1+1 1+1 1+1
1+1 1+1 1+1 1+1
IQ
Buffer times for AC UPS module
Select your UPS-BAT for 120 V AC/230 V AC applications here.
Example: 125 W needs to be buffered for one hour
QUINT-UPS/1AC/1AC/500VA and UPS-BAT/VRLA/24DC/12AH
Power
15 W
35 W
55 W
90 W
125 W
180 W
275 W
400 W
Buffer time
Seconds
0.2 0.4 2
8
Minutes
2
3
5
6
7
8
9
10
20
30
1+1 … Two power storage devices of the same capacity are required in this case.
The data is based on an ambient temperature of 20°C.
40
PHOENIX CONTACT
40
45
50
Hours
1
2
3
5
8
1+1
1+1
1+1
1+1 1+1
1+1
DC UPS modules
Dual output
125
130
130
130
130
35
47
40
35
125
125
130
125
125
35
24 V / 5 A
24 V / 10 A
24 V / 20 A
24 V / 40 A
12 V / 5 A, 24 V / 10 A
QUINT-UPS/
24DC/24DC/5
2320212
QUINT-UPS/
24DC/24DC/10
2320225
QUINT-UPS/
24DC/24DC/20
2320238
QUINT-UPS/
24DC/24DC/40
2320241
QUINT-UPS/
24DC/12DC/5/24DC/10
2320461
Recommended:
UPS-CAP
UPS-BAT/VRLA-WTR
UPS-BAT/LI-ION
Recommended:
UPS-CAP
UPS-BAT/VRLA-WTR
UPS-BAT/LI-ION
Recommended:
UPS-CAP 20 A
UPS-BAT/VRLA-WTR
UPS-BAT/LI-ION
Recommended:
UPS-BAT/VRLA-WTR
Recommended:
UPS-CAP
UPS-BAT/VRLA-WTR
UPS-BAT/LI-ION
AC UPS module
130
125
125
400 W / 500 VA
QUINT-UPS/
1AC/1AC/500VA
2320270
Recommended:
UPS-CAP 20 A
UPS-BAT/VRLA-WTR
UPS-BAT/LI-ION
UPS-BAT/VRLA power storage devices
113
110
110
110
202
202
221
191
157
197
54
85
135
202
330
1.3 Ah
3.4 Ah
7.2 Ah
12 Ah
38 Ah
UPS-BAT/
VRLA/24DC/1.3AH
2320296
UPS-BAT/
VRLA/24DC/3.4AH
2320306
UPS-BAT/
VRLA/24DC/7.2AH
2320319
UPS-BAT/
VRLA/24DC/12AH
2320322
UPS-BAT/
VRLA/24DC/38AH
2320335
PHOENIX CONTACT
41
QUINT UPS
Signaling and configuration
Monitor and configure your UPS system
using the UPS-CONF configuration and
management software.
For quick startup, important information
is provided in the poster-sized brief
instructions. Pictures and screenshots aid
hardware and software installation and
help explain the method of operation of
UPS-CONF.
The quick start guide is available free of
charge on the Phoenix Contact website
under “Downloads” for the QUINT UPS
products.
Signaling via contacts
USB interface is ideal for:
LEDs and floating relay contacts provide
function monitoring. QUINT UPS-IQ supplies
the following information via the wired
contacts:
• Monitoring and configuration with
UPS-CONF
• The load is being supplied by the power
storage
• The power storage is being charged
• An alarm is present
42
PHOENIX CONTACT
• Safe shutdown of industrial PCs with
optimum utilization of the power storage
Configurable
• Flexible adaptation of QUINT UPS
behavior to individual requirements
Preventative
function monitoring
• All relevant operating parameters
are displayed graphically
• Important messages appear in the
foreground
Integrated data recorder
• Log file archives events, e.g., when
and for how long QUINT UPS has
bridged mains failures
Accessories
19
6
6
39
16
16
Software
USB data cable
Memory module
Memory module
UPS-CONF
2320403
IFS-USB-DATACABLE
2320500
IFS-CONFSTICK
2986122
IFS-CONFSTICK-L
2901103
• Available free of charge on
the Phoenix Contact website
under “Downloads” for the
QUINT-UPS/... products
• For communication between
UPS module and UPS-CONF
• Length: 3 m
• For saving and transferring
configured values to other
QUINT UPS
• For saving and transferring
configured values to other
QUINT UPS
PHOENIX CONTACT
43
QUINT UPS
Communication
Use the available data cables to integrate
the UPS module into your application.
You can therefore benefit from all the
advantages of IQ technology and be kept
informed of the state of your UPS solution.
The information provided by QUINT UPS
can, for example, be forwarded to
higher-level controllers via Ethernet or be
implemented directly in control solutions
from Phoenix Contact.
The IFS-MINI-DIN DATACABLE is suitable for direct
communication with the 100 series higher-level ILC
(Inline controller).
44
PHOENIX CONTACT
Accessories
RS-232 data cable
Open end data cable
MINI DIN data cable
IFS-RS232-DATACABLE
2320490
IFS-OPEN-END-DATACABLE
2320450
IFS-MINI-DIN-DATACABLE
2320487
• Modbus communication with
RS-232 interface
• Open cable for flexible
communication
• COM server from Phoenix Contact for Ethernet
communication
• Length: 2 m
• Address higher-level controllers such as Inline
controllers (ILCs) or Remote Field Controllers
(RFCs) directly
• Direct communication with the
Inline controller (ILC) from the
Phoenix Contact Inline system
(100 series)
• Length: 2 m
• Use the Inline controller from Phoenix Contact as a
gateway and access other communication protocols
• Length: 2 m
Do you use PC Worx software?
Then use the library with function blocks for the further processing of information communicated via
data cables. It is available free of charge on the Phoenix Contact website under “Downloads” for the
QUINT-UPS/... products.
PHOENIX CONTACT
45
UPS modules with
integrated power storage
Particularly space saving and easy to
retrofit, the UPS module and power
storage are combined in the same housing.
It's just a case of connecting a power
supply upstream and the reliable UPS
solution is complete.
UNO UPS
STEP UPS
Input: 1-phase,
23 ... 30 V DC
Input: 1-phase,
24 V: 22.5 ... 29.5 V DC,
12 V: 10 ... 16.5 V DC
61
90
90
90
110
108
24 V / 60 W
~
UNO-UPS/24DC/24DC/60
2905907
–
+
• Power storage with lead AGM
technology
Power supply UPS module Power storage
QUINT UPS
IQ
12 DC / 12 DC / 4 A
2x
STEP-UPS/12DC/12DC/4
2868693
• LiPo-based power storage
Input: 1-phase, 18 ... 30 V DC
125
125
130
169
138
125
88
120
64
24 DC / 5 A / 1.3 Ah
24 DC / 10 A / 3.4 Ah
24 V / 40 A
QUINT-UPS/24DC/24DC/5/1.3AH
2320254
QUINT-UPS/24DC/24DC/10/3.4AH
2320267
QUINT-BUFFER/24DC/24DC/40
2320393
• Power storage with lead AGM technology
• Integrated temperature sensor optimizes load currents
and increases the service life
• Function monitoring via LED and floating relay contact
PHOENIX CONTACT
STEP-UPS/24DC/24DC/3
2868703
QUINT BUFFER
Input: 1-phase, 18 ... 30 V DC
46
24 DC / 24 DC / 3 A
• Capacitor-based
power storage
• Maintenance-free
Buffer times for UNO UPS and STEP UPS
Select your UNO UPS here.
Select your STEP UPS here.
With the 12 V version, buffer times are
double those of the 24 V version.
Buffer time
Load
Seconds
current
0.2 0.4 1 2
0.5 A
1A
1.5 A
2A
2.5 A
Buffer time
Load
Seconds
current
0.2 0.4 1 2
0.5 A
1A
2A
3A
Minutes
8 16 30 1 2 3
5
6
7
8
9 10 20 30 40 45
Minutes
8 16 30 1 2 3
5
6
7
8
Hours
9 10 15 20 25 30 40 45 50 1 2 3
5
6
7
8
Hours
9 10 15 20 25 30 40 45 50 1 2 3
Buffer times for QUINT UPS and QUINT BUFFER
Select your UPS solution here.
Example: 5 A needs to be buffered for
20 minutes
QUINT-UPS/24DC/24DC/10A/3.4AH
Buffer time
Load
Seconds
current
0.2 0.4 1 2
0.5 A
1A
2A
3A
5A
7A
10 A
15 A
20 A
25 A
30 A
35 A
40 A
Minutes
8 16 30 1 2 3
PHOENIX CONTACT
47
UPS modules with
integrated power supply
The UPS module and power supply
are combined in the same housing in a
particularly space-saving way. Only one
power storage is required to complete the
UPS system.
~
–
+
Power supply UPS module Power storage
MINI UPS
Power storage devices with lead AGM
technology enable buffer times of up to
40 minutes under nominal load for output
voltages of 24 or 12 V DC.
MINI UPS + ...
Input: 1-phase,
85 ... 264 V AC, 100 ... 350 V DC
MINI-DC-UPS/24DC/2
2866640
107
99
Output: 24 V DC / 2 A
TRIO UPS
Power storage devices with lead AGM
technology buffer failures lasting up to
2 hours with 5 A load current.
MINI-DC-UPS/12DC/4
2866598
67.5
Output: 12 V DC / 4 A
TRIO UPS + ...
Input: 1-phase,
85 ... 264 V AC, 100 ... 350 V DC
TRIO-UPS/1AC/24DC/5
2866611
Accessories
130
UPS-CONF
2320403
Configuration software available for free
on the Phoenix Contact website under
“Downloads” for the TRIO UPS product
118
IFS-USB-DATACABLE
2320500
Data cable for communication between
UPS-CONF and TRIO UPS
60
Memory modules
2986122 / 2901103
Memory module for saving and transferring
configured values to other TRIO UPS
48
PHOENIX CONTACT
Buffer times for MINI UPS and TRIO UPS
Select your MINI-BAT for MINI UPS and QUINT-BAT for TRIO UPS here.
Example: 2 A needs to be buffered for 20 minutes
MINI-DC-UPS/24DC/2 and MINI-BAT/24DC/1.3AH
Minutes
2
3
Load current
5
6
7
8
9
10
20
30
40
45
50
Hours
1
2
3
0.5 A
1A
1.5 A
2A
3A
4A
5A
... MINI-BAT for MINI UPS
2x
110
107
2x
110
67.5
130
130
99
99
107
67.5
52
52
24 V DC / 0.8 Ah
24 V DC / 1.3 Ah
12 V DC / 1.6 Ah
12 V DC / 2.6 Ah
MINI-BAT/24DC/0.8AH
2866666
MINI-BAT/24DC/1.3AH
2866417
MINI-BAT/12DC/1.6AH
2866572
MINI-BAT/12DC/2.6AH
2866569
... QUINT-BAT for TRIO UPS
52
156
110
112
156
110
112
145
130
110
164
231
24 V / 1.3 Ah
24 V / 3.4 Ah
24 V / 7.2 Ah
12 Ah
MINI-BAT/24DC/1.3AH
2866417
QUINT-BAT/24DC/3.4AH
2866349
QUINT-BAT/24DC/7.2AH
2866352
QUINT-BAT/24DC/12AH
2866365
PHOENIX CONTACT
49
Accessories for power supplies
Mounting on S7-300 rail
Mounting on level surfaces
130
130
130
9
17
11
11
182
104
74
52
25
QUINT-PS adapter S7/1
QUINT-PS adapter S7/2
Adapter UWA 182/52
Adapter UWA 130
2938196
2938206
2938235
2901664
For: QUINT-PS/1AC/24DC/3.5,
QUINT-PS/1AC/24DC/5,
QUINT-PS/3AC/24DC/5
For: QUINT-PS/1AC/24DC/10,
QUINT-PS/3AC/24DC/10,
QUINT-PS/3AC/24DC/20
For TRIO-PS from 10 A, QUINT-PS,
QUINT-DC-UPS,
QUINT-BUFFER
For QUINT-PS/1AC/24DC/40,
QUINT-UPS/1AC/1AC/500VA
Accessories for uninterruptible power supplies
Power storage mounting
Fuses for power storage
BATTERY
MOUNTING KIT
BATTERY
MOUNTING CASE
2320788
2320458
For: UPS-BAT/VRLA/24DC/38AH,
UPS-BAT/VRLA-WTR/24DC/13AH,
UPS-BAT/VRLA-WTR/24DC/26AH
For: UPS-BAT/VRLA/24DC/38AH,
UPS-BAT/VRLA-WTR/24DC/13AH,
UPS-BAT/VRLA-WTR/24DC/26AH
SI FORM C 15 A DIN 72581
0913676
SI FORM C 25 A DIN 72581
0913757
• Flat-type plug-in fuse
• 15 A and 25 A nominal current
Ethernet communication
99
116
71.5
80
22.5
FL COMSERVER UNI 232/422/485
ILC 130 ETH
2313452
2988803
• Integration of serial RS-232, RS-422,
and RS-485 interfaces
• For machine and system access via Ethernet network
50
119.8
PHOENIX CONTACT
Inline compact controller with Ethernet interface for coupling to
other controllers and systems
Approvals
DeviceNet™
SEMI F47-0706 Compliance
Certificate PQ Star
CB Scheme
Medical standard IEC 60601
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
d
QUINT-PS/1AC/24DC/10
2866763
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
c
QUINT-PS/1AC/24DC/20
2866776
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
d
QUINT-PS/1AC/24DC/40
2866789
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
b
QUINT-PS/1AC/12DC/15
2866718
•
•
•
•
•
•
•
•
•
•
•
•
c
QUINT-PS/1AC/12DC/20
2866721
•
•
•
•
•
•
•
•
•
•
•
•
d
QUINT-PS/1AC/48DC/5
2866679
•
•
•
•
•
•
•
•
•
•
•
•
c
QUINT-PS/1AC/48DC/10
2866682
•
•
•
•
•
•
•
•
•
•
•
d
QUINT-PS/1AC/48DC/20
2866695
•
•
•
•
•
•
•
QUINT-PS/3AC/24DC/5
2866734
•
•
•
•
•
•
•
•
•
•
•
QUINT-PS/3AC/24DC/10
2866705
•
•
•
•
•
•
•
•
•
•
•
QUINT-PS/3AC/24DC/20
2866792
•
•
•
•
•
•
•
•
•
•
•
QUINT-PS/3AC/24DC/40
2866802
•
•
•
•
•
•
•
•
•
•
•
QUINT-PS/3AC/48DC/20
2320827
•
•
•
•
•
•
QUINT-PS/1AC/24DC/5/CO
2320908
•
•
•
•
•
•
•
QUINT-PS/1AC/24DC/10/CO
2320911
•
•
•
•
•
•
•
QUINT-PS/1AC/24DC/20/CO
2320898
•
•
•
•
•
•
•
QUINT-PS/3AC/24DC/20/CO
2320924
•
•
•
•
•
•
•
Installation height
NK - Nippon Kaiji Kyokai
•
•
Startup at -40°C
LR - Lloyd's Register
•
•
EAC
BV - Bureau Veritas
•
•
IEC Ex
ABS - American Bureau of Shipping
•
•
ATEX
GL - Germanischer Lloyd
•
•
RINA
CSA 22.2 No 60950-1-07
•
2866750
DNV - Det Norske Veritas
CSA 22.2 No 107.1-01
2866747
QUINT-PS/1AC/24DC/5
UL 1310 NEC Class 2
QUINT-PS/1AC/24DC/3.5
Order No.
UL/C-UL Listed UL 508
UL Listed ANSI/ISA-12.12.01 Class I,
Division 2, Groups A, B, C, D
Railway standard EN 50155, 50121-4
EX
UL/C-UL Recognized UL 60950
Ship
UL Listed UL 508
CSA
CE
UL
QUINT POWER power supplies
•
•
•
•
c
•
•
•
d
•
•
•
•
•
c
•
•
•
•
•
•
b
•
•
•
•
•
•
c
•
•
•
•
•
•
b
•
•
•
b
•
•
•
•
•
•
•
•
•
•
•
d
•
•
•
•
•
•
•
•
•
c
•
•
•
•
•
•
•
•
•
d
•
•
•
•
•
c
TRIO POWER power supplies
TRIO-PS-2G/1AC/24DC/3C2LPS
2902147
•
•
•
TRIO-PS-2G/1AC/24DC/5
2903148
•
•
•
•
•
•
TRIO-PS-2G/1AC/24DC/10
2903149
•
•
•
•
•
TRIO-PS-2G/1AC/24DC/20
2903151
•
•
•
•
•
TRIO-PS/1AC/12DC/5
2866475
•
•
•
•
d
TRIO-PS/1AC/12DC/10
2866488
•
•
•
•
d
TRIO-PS/1AC/48DC/5
2866491
•
•
•
•
a
TRIO-PS/1AC/48DC/10
2866501
•
•
•
•
b
TRIO-PS-2G/3AC/24DC/5
2903148
•
•
•
•
TRIO-PS-2G/3AC/24DC/10
2903148
•
•
•
•
•
TRIO-PS-2G/3AC/24DC/20
2903148
•
•
•
•
•
TRIO-PS/3AC/24DC/40
2866404
•
•
•
•
PHOENIX CONTACT
d
b
51
MINI-PS-100-240AC/24DC/4
2938837
•
•
•
MINI-PS-100-240AC/5DC/3
2938714
•
•
•
MINI-PS-100-240AC/10-15DC/2
2938756
•
•
MINI-PS-100-240AC/10-15DC/8
2866297
•
MINI-PS-100-240AC/2x15DC/1
2938743
•
Installation height
•
Startup at -40°C
•
•
EAC
•
•
Railway standard EN 50155, 50121-4
•
•
Medical standard IEC 60601
•
2866336
CB Scheme
2938730
MINI-PS-100-240AC/24DC/C2LPS
SEMI F47-0706 Compliance
Certificate PQ Star
MINI-PS-100-240AC/24DC/2
DeviceNet™
•
•
IEC Ex
•
•
ATEX
•
•
RINA
•
2866653
DNV - Det Norske Veritas
2866983
MINI-SYS-PS-100-240AC/24DC/1.5/EX
NK - Nippon Kaiji Kyokai
MINI-SYS-PS-100-240AC/24DC/1.5
LR - Lloyd's Register
•
BV - Bureau Veritas
•
EX
ABS - American Bureau of Shipping
•
GL - Germanischer Lloyd
•
Ship
CSA 22.2 No 60950-1-07
UL 1310 NEC Class 2
•
CSA 22.2 No 107.1-01
UL Listed ANSI/ISA-12.12.01 Class I,
Division 2, Groups A, B, C, D
2866446
UL Listed UL 508
MINI-PS-100-240AC/24DC/1.3
Order No.
CE
UL/C-UL Recognized UL 60950
CSA
UL/C-UL Listed UL 508
UL
MINI POWER power supplies
•
d
•
a
•
a
•
•
b
•
•
a
•
•
a
•
•
b
•
•
•
d
•
•
•
•
a
•
•
•
•
b
a
•
•
UNO POWER power supplies
UNO-PS/1AC/24DC/30W
2902991
•
•
•
•
•
•
UNO-PS/1AC/24DC/60W
2902992
•
•
•
•
•
•
UNO-PS/1AC/24DC/90W/C2LPS
2902994
•
•
•
UNO-PS/1AC/24DC/100W
2902993
•
•
•
•
•
•
a
•
•
a
UNO-PS/1AC/24DC/150W
2904376
•
•
UNO-PS/1AC/24DC/240W
2904372
•
•
•
•
•
c
•
•
•
a
UNO-PS/1AC/5DC/25W
2904374
•
•
•
•
•
b
UNO-PS/1AC/5DC/40W
2904375
•
•
•
•
•
•
a
•
•
a
•
•
•
d
•
•
c
•
•
a
•
•
d
•
•
d
•
•
d
•
•
c
•
•
b
•
•
UNO-PS/1AC/12DC/30W
2902998
•
•
•
UNO-PS/1AC/12DC/55W
2902999
•
•
•
UNO-PS/1AC/12DC/100W
2902997
•
•
•
UNO-PS/1AC/15DC/30W
2903000
•
•
•
UNO-PS/1AC/15DC/55W
2903001
•
•
•
UNO-PS/1AC/15DC/100W
2903002
•
•
•
UNO-PS/1AC/48DC/60W
2902995
•
•
•
UNO-PS/1AC/48DC/100W
2902996
•
•
•
UNO-PS/2AC/24DC/90W/C2LPS
2904371
•
•
•
a) Max. 3000 m
b) Max. 4000 m
c) Max. 5000 m
d) Max. 6000 m
e) Max. 2000 m
All products receive further approvals on a continual basis.
For up-to-date information, please refer to the
Phoenix Contact website under “Downloads” for the
relevant products.
52
PHOENIX CONTACT
•
•
•
•
•
•
d
•
•
•
•
•
•
•
•
•
STEP-PS/1AC/24DC/2.5
2868651
•
•
•
•
•
•
•
STEP-PS/1AC/24DC/3.8/C2LPS
2868677
•
•
•
•
•
•
STEP-PS/1AC/24DC/4.2
2868664
•
•
•
•
STEP-PS/277AC/24DC/3.5
2904945
•
•
•
•
STEP-PS/1AC/5DC/2
2320513
•
•
•
•
STEP-PS/1AC/5DC/6.5
2868541
•
•
•
•
•
•
STEP-PS/1AC/15DC/4
2868619
•
•
•
•
•
•
STEP-PS/1AC/48DC/2
2868680
•
•
•
•
•
•
STEP-PS/1AC/12DC/1
2868538
•
•
•
•
•
STEP-PS/1AC/12DC/1.5FL
2868554
•
•
•
•
•
•
•
•
STEP-PS/1AC/12DC/1.5
2868567
•
•
•
•
•
•
•
•
•
STEP-PS/1AC/12DC/3
2868570
•
•
•
•
•
•
•
•
STEP-PS/1AC/12DC/5
2868583
•
•
•
•
•
•
•
Installation height
•
•
Startup at -40°C
•
•
EAC
•
2868648
CB Scheme
2868635
STEP-PS/1AC/24DC/1.75
SEMI F47-0706 Compliance
Certificate PQ Star
STEP-PS/1AC/24DC/0.75
DeviceNet™
•
IEC Ex
•
ATEX
•
•
RINA
•
•
DNV - Det Norske Veritas
•
•
NK - Nippon Kaiji Kyokai
•
•
LR - Lloyd's Register
•
2868622
BV - Bureau Veritas
2868596
STEP-PS/1AC/24DC/0.75FL
GL - Germanischer Lloyd
STEP-PS/1AC/24DC/0.5
CSA 22.2 No 60950-1-07
•
CSA 22.2 No 107.1-01
UL/C-UL Recognized UL 60950
•
UL 1310 NEC Class 2
UL/C-UL Listed UL 508
•
UL Listed UL 508
2868716
CE
STEP-PS/48AC/24DC/0.5
Order No.
Railway standard EN 50155, 50121-4
EX
Medical standard IEC 60601
Ship
ABS - American Bureau of Shipping
CSA
UL Listed ANSI/ISA-12.12.01 Class I,
Division 2, Groups A, B, C, D
UL
•
•
b
STEP POWER power supplies
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
c
•
•
•
c
•
a
•
•
d
•
•
•
d
•
•
•
•
•
•
d
•
•
•
•
c
•
•
•
•
d
•
•
•
b
•
•
•
c
•
•
•
c
•
•
•
c
•
•
•
d
•
•
•
•
•
•
•
•
•
•
•
•
•
QUINT-DIODE/24DC/2x20A
2320157
•
•
•
•
•
QUINT-DIODE/48DC/2x20A
2320160
•
•
•
•
TRIO-DIODE/12-24DC/2x10/1x20
2866514
•
•
•
TRIO-DIODE/48DC/2x10/1x20
2866527
•
•
STEP-DIODE/5-24DC/2x5/1x10
2868606
•
•
UNO-DIODE/5-24DC/2x10/1x20
2905489
•
•
•
•
•
Startup at -40°C
•
•
•
EAC
•
2902879
•
Type tested
2320186
QUINT-ORING/24DC/2x40/1x80
•
Medical standard IEC 60601
QUINT-ORING/24DC/2x20/1x40
•
CB Scheme
NK - Nippon Kaiji Kyokai
•
SEMI F47-0706 Compliance
Certificate PQ Star
LR - Lloyd's Register
•
DeviceNet™
BV - Bureau Veritas
•
IEC Ex
ABS - American Bureau of Shipping
•
ATEX
GL - Germanischer Lloyd
•
RINA
UL Listed ANSI/ISA-12.12.01 Class I,
Division 2, Groups A, B, C, D
•
DNV - Det Norske Veritas
UL/CUL Recognized UL 60950
•
CSA 22.2 No 60950-1-07
b
EX
UL/CUL Listed UL 508
Ship
•
CSA 22.2 No 107.1-01
c
•
CSA
UL 1310 NEC Class 2
•
•
•
UL Listed UL 508
b
•
•
2320173
CE
•
•
•
•
QUINT-ORING/24DC/2x10/1x20
Order No.
•
•
•
•
UL
•
•
•
•
•
Redundancy modules
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
PHOENIX CONTACT
53
Order
No.
54
PHOENIX CONTACT
QUINT-PS/2AC/1DC/24DC/20
2320830
•
•
•
TRIO-PS/600DC/24DC/20
2866530
•
•
•
Power supplies for frequency inverters
•
•
•
•
•
•
•
•
•
d
•
•
•
•
•
•
•
•
•
d
QUINT-PS/24DC/24DC/20/CO
•
•
•
•
•
•
•
•
•
•
•
•
•
d
•
d
•
d
•
QUINT-PS/96-110DC/24DC/10/CO 2905012
•
•
•
2866284
•
•
•
•
•
•
•
d
MINI-PS-12-24DC/5-15DC/2
2320018
•
•
•
•
•
•
•
d
MINI-PS-12-24DC/48DC/0.7
2320021
•
•
•
•
•
•
•
d
MINI-PS-48-60DC/24DC/1
2866271
•
•
•
•
•
•
d
MINI-PS/10-42AC/15-60DC/3
2320199
•
•
•
•
Installation height
UL Listed ANSI/ISA-12.12.01 Class I,
Division 2, Groups A, B, C, D
GL - Germanischer Lloyd
ABS - American Bureau of Shipping
BV - Bureau Veritas
LR - Lloyd's Register
NK - Nippon Kaiji Kyokai
DNV - Det Norske Veritas
RINA
EN 50121
Startup at -40°C
Installation height
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
d
2320092
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
d
•
•
•
•
•
•
•
d
•
•
•
•
•
•
•
•
d
•
QUINT-PS/24DC/24DC/20
2320102
•
•
•
•
•
QUINT-PS/24DC/12DC/8
2320115
•
•
•
•
•
•
•
QUINT-PS/24DC/48DC/5
2320128
•
•
•
•
•
•
•
•
•
•
•
•
•
•
d
QUINT-PS/12DC/24DC/5
2320131
•
•
•
•
•
•
•
•
•
•
•
•
d
QUINT-PS/12DC/12DC/8
2905007
•
•
•
•
d
QUINT-PS/48DC/24DC/5
2320144
•
•
•
•
•
•
•
•
•
•
•
•
d
QUINT-PS/48DC/48DC/5
2905008
•
•
•
•
•
d
QUINT-PS/60-72DC/24DC/10
2905009
•
•
•
•
•
d
QUINT-PS/96-110DC/24DC/10
2905010
•
•
•
•
•
d
•
Startup at -40°C
EN 50121
EN 50155
•
•
MINI-PS-12-24DC/24DC/1
•
EAC
Railway standard EN 50155
Medical standard IEC 60601
CB Scheme
SEMI F47-0706 Compliance Certificate
PQ Star
Ship
DeviceNet™
UL/CUL Recognized UL 60950
2320034
QUINT-PS/24DC/24DC/10
EN 50155
EAC
Railway standard EN 50155
Medical standard IEC 60601
CB Scheme
SEMI F47-0706 Compliance Certificate
PQ Star
DeviceNet™
IEC Ex
ATEX
CSA 22.2 No 60950-1-07
CSA 22.2 No 107.1-01
UL 1310 NEC Class 2
UL Listed UL 508
Ship
ATEX
CSA
RINA
UL
DNV - Det Norske Veritas
•
•
•
NK - Nippon Kaiji Kyokai
•
•
•
LR - Lloyd's Register
•
•
•
BV - Bureau Veritas
•
•
•
ABS - American Bureau of Shipping
UL/CUL Listed UL 508
DC/DC converters
QUINT-PS/24DC/24DC/5
CE
CSA
GL - Germanischer Lloyd
•
•
•
CSA 22.2 No 60950-1-07
•
•
•
CSA 22.2 No 107.1-01
2320542
2320555
2320568
UL 1310 NEC Class 2
QUINT-PS/24DC/24DC/5/CO
QUINT-PS/24DC/24DC/10/CO
QUINT-PS/60-72DC/24DC/10/CO 2905011
UL Listed ANSI/ISA-12.12.01 Class I,
Division 2, Groups A, B, C, D
UL/CUL Recognized UL 60950
UL/CUL Listed UL 508
UL Listed UL 508
Order
No.
CE
UL
EX
•
EX
EX
d
•
d
QUINT-UPS/24DC/12DC/5/24DC/10
2320461
•
•
•
QUINT-UPS/24DC/24DC/5/1.3AH
2320254
•
•
•
•
•
d
QUINT-UPS/24DC/24DC/10/3.4AH
2320267
•
•
•
•
•
d
QUINT-UPS/1AC/1AC/500VA
2320270
•
•
e
QUINT-BUFFER/24DC/40
2320393
•
•
•
•
•
e
UPS-BAT/VRLA/24DC/1.3AH
2320296
•
•
•
•
•
d
UPS-BAT/VRLA/24DC/3.4AH
2320306
•
•
•
•
•
d
UPS-BAT/VRLA/24DC/7.2AH
2320319
•
•
•
•
•
d
UPS-BAT/VRLA/24DC/12AH
2320322
•
•
•
•
•
d
UPS-BAT/VRLA/24DC/38AH
2320335
•
•
•
•
•
•
UPS-BAT/VRLA-WTR/24DC/13AH
2320416
•
•
•
•
•
•
•
d
UPS-BAT/VRLA-WTR/24DC/26AH
2320429
•
•
•
•
•
•
•
d
UPS-BAT/LI-ION/24DC/120WH
2320351
•
•
•
•
•
UPS-CAP/24DC/10A/10KJ
2320377
•
•
•
•
•
•
d
UPS-CAP/24DC/20A/20KJ
2320380
•
•
•
•
•
•
d
STEP-UPS/24DC/24DC/3
2868703
•
•
•
•
•
e
STEP-UPS/12DC/12DC/4
2868693
•
•
•
•
•
e
STEP-BAT/LIPO/18,5DC/1.4AH
2320364
•
•
•
•
e
TRIO-UPS/1AC/24DC/5
2866611
•
MINI-DC-UPS/24DC/2
2866640
•
MINI-BAT/24DC/0.8AH
2866666
MINI-BAT/24DC/1.3AH
2866417
MINI-DC-UPS/12DC/4
2866598
•
MINI-BAT/12DC/1.6AH
2866572
•
MINI-BAT/12DC/2.6AH
2866569
•
a) Max. 3000 m
b) Max. 4000 m
c) Max. 5000 m
d) Max. 6000 m
e) Max. 2000 m
All products receive further approvals on a continual basis.
For up-to-date information, please refer to the
Phoenix Contact website under “Downloads” for the
relevant products.
Installation height
•
•
Startup at -40°C
•
•
EAC
•
•
Medical standard IEC 60601
•
•
CB Scheme
•
•
DeviceNet™
•
2320241
ATEX
2320238
QUINT-UPS/24DC/24DC/40
RINA
QUINT-UPS/24DC/24DC/20
DNV - Det Norske Veritas
d
NK - Nippon Kaiji Kyokai
d
•
LR - Lloyd's Register
•
•
BV - Bureau Veritas
•
•
GL - Germanischer Lloyd
•
•
CSA 22.2 No 60950-1-07
•
•
CSA 22.2 No 107.1-01
•
•
UL 1310 NEC Class 2
•
2320225
UL 1778
UL/CUL Recognized UL 60950
2320212
QUINT-UPS/24DC/24DC/10
UL Listed UL 508
QUINT-UPS/24DC/24DC/5
Order No.
CE
UL/CUL Listed UL 508
SEMI F47-0706 Compliance Certificate
PQ Star
Ship
ABS - American Bureau of Shipping
CSA
UL Listed ANSI/ISA-12.12.01 Class I,
Division 2, Groups A, B, C, D
UL
Uninterruptible power supplies
•
•
e
•
d
•
d
•
c
•
•
•
d
•
•
•
d
•
•
d
•
•
d
•
•
d
•
•
•
•
d
•
•
•
•
PHOENIX CONTACT
55
Always up-to-date, always available to you. Here
you‘ll find everything on our products, solutions
and service:
phoenixcontact.com
Product range
• Industrial communication technology
• Industrial Ethernet
• Installation and mounting material
• Lighting and signaling
• Marking and labeling
• Measurement and control technology
• Modular terminal blocks
• Monitoring
• PCB terminal blocks and
PCB connectors
• Power supply units and UPS
• Protective devices
• Relay modules
• Sensor/actuator cabling
• Software
• Surge protection and interference filters
• System cabling for controllers
• Tools
• Wireless data communication
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstraße 8
32825 Blomberg, Germany
Phone: + 49 5235 3-00
Fax: + 49 5235 3-41200
E-mail: [email protected]
phoenixcontact.com
PS 02-14.000.L3
MNR 52004103/2015-04-01/08
Printed in Germany
© PHOENIX CONTACT 2015
• Cables and wires
• Connectors
• Controllers
• Electronics housings
• Electronic switchgear and
motor control
• Fieldbus components and systems
• Functional safety
• HMIs and industrial PCs
• I/O systems