Vigilant H2 Series High Bay 480V Installation Manual

Vigilant® H2 LED High Bay Fixture
Important information:
These instructions contain safety information, read and follow them carefully. Dialight will not accept any
responsibility for injury, damage or loss which may occur due to incorrect installation, operation or maintenance
Operating Instructions
9100127247299_A
High Bay Series LED Fixture for hazardous
® H2 LED High Bay Fixture
Vigilant
areas

NOTE: Save these instructions for
future use.
WARNING:
To avoid the risk of fire, explosion, or
electric shock, this product should be
installed, inspected, and maintained
by a qualified electrician only, in
accordance with all applicable
electrical codes.
To avoid electric shock:

Be certain electrical power is OFF
before and during installation and
maintenance.

Luminaire must be connected to
a wiring system with an
equipment-grounding conductor.


Make sure the supply voltage is
the same as the rated luminaire
voltage.
Do not operate in ambient
temperatures above those
indicated on the luminaire
nameplate.
Introduction
This High Bay light is designed for illumination of
industrial location and uses the latest in solid
state lighting technology for long life, low
maintenance, and high efficiency.
The unique optical design focuses light downward
to where it is needed, giving improved efficiency
over a conventional HID luminaire.
An internal power-factor-corrected switch-mode
supply allows it to be used from any nominal 347V480V, 50/60Hz AC supply without any variation in
light output.
Models H2xxx5xxxxx are suitable for use in dry
locations only per UL 1598.
Recommended mounting height: 25-40 feet
Installation
For maximum reliability and light output the light
must be installed in free air. The High Bay fixture
design incorporates an over-temperature control
circuit that reduces input power should internal
temperatures reach a maximum level. As a result,
light output may be reduced.
Pendent Mount Installation Steps
The High Bay fixture is threaded for ¾”NPT in order
to be assembled to conduit.




Technical Data
Rated Input Voltage:
Hxxxx5xxxxx:
347-480VAC 50/60Hz
Operating
Temperature
-40°C to +65°C
Rated Input Power:
H2xxxxNxxxx:
192W nominal
Power Factor:
>.9
ATHD:
<20%
Storage Temp.
-40°C to +65°C
Dimensions:
16” Diameter
10.5-13.5” Height
depending on lens
configuration
Weight:
33 lbs [15 kg]
Calculate and measure required conduit
length.
Feed the power cable through the conduit
and into the junction box.
Attach the fixture to the conduit using Teflon
tape or pipe sealant.
Insert ¼-20 anti-rotation screw in order to
secure the fixture to the conduit.
Restore power and verify operation.
For dimming models only (HxxxxxxDxxx)
Dimming is controlled by means of a 0-10 VDC
signal (to be provided by the installer) to control
the level of dimming. At 10 volts, the output of the
unit is 100%; at 0 volts, the output will be
approximately 15%. The DC dimming voltage
should not exceed 15 VDC. Increasing the voltage
from 10VDC to 15VDC will not result in additional
light output.
Violet wire connects to +, Grey wire connects to -.
Important Notes
- The low voltage Dimming wires are connected to
the grounded output section of the driver inside
the light. Never connect either one to the Hot or
Neutral supply wires.
- Never use these wires for any purpose other than
dimming.
1) Variable Voltage Control
An analog 0-10V active dimmer may be
connected to the two wires to control the light
output of the fixture. Multiple lights may be
connected to the same dimmer, as long as the
maximum current rating of the dimmer is not
exceeded.
The dimmer must be capable of sinking 0.5mA per
light. Light output will vary approximately linearly
with control voltage, with 10V corresponding to
100% light output.
2) Step dimming
Simply shorting the two wires together will cause
the light to dim to a low level. When this is done,
the light will dim down to approximately 15% of its
full light output, with a corresponding decrease in
input power.
Connect the power cable conductors as follows:
For single phase (non 3-phase systems)

Green wire to Safety Ground.

Red wire to Live

Black wire to Neutral
For two phase (3-phase systems)

Green wire to Safety Ground.

Red wire to phase 1

Black wire to phase 2
Remove protective film, if present, from the High
Bay fixture lens.
9100127247299_A
High Bay Series LED Fixture for hazardous
areas
Maintenance
To avoid personal injury, disconnect power to the
light and allow the unit to cool down before
performing maintenance.
WARNING: No user serviceable parts inside of
fixture. Risk of electric shock. Removal of the lens
will void the warranty.
Perform visual, mechanical, and electrical
inspections on a regular basis. Dialight
recommends checks to be made on a yearly
basis. Frequency of use and environmental
conditions, however should determine the
frequency of checks. It is recommended to follow
an Electrical Preventive Maintenance Program as
described in NFPA 70B: Recommended Practice
for Electrical Equipment.
The lens should be cleaned periodically, as
needed, to ensure continued photometric
performance. Clean the lens with a damp, nonabrasive, and lint-free cloth. If not sufficient, use
mild soap or a liquid cleaner. Do not use and
abrasive, strong alkaline, or acid cleaners as
damage may occur.
Inspect the cooling fins on the luminaire to ensure
that they are free of any obstructions or
contamination (i.e. excessive dust build-up). Clean
with a non-abrasive cloth, if needed.
All statements, technical information, and
recommendations contained herein are based on
information and tests that Dialight believes to be
reliable. The accuracy or completeness thereof is
not guaranteed. In accordance with Dialight
“Terms and Conditions of Sale” and since
conditions of use are outside our control, the
purchaser should determine the suitability of the
product for his or her intended use and assumes all
risk and liability whatsoever in connection
therewith.