Vigilant® LED High Bay Fixture with DALI controls

Vigilant® LED High Bay Fixture with DALI controls
Important information:
These instructions contain safety information, read and follow them carefully. Dialight will not accept any
responsibility for injury, damage or loss which may occur due to incorrect installation, operation or maintenance
Operating Instructions
Languages
English
Page Number
1
Dimensions in mm [inches]
9100127226599_B
High Bay Series LED Fixture for hazardous
® LED High Bay Fixture with DALI controls
Vigilant
areas

NOTE: Save these instructions for
future use.
Safety Instruction:

The technical data indicated on
the LED luminaires are to be
observed.

Changes of the design and
modifications to the LED luminaire
are not permitted.

Observe the national electrical
safety rules and regulations during
installation.

No user serviceable parts inside.

No field replaceable parts.

Be certain electrical power is OFF
before and during installation and
maintenance.

Luminaire must be connected to
a wiring system with an
equipment-grounding conductor.

Make sure the supply voltage is
the same as the rated luminaire
voltage.

Do not operate in ambient
temperatures above those
indicated on the luminaire
nameplate.
Technical Data
Nominal AC
Supply Voltage
HE*****P****:
All Others:
Supply Current
(nominal @ 230V)
110-277V AC, 50/60Hz
100-277V AC, 50/60Hz
0.4A – HE*****D****
0.5A – HE*****G****
0.7A – HE*****K****
0.9A – HE*****P****
Power consumption 89W – HE*****D****
113W – HE*****G****
145W – HE*****K****
206W – HE*****P****
Operating
temperature range
-40°C to +65°C
Power factor
>0.9
ATHD
<20% @230/240V AC
Dimensions
(Height x Diameter) 12.7cm x 40.6cm
Weight
HE**********: 9kg
Introduction
An internal power-factor-corrected switch-mode
supply allows it to be used at a nominal 100277VAC (except for HE*****P****; see note below),
50/60Hz AC supply without any variation in light
output. For supply connections, use suitable cable
rated for 100-277VAC 1.5mm2 and at least 90ºC
Recommended mounting height: 6 to 12m.
This luminaire is IP66 rated and is suitable for indoor
and outdoor applications.
NOTE: HE*****P**** versions are rated for 110277VAC ONLY.
A 2 conductor, 18AWG, plenum-rated cable is
provided for connection to a DALI network. The
cable jacket is red in color and contains one black
conductor and one red conductor.
Alternately, an integrated power and signal cable
is provided for connection to a DALI network. The
DALI conductors are violet and grey in colour.
DALI employs a diode bridge so devices can be
wired without regard for polarity. A standalone
system can control up to 64 devices.
Installation
For maximum long term reliability and light output,
the light must be installed in free air. The High Bay
luminaire design incorporates an over-temperature
control circuit that reduces input power should
internal temperatures reach a maximum level. As a
result, light output may be temporarily reduced at
higher ambient temperatures.
The High Bay luminaire is fitted with a 3m long
cable that can be extended if required. High Bay
models HE******H**, HE******E** are fitted with a
snap hook in order to hang the luminaire from an
appropriately sized mounting point.
Rear alignment mark should be observed when
installing the oval light output version, model types
HE*6********, HE*7********, HE*E********, HE*N********.
Stirrup Mounting
The ‘Stirrup Bracket’ is fixed into place using 2 bolts
and the threaded holes on the side of the luminaire.
When secured into the desired position the 2 bolts
should be tightened to 8.0 – 10.0Nm.
Installation of Luminaire
Electrical Connection
Note: Electrical installation of the extension should
be carried out by a qualified electrician.
Connecting the fitted power cable conductors as
follows:
- Green/Yellow wire connects to Safety Ground
(Earth).
- BROWN wire connects to Live.
- BLUE wire connects to Neutral.
- RED or VIOLET wire connects to DALI bus.
- BLACK or GREY wire connects to DALI bus.
anchorage and the terminals shall be such that,
should the cable or cord move out of the cord
anchorage, the current-carrying conductors
become taut before the earthing conductor.
Connect the DALI control wires to an appropriate
DALI bus. NOTE: The DALI bus cannot exceed 300
meters in length. Do not connect DALI control wires
to Live or Neutral supply wires. Never use the DALI
control wires for any other purpose than to connect
to an appropriate DALI bus.
- Restore power and verify operation
To properly configure the luminaire for use on the
DALI network, please refer to the applicable
controller documentation.
Remove protective film, if present, from the High
Bay fixture lens.
Maintenance
To avoid personal injury, disconnect power to the
light and allow the unit to cool down before
performing maintenance.
WARNING: The external flexible cable of this luminaire
cannot be replaced; if the cord is damaged, the
luminaire must be taken out of service.
Warning: Removal of the lens will void the warranty.
The lens could be cleaned periodically as needed
to ensure continued photometric performance.
Clean the lens with a damp, non-abrasive, lint-free
cloth. If not sufficient, use mild soap or a liquid
cleaner.
During any maintenance inspect the cooling fins on
the luminaire to ensure that they are free of any
obstructions or contamination (i.e. excessive dust
build-up).Clean with a non-abrasive cloth if
needed.
Electrical Parameters (LED Module Only)
Supply
Max
Working
Current
Model No
Tc
Voltage
Rating
(point)
(nominal)
(nominal)
HE*****D****
130°C
0.092A
45V
HE*****G****
130°C
0.092A
46V
HE*****K****
130°C
0.095A
39V
HE*****P****
130°C
0.100A
51V
All statements, technical information, and
recommendations contained herein are based on
information and tests that Dialight believes to be
reliable. The accuracy or completeness thereof is
not guaranteed. In accordance with Dialight
“Terms and Conditions of Sale” and since
conditions of use are outside our control, the
purchaser should determine the suitability of the
product for his or her intended use and assumes all
risk and liability whatsoever in connection
therewith.
Numbered cable installation connection:
- Green/Yellow wire connects to Safety Ground
(Earth).
- Number 1 wire connects to Live.
- Number 2 wire connects to Neutral.
Connections to be made inside a junction box with
minimum IP44 rating. Connections to be made
using appropriately rated terminal blocks. The
length of the conductors between the cord
9100127226599_B