Edco SLCP Series Two Pair SLC Loop Protector (Modular) The Edco SLCP Series are four-wire modules designed to protect signaling line circuits (SLC). The device has 0 ohms of resistance and offers line to ground protection. General Technical Specifications Operating Voltage 5, 12, 18, 24, 32, 36, 48, 52 VDC Clamping Voltage 8, 15, 20, 30, 36, 43, 50, 60 VDC Operating Current 1A Peak Surge Current 250 A (8 x 20 μs) Frequency Range 0 to 20 MHz Insertion Loss < 0.1 dB at 20 MHz SPD Technology Silicon Avalanche Diode (SAD) Connection Type Terminal block w/ compression lugs Terminals accept up to 10 AWG Operating Temperature -40°C to +85°C Dimensions (in / mm) 2.0˝ H x 1.0˝ W x 2.5˝ L [50.8 x 25.4 x 63.5 mm] (SLCP + PCB1B-WKEY Base) Weight (oz / kg) 1 oz [0.03 kg] Certifications UL 497B Warranty 5 years How to Specify the Appropriate Model SLCP-08 Features ■■ Compatible with SLC circuits ■■ Line-to-ground protection ■■ State-of-the-art silicon technology ■■ Over-current protection ■■ UL listed 497B ■■ Requires Edco PCB1B-WKEY base ■■ PC642PTU (Pass Thru Unit) ■ available for troubleshooting Ordering Information MODEL EDCO PCB1B-WKEY BASE SOLD SEPARATELY OPERATING VOLTAGE CLAMPING VOLTAGE 5 VDC 8 VDC SLCP-15 12 VDC 15 VDC SLCP-20 18 VDC 20 VDC SLCP-30 24 VDC 30 VDC SLCP-36 32 VDC 36 VDC SLCP-43 36 VDC 43 VDC SLCP-50 48 VDC 50 VDC SLCP-60 52 VDC 60 VDC ■■ 5 year warranty Installation Instructions V DANGER! Only qualified personnel should install or service this system. Electrical safety precautions must be followed when installing or servicing this equipment. To prevent risk of electrical shock, turn off and lock out all power sources to the unit before making electrical connections or servicing. Terminal Assignments PCB1B-WKEY Odd Terminals Unprotected Pair 2 { Field Side Unprotected Pair 1 { Even Terminals 10 9 8 7 6 5 4 3 2 1 } Protected Pair 2 Electronics Side } Protected Pair 1 Keying Pin 2.4" [60.96] 2.125" [53.98] Seulement le personnel qualifié doit installer ou maintenir ce systéme. Des précautions de sécurité en électricité doivent être suivis lors de l’installation ou de la maintenance de cet equipement. Pour eviter tout risque de choc électrique, débranchez et verouiller toutes les sources d’alimentation de cet equipement avant de. 1.0” [25.40] Ground Terminal 1 or 10 to Building Approved Ground ■ (preferably AC Power safety ground). NOTE: DO NOT daisy chain grounds. NOT intended for shield termination. Install ground in accordance with all applicable codes. Emerson Network Power Contact information www.EmersonNetworkPower.com/Surge Surge Protection 100 Emerson Parkway Binghamton, NY 13905 T: (607) 721-8840 T: (800) 288-6169 F: (607) 722-8713 E: [email protected] IO-50116 5/14 Rev. 3 Printed in USA Emerson Network Power, the Emerson Network Power logo and Edco are trademarks and service marks of Emerson Electric Co. ©2014 Emerson Electric Co. While every precaution has been taken to ensure accuracy and completeness herein, Emerson Network Power Surge Protection assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.