USER MANUAL - Emerson Network Power

S
■
■
■
■
■
I T E
■
■
M
O N I T O R I N G
■
RCM4
Remote Contact Monitor
USER MANUAL
TABLE OF CONTENTS
Section 1: INTRODUCTION.......................................................................................... 1
Specifications ................................................................................................................................................ 1
Section 2: INSTALLATION ........................................................................................... 3
Mounting........................................................................................................................................................ 3
Electrical Connections................................................................................................................................... 4
Section 3: HARDWARE CONFIGURATION ................................................................. 5
DIP Switch Settings ....................................................................................................................................... 5
Section 4: OPERATION................................................................................................ 7
Latched Operation......................................................................................................................................... 7
Unlatched Operation ..................................................................................................................................... 8
TABLE OF FIGURES
Figure 1. Typical System Configuration ........................................................................................................ii
Figure 2: Enclosure and Mounting Dimensions ........................................................................................... 3
Figure 3: Connection Diagram ..................................................................................................................... 4
NOTE
This equipment has been tested and found to
comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC rules.
These limits are designed to provide reasonable
protection against harmful interference when the
equipment is operated in a commercial
environment. This equipment generates, uses,
and can radiate radio frequency energy and, if
not installed and used in accordance with the
instruction manual, may cause harmful
interference
to
radio
communications.
Operation of this equipment in a residential area
is likely to cause harmful interference in which
case the user will be required to correct the
interference at his own expense.
NOTE
When the following symbols are displayed, they
indicate:
a.
Earth grounding conductor
b.
Alternating Current
Figure 1. Typical System Configuration
Section 1: INTRODUCTION
The Liebert RCM4 is a basic alarm panel. This device monitors
four sets of non-powered, normally open (N.O.) contacts. In
response to detection of an alarm, the RCM4 activates a LED;
optionally, it also activates an audible alarm and a common
alarm output. All interconnections are Class 2 circuits.
The unit is configured for latching or non-latching operation,
and the Form-C common alarm output can operate in supervised
or unsupervised mode.
The only user control is the Silence/Reset button.
The RCM4 may monitor contact-closures from a Liebert unit, or
any generic sensor or signalling device that provides N.O.
contacts as output.
Specifications
Electrical Specifications:
Voltage: 24 VAC/DC, +/-10% of nominal
Power:
6 VA
Phase:
1
Frequency: 50/60 Hz
Environmental Conditions:
Operating Temperature:
5°C to 40°C
Operating Relative Humidity: 0% to 95% (non-condensing)
Operating Altitude:
up to 2000 meters
Dimensions:
6.5”H x 6.5”W x 3.1”D
165mm x 165mm x 78mm
3.2 lbs
1.45 kg
Agency Approvals:
UL873 - Temperature-Indicating and Regulating Equipment
Liebert RCM4 • 1
Section 2: INSTALLATION
Mounting
The RCM4 is designed for wall-mounting on a finished interior
wall. Separate the display module from the base plate by
removing (3) screws -- (2) on top, (1) on bottom of unit. Save
screws for use later in re-assembly. Using appropriate tools,
remove conduit knock-outs as necessary. Knock-outs are
provided on the top and rear surfaces.
Using the base plate as a template if necessary, locate and drill
(2) mounting holes. Refer to Figure 2. Using #10 screws, affix
base plate to interior wall. Ensure base plate is secure and level.
Pull all necessary power and signal wires through knock-outs on
base plate prior to connecting to display module. Refer to subsection on Electrical Connections. Ensure all interconnects are
in place before re-attaching the display module to base plate.
Call Liebert Environmental Support at 1-800-543-2778 if
assistance is required for the installation or operation of the
RCM4 remote contact monitor.
Figure 2: Enclosure and Mounting Dimensions
Liebert RCM4 • 3
Electrical Connections
Wiring considerations for the RCM4 can be partitioned into (3)
categories: alarm inputs; common alarm output; power. Refer to
Figure 3.
Note: Minimum 20AWG wiring
recommended for all field
connections.
Alarm input #1 is wired to TB1-1 and TB1-2; alarm input #2 is
wired to TB1-3 and TB1-4; alarm input #3 is wired to TB1-5
and TB1-6; alarm input #4 is wired to TB1-7 and TB1-8. Each
input is connected to a normally-open (N.O.) contact; upon
closure of this contact, the RCM4 signals an alarm condition. It
is recommended that the RCM4 be placed no further than 300
feet (100 meters) from the signalling device.
The RCM4 provides a Common Alarm Output, at TB3. This
Form-C dry-contact is rated for Class 2 circuits 24VAC @ 3A.
Note that the common alarm can be wired for supervised or
unsupervised operation.
Power for the RCM4 is supplied to TB2-1 and TB2-2. Maximum
current draw is 0.25A at 24V AC/DC. It is strongly
recommended that the RCM4 be powered independently by an
external transformer.
Figure 3: Connection Diagram
4 • User Manual
Section 3: HARDWARE CONFIGURATION
DIP Switch Settings
The following user selectable operations are set by DIP SW1 on
the display circuit board: Refer to Table 1 and Figure 2.
Position
1
6
OFF
Alarm #1
Unlatched
Alarm #2
Unlatched
Alarm #3
Unlatched
Alarm #4
Unlatched
Audible Alarm
Disabled
See Note 1
7
See Note 1
8
Normal Mode of
Operation
2
3
4
5
ON
Alarm #1
Latched
Alarm #2
Latched
Alarm #3
Latched
Alarm #4
Latched
Audible Alarm
Enabled
Unsupervised
Common Alarm
Output
Supervised Common
Alarm Output
Test Mode
See Note 2
Table 1: DIP Switch Settings
Notes:
1. Position #6 and #7 cannot be ON at the same time. If 6 and
7 are both OFF, common alarm relay is disabled.
Supervised common alarm relay is energized on power up;
unsupervised relay is energized on detection of alarm.
2. Position #5 must be ON to test audible alarm. LEDs and
Audible Alarm Tested (only the LEDs that are in the latched
mode).
Liebert RCM4 • 5
Section 4: OPERATION
There are two basic modes of operation for the RCM4 – latched
or unlatched. The following subsections detail the respective
operation sequences.
Latched Operation
When an external alarm contact closes, the RCM4 latches the
alarm indicator (LED), latches the audible alarm, and activates
the common alarm output. The audible alarm will continue to
sound until the SILENCE/RESET button is pressed, regardless
whether the alarm condition has cleared itself or not. The
common alarm output always tracks the status of the inputs.
However, the behavior of the alarm LED is more complex; the
following two examples illustrate the subtle differences.
Example 1: Latched/Silence before alarm clears.
When the SILENCE/RESET switch is pressed while an alarm is
active, only the audible alarm will be silenced. The alarm
indicator will remain on until the input alarm condition is
cleared.
Event
Alarm Input
1
2
No Alarms
Contact Closes
Alarm Active
Alarm Stays Active;
SILENCE/RESET
pressed
Alarm Clears
3
4
NORMAL
Status LED
Green
Unlit
ALARM
Status LED
Unlit
Red
Common
Alarm
Not Active
Active
Audible
Alarm
Off
On
Unlit
Red
Active
Off
Green
Unlit
Not Active
Off
Example 2: Latched/Silence after alarm clears.
When the alarm condition clears itself before the
SILENCE/RESET switch is pressed, the alarm LED and audible
alarm will continue to be active until user acknowledgement.
The common alarm output tracks the alarm input; thus it will be
de-activated when the alarm condition clears.
Event
Alarm Input
1
2
No Alarms
Contact Closes
Alarm Active
Alarm Clears
3
4
SILENCE/RESET
pressed
NORMAL
Status LED
Green
Unlit
ALARM
Status LED
Unlit
Red
Common
Alarm
Not Active
Active
Audible
Alarm
Off
On
Green
Red
Not Active
On
Green
Unlit
Not Active
Off
Liebert RCM4 • 7
Unlatched Operation
The common alarm output, alarm indicators, and audible alarm
track the input alarm condition. If an alarm is present and the
Silence/Reset switch is pressed, then only the audible alarm is
silenced. If a new alarm is detected, the audible alarm is retriggered for the new occurrence.
Example 3: Unlatched/Silence before alarm clears.
When the SILENCE/RESET switch is pressed while an alarm is
active, only the audible alarm will be silenced. The alarm
indicator will remain on until the input alarm condition is
cleared. There is no functional difference between latched and
unlatched modes when alarms are acknowledged while they are
active.
Event
Alarm Input
1
2
No Alarms
Contact Closes
Alarm Active
Alarm Stays Active;
SILENCE/RESET
pressed
Alarm Clears
3
4
NORMAL
Status LED
Green
Unlit
ALARM
Status LED
Unlit
Red
Common
Alarm
Not Active
Active
Audible
Alarm
Off
On
Unlit
Red
Active
Off
Green
Unlit
Not Active
Off
Example 4: Unlatched/Alarm clears prior to Silence.
When the alarm condition clears itself before the
SILENCE/RESET switch is pressed in the unlatched mode, the
visible and audible alarms will automatically reset without user
intervention. This is the main difference between the latched
and unlatched modes of operation.
Event
Alarm Input
1
2
No Alarms
Contact Closes
Alarm Active
Alarm Clears
3
8 • User Manual
NORMAL
Status LED
Green
Unlit
ALARM
Status LED
Unlit
Red
Common
Alarm
Not Active
Active
Audible
Alarm
Off
On
Green
Unlit
Not Active
Off
■
■
■
■
■
■
■
■
RCM4
Remote Contact Monitor
THE COMPANY BEHIND
THE PRODUCTS
With more than 500,000 installations around the globe, Liebert
is the world leader in computer protection systems. Since its
founding in 1965, Liebert has developed a complete range of
support and protection systems for sensitive electronics:
•
Environmental systems: close-control air conditioning
from 1.5 to 60 tons.
•
Power conditioning and UPS with power ranges from 250
VA to more than 1000 kVA.
•
Integrated systems that provide both environmental and
power protection in a single, flexible package.
•
Monitoring and control – on-site or remote – from systems
of any size or location.
•
Service and support, through more than 100 service
centers around the world, and a 24-hour Customer
Response Center.
LIEBERT CORPORATION
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMBUS, OHIO 43229
800.877.9222 PHONE
614.841.6022 FAX
LIEBERT EUROPE
LIEBERT ASIA
GLOBE PARK
MARLOW
BUCKINGHAMSHIRE SL7 1YG
UNITED KINGDOM
+44.1628.403200 PHONE
+44.1628.403203 FAX
19/F, CAUSEWAY BAY PLAZA
489 HENNESSY ROAD
CAUSEWAY BAY
HONG KONG
852.2.572.2201 PHONE
852.2.831.0114 FAX
LIEBERT W EB SITE
http://www.liebert.com
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 1996 Liebert Corporation. All rights reserved throughout the world.
Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks of their
respective owners.
SL-31022 (Rev1, 10/99)
U.S.A.
Printed in