Liebert Hipulse E - Emerson Network Power

AC Power Systems
Liebert Hipulse E
The High-ECO-Availability UPS
We’re Emerson Network Power, backed by Emerson, a global
company that brings technology and engineering together to
provide innovative solutions for the benefit of our customers.
We’re the world leader in providing Business-Critical Continuity™
to organizations like yours, enabled by our product and service
centres of expertise.
Liebert, is one of industry-leading
Product Brand for many technology
solutions in power systems, connectivity,
embedded power, outside plant,
precision cooling and monitoring.
The Liebert Adaptive ArchitectureTM
creates a power and cooling
infrastructure for IT systems that
can meet the highest availability
requirements, enhance operation
flexibility and reduce the cost of ownership.
2
Liebert Hipulse E
Hi-Availability UPS
The growth of mission critical
applications in today's digital world
and the increased dependence of
your business on such applications
have led Emerson Network Power to
design Liebert Hipulse E UPS to
provide you with reliable,
high-availability power.
Having extensively surveyed
customers’ needs and thoroughly
mapped their requirements,
Hipulse E has been carefully
designed to deliver maximum
Return On Investment (ROI).
The Liebert Hipulse E
provides industry-leading
overload and short-circuit
capability
3 Phase
110% for 1hour
125% for 10 min
150% for 1 min
1 Phase
200% for 30 sec
Inverter Short-Circuit
3 phase = 1.5 times nominal current
1 phase = 2.9 times nominal current
for <5 sec (EN 50091-1)
3
Liebert Hipulse ensures you the highest availability
• From scalability to redundancy, from user-friendliness
to maintainability, from parallel ability to
connectivity, and from investment protection to
lower cost of ownership, whichever values you need,
Liebert Hipulse E provides industry leading efficiency.
Liebert Hipulse E, is the top line in our range of power
quality solutions for mission critical applications,
some of which are listed below. Liebert Hipulse E
(with true on-line double conversion topology) comes
in five popular ratings, ranging from 300 to 800 kVA
(400 V, 50/60 Hz).
4
• With a set of options and features that address
customer needs by providing value and achieving
high availability and reliability.
• The New Liebert Hipulse E with its parallel
redundant and dual bus configurations is best
in class for MTBF and MTTR, providing your critical
load with the optimum availability With a
dual bus system, availability can reach 99,9999999
The best flexibility in and adaptability to load type
(Leading PF compatibility)
Load compatibility
The trend in ICT loads is to absorb
a capacitive PF especially in light load
conditions. Hipulse has an innovative
design that adapts the UPS output filter
to the capacitive PF and an output
transformer with a rating that is optimised to handle these loads.
With Liebert Hipulse E you can tune the
output filter by matching different load
power factor values. With the option of
the internal Xtreme power factor, a wide
range of output power factors can be
covered, increasing the maximum value
of active power. Different factory
settings enable the unit to provide its
Medium flexibility with Xtreme PF1
max power performance
whatever the load power factor is.
1) Level 1: No kW derating for a load PF
range from 0.95 lead to 0.8 lagging
2) Level 2: No kW derating for a load PF
range from 0.9 lead to 0.9 lagging
Maximum flexibility with Xtreme PF0.9
Line compatibility
The new Liebert Hipulse E provides
optimum harmonic reduction,
thanks to three key features:
- Upstream Green Power through low - Further reduced THDI can be
input current THDI & high input
achieved with the addition of the
power factor using different solutions
Active Filter as an external option;
by way of 6-pulse with harmonic filter
this reduces the cost of ownership
or 12-pulse with passive harmonic
thanks to an improved input power
filter, depending on the requirement
factor that will reduce electricity
costs.
5
The new Liebert HipulseE provides
you with an extremely efficient way
of using the UPS Available in single
module or dual bus configuration,
the Intelligent ECOMode improves
UPS Efficiency by up to 98%.
Efficiency without compromise
and lower ownership costs
The brand new Intelligent
ECOMode option
Intelligent ECOmode gives you many
advantages and cost savings:
• Set UPS control either in double conversion or ECOmode without any
impact on the load
• Immediately achieve significant
energy savings in existing data
centers
• Save energy continuously or in periodical cycles and transfer to double
conversion when the utility exceeds
the ITIC limit
• Ecomode can be activated in various
ways,
depending
upon
the
customer’s needs
Cost saving per year
at 0.1€/kWh
(estimation)
300 kVA
400 kVA
500 kVA
600 kVA
800 kVA
6
Compared with a double conversion
running at a typical efficiency of
around 93% at full load (92% at 50% of
Load), annual savings on the UPS can
be considerable (@ 0.1€/kWh)
Indirect effect
Generally, the UPS is kept in an air
conditioned room. The heat losses
from the UPS must be compensated for
by air conditioning, which further
increases electricity consumption.
Therefore, UPS efficiency affects the
degree of air conditioning required.
UPS
At 50%
€/year
€ 6.996
€ 9.327
€ 11.659
€ 13.991
€ 18.655
At 100%
€/year
€
€
€
€
€
11.534
15.379
19.223
23.068
30.757
Cooling
at 100% load
€/year
€ 3.845
€ 5.126
€ 6.408
€ 7.689
€ 10.252
How much you can save and how
1) With the power utility within a user-adjustable voltage range,
the UPS is working on bypass at high efficiency. The inverter is always
syncronised with the bypass.
2) If the grid exceeds the pre-fixed limits, the UPS switches immediately to
double conversion.
3) For wide grid variation, the UPS switches to battery, continuously
feeding the load.
7
This operation mode reduces the cost of ownership by saving energy
The UPS can work either in DOUBLE CONVERSION or in ECO-MODE and either continuously or in duty cycles fixed
by the user
The cost savings in ECO-MODE operation vs. DOUBLE CONVERSION, working at 93% of full load efficiency,
are sumarised in the following graph, in continuous operation at 100% of load and with an energy cost of 0.1€/kWh
.
.
Total cost
saving.
.
.
Cost saving
UPS
.
.
.
.
.
8
Cost saving
Cooling
Value-added power
options
Liebert Hipulse E offers you an array of value-added
options listed below:
External
Battery circuit breaker (wall or cabinet
mounted)
Battery cabinet
Main static switch (MSS) for centralised
static
bypass switch
Wrap-around maintenance bypass cabinet
Top cable entry
Input isolation transformer
Remote alarm monitor (wall mounted)
Internal
Paralleling kit (for 1+5 modules)
Input harmonic filter
Common battery sharing kit
Fan failure alarm
Power communication option
IP protection: IP21 - IP30 - IP31
Special feature applications (SFA’s)*
Dynamic system expander (DSE)
Multi-bus (2-bus, 3-bus and 4-bus)
9
Multi bus configurations
Liebert Hipulse E is designed to include numerous useful optional configurations. The top 4 are listed below:
Hot Stand-by
1 + N with Distributed Bypass
Parallel configuration without centralised bypass
Bypass Mains
Bypass Mains
Normal
Mains
Normal Mains
Normal
Mains
Normal
Mains
Normal Load
Priority Load
Normal Mains
UPS 2
UPS 1
UPS 6
LOAD
N + 1 with Centralized Bypass
Parallel configuration with centralised bypass
Multi Bus (2-bus, 3-bus, 4-bus)
2- bus configuration with HiSwitch2
Bypass
Mains
Bypass
Mains
Bypass Mains
Normal
Mains
PSI 1
Normal
Mains
PSI 6
PSI 1
Normal
Mains
Normal
Mains
Normal
Mains
HiSynch
HiSwitch 1
Load 1
UPS 2
UPS 1
UPS 6
HiSwitch 2
LOAD
Load 2
*Both HiSwitch and HiSwitch2 are compatible
10
Normal
Mains
PSI 6
General Characteristics - [Liebert Hipulse E]
Model Name
Nominal Power Rating at 0.8 PF Load
Hipulse E
KVA
300
400
500
600
800
Input Parameters
Input Voltage to Rectifier
Vac
380/400/415*(400V:nominal) 3-phase, 3-wire
Input Voltage to Bypass
Vac
380/400/415*(400V:nominal) 3-phase +N, 4-wire
Permissible Input Voltage Range
Vac
323 to 457
Input Frequency
Hz
50 or 60
Permissible Input Frequency Range
Hz
47 or 63
Input THDi at nominal voltage at full load
%
<4-5% with 12-pulse + Filter
Input Power Factor at nominal voltage
Flexi Power Walk-In
>=0,90% with 12-pulse + Filter
second
5 to 120 (selectable)
Battery & DC Parameters
Battery Type
Nominal Battery Bus
VRLA (Valve Regulated lead Acid) or Wet or NiCd
Vdc
396 (Float Voltage: 446V)
480
396
480
(F. V.: 540V) (F. V.: 446 V) (F. V.: 540V)
End-Cell Voltage
DC ripple voltage in float & Const V Ch.mode
Vdc/Cell
Selectable from 1,65 to 1,90 (for VRLA/Wet Cells)
%
<1 (RMS value)
Temperature compensated Battery Charging
Optional
Output Parameters
Inverter Type
IGBT-based Sine-Sine PWM Cotrolled
Output Power
KW
240
320
Output Voltage
Vac
380/400/415* (400V:nominal) 3-phase, 4-w
Output Voltage Regulation
%
+/- 0,5 (3 phase RMS average)
Output Frequency
Hz
50 or 60
Output Frequency Regulation
%
+/- 0,05
Output Voltage THD at nominal voltage
%
1 (typ), 2% (max)
Capability to handle High Crest Factor Load
Capability to handle Step Load
400
480
3:1 (compliant with IEC 62040-3)
%
0-100 or 100-0
m seconds
10 (recovery to 95% of the voltage level)
Voltage Displacement
°el
120° +/- 1° el (with 100% unbalanced load)
Overload Conditions
%FL
Transient Recovery
640
Capability to handle Leading PF Load
Up to 0,7**
110 for 60 minutes
125 for 10 minutes
150 for 1 minutes
System Parameters
UPS Efficiency (without any power option)
%
Up to 98% in ECOmode
Physical Parameters & Standards
Width (applicable to 6 pulse version)***
mm
1640
2460
Width (applicable to 12 pulse version)***
mm
2280
2460
Depth
mm
Height
mm
3200
850
4410
1000
1900
Weight 6p (approx.)
Kg
1850
2400
Weight 12p (approx.)
Kg
2540
3100
Colour
Not Applicable
2460
Not applicable
4200
4500
5050
Ral 7021 - Ral 7035
Front door Opening (for better Serviceability)
More than 180°
Degree of Protection for UPS Enclosure
IP 20 even with front door in opened condition
Standards & Conformities
IEC 62040-3, IEC 62040-2, IEC 62040-1-1, CE Mark ; EN 62040-1-1,
EN 50091-2, EN62040-3, EN 60950, EN 60529 and VFI 111
Enviromental Parameters
Storage Temperature Range
°C
-25 to 70 (UPS) & -20 to 30 (Battery)
Operating Temperature Range
°C
0 to 40 (UPS) & 20 +/- 5 (Battery)
Relative Humidity
%
0 to 95 (non condensing)
Maximum Altitude above MSL (Mean Sea Level)
m
1000 (as per IEC 62040/3)
* 4-5% more power output for 415V input & output ; ** with suitable derating; ***with OR without input harmonic filter
While specifying the parameters here, it is assumed that, extremes of all the conditions do not apply simultaneously.
While every precaution has been taken to ensure accuracy and completeness in this brochure, Liebert Corporation assumes no responsibility, and discaims all liability
for damages resulting from use of this information or for any errors or omissions. © 2004 Liebert Corporation. All rights reserved throughout the world. Specifications subject
to change without notice. All names referred to are trademarks or registered trademarks of their respective owners.
11
Emerson Network Power, a business of Emerson (NYSE:EMR),
is the global leader in enabling Business- Critical ContinuityTM
from grid to chip for telecommunication networks, data centers,
health care and industrial facilities. Emerson Network Power
provides innovative solutions and expertise in areas including AC
and DC power and precision cooling systems, embedded
computing and power, integrated racks and enclosures, power
switching and controls, monitoring and connectivity.
All solutions are supported globally by local Emerson Network
Power service technicians. Liebert power, precision cooling and
monitoring products and services from Emerson Network Power
improve the utilization and management of data center and
network technologies by increasing IT system availability,
flexibility and efficiency. For more information, visit
www.liebert.com, www.emersonnetworkpower.com or
www.eu.emersonnetworkpower.com.
Locations
Emerson Network Power - Headquarters EMEA
Liebert Business
Via Leonardo Da Vinci 16/18
Zona Industriale Tognana
35028 Piove di Sacco (PD) Italy
Tel: +39 049 9719 111
Fax: +39 049 5841 257
[email protected]
Emerson Network Power - Service EMEA
Via Leonardo Da Vinci 16/18
Zona Industriale Tognana
35028 Piove di Sacco (PD) Italy
Tel: +39 049 9719 111
Fax: +39 049 9719045
[email protected]
Emerson Network Power Ltd
Fourth Avenue, Globe Park
Marlow, Buckinghamshire,
SL7 1YG
UK
Tel: +44 (0) 1628 403 200
Fax: +44 (0) 1628 403 294
[email protected]
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2009 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert
Corporation. All names referred to are trademarks
or registered trademarks of their respective owners.
BRO-HIP E-EN-XX
www.eu.emersonnetworkpower. com
Emerson Network PowerTM.
The global leader in enabling business-critical continuity .
TM
[email protected]
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Out Side Plant
Power Switching e Controls
Precision Cooling
Rack & Integrated Cabinets
Services
Surge Protection