ADAM-4017/4017+ ADAM-4018/4018+ ADAM-4019+

ADAM-4017/4017+
ADAM-4018/4018+
ADAM-4019+
ADAM-4017/4017+
ADAM-4018/4018+
Specifications
Specifications
General
 Power Consumption
8-channel Analog Input Modules
with Modbus®
8-channel Thermocouple Input
Module with Modbus®
8-channel Universal Analog
Input Module with Modbus®
ADAM-4019+
Specifications
General
1.2 W @ 24 VDC
Analog Input
 Channels
Six differential, two
single-ended (4017)
eight differential (4017+)
 Ch. Independent Conf. ADAM-4017+ only
 Input Impedance
Voltage: 20 MΩ
Current: 120 Ω
 lnput Type
mV, V, mA
 lnput Range
±150 mV, ±500 mV, ±1
V, ±5 V, ±10 V, ±20 mA,
4~20mA (4017+ only)
 Modbus®
ADAM-4017+ only
 Overvoltage Protection ±35 V
 Sampling Rate
10 samples/sec. (total)
 Span Drift
±25 ppm/° C
 TVS/ESD Protection
Built-in
 Zero Drift
±6 µV/° C
 Power Consumption
 T/C-Burnout Detector
0.8 W @ 24 VDC
Yes (4018+ only)
Analog Input
 Channels









Six differential, two
single-ended (4018)
eight differential (4018+)
Ch. Independent Conf. ADAM-4018+ only
Input Impedance
Voltage: 20 MΩ
Current: 120 Ω
lnput Range
±15 mV, ±50 mV, ±100
mV, ±500 mV, ±1 V, ±2.5
V, ±20 mA (4018);
4~20 mA (4018+)
lnput Types
Thermocouple, mV,
V, mA (4018) (4018+
Supports T/C & 4~20
mA only)
Modbus®
ADAM-4018+ only
Overvoltage Protection ±35 V
Sampling Rate
10 samples/sec. (total)
Span Drift
±25 ppm/° C
T/C Type and Temperature Ranges
J 0 ~ 760° C
R 500 ~1750° C
K 0 ~ 1370° C
S 500 ~1750° C
T -100 ~ 400° C
B 500 ~1800° C
E 0 ~ 1000° C
 TVS/ESD Protection
 Zero Drift
Built-in
±6 µV/° C
Common Specification
General
 Dimensions
 Connectors




13-16
Enclosure
Mounting
Power Input
Watchdog Timer
70 x 122 x 30 mm
2 x Plug-in terminal
block (#14~22 AWG)
ABS+PC
DIN 35 rail, stack, wall
Unregulated 10~30 VDC
1.6 sec. (system)
Remote DA&C Modules
General
 Power Consumption
1.0 W @ 24 VDC
Analog Input
 Accuracy
 Bandwidth












±0.1% of voltage input
13.1 Hz @ 50 Hz, 15.72
Hz @ 60 Hz
Burn-out Detection
+4~20mA & all T/C
Channels
8 differential channels
for individual input type
CMR @ 50/60 Hz
92 dB min.
Resolution
16 bits
Input Range
+/-1V, +/-2.5V, +/-5V,
+/-10V,
+/- 100mV, +/-500mV,
+/-20mA, +4~20mA
Input Impedance
Voltage: 20 MΩ
Current: 120 Ω
Input Type
T/C, mV, V,mA
Isolation Protection
3000 VDC
Overvoltage Protection ±35 V
T/C Type and Temperature Range
J
0 ~ 760 °C
K
0 ~ 1370 °C
T
-100 ~ 400 °C
E
0 ~ 1000 °C
R
500 ~ 1750 °C
S
500 ~ 1750 °C
B
500 ~ 1800 °C
Span Drift
±25 ppm/°C
Zero Drift
±6 µV/°C
Ordering Information
Environment
 ADAM-4017
 Humidity
5 ~ 95% RH
 Operating Temperature -10~70° C (14~158° F)
 Storage Temperature -25~85°C (-13~185° F)
 ADAM-4017+
 ADAM-4018
 ADAM-4018+
 ADAM-4019+
8-channel Analog Input
Module
8-channel Differential Analog
Input Module w/Modbus®
8-channel Thermocouple, mV,
V, mA Input Module
8-channel Differential, mA and
Thermocouple Input Module
w/Modbus®
8-channel Universal Analog
Input Module w/Modbus®
ADAM 4000/4100 Series
Common Specifications
Unit: mm
Communication
 RS-485 (2-wire) to host
 Speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps (ADAM-4080,
ADAM-4080D only support up to 38400 bps)
 Max. communication distance: 4000 feet (1.2 km)
 Power and communication LED indicator
 ASCII command/response protocol
 Communication error checking with checksum
 Asynchronous data format:
Advantech protocol: 1 start bit, 8 data bits, 1 stop bit, no parity
Modbus protocol: 1 start bit, 8 data bits, 1 or 2 stop bit, parity check (none, odd,
even) (ADAM-4100 series only)
 Up to 256 multidrop modules per serial port
 Online module insertion and removal
 Transient suppression on RS-485 communication lines
13-24
Dimensions
Remote DA&C Modules