ADAM-4017/4017+ ADAM-4018/4018+ ADAM-4019+ ADAM-4017/4017+ ADAM-4018/4018+ Specifications Specifications General Power Consumption 8-channel Analog Input Modules with Modbus® 8-channel Thermocouple Input Module with Modbus® 8-channel Universal Analog Input Module with Modbus® ADAM-4019+ Specifications General 1.2 W @ 24 VDC Analog Input Channels Six differential, two single-ended (4017) eight differential (4017+) Ch. Independent Conf. ADAM-4017+ only Input Impedance Voltage: 20 MΩ Current: 120 Ω lnput Type mV, V, mA lnput Range ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA, 4~20mA (4017+ only) Modbus® ADAM-4017+ only Overvoltage Protection ±35 V Sampling Rate 10 samples/sec. (total) Span Drift ±25 ppm/° C TVS/ESD Protection Built-in Zero Drift ±6 µV/° C Power Consumption T/C-Burnout Detector 0.8 W @ 24 VDC Yes (4018+ only) Analog Input Channels Six differential, two single-ended (4018) eight differential (4018+) Ch. Independent Conf. ADAM-4018+ only Input Impedance Voltage: 20 MΩ Current: 120 Ω lnput Range ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V, ±20 mA (4018); 4~20 mA (4018+) lnput Types Thermocouple, mV, V, mA (4018) (4018+ Supports T/C & 4~20 mA only) Modbus® ADAM-4018+ only Overvoltage Protection ±35 V Sampling Rate 10 samples/sec. (total) Span Drift ±25 ppm/° C T/C Type and Temperature Ranges J 0 ~ 760° C R 500 ~1750° C K 0 ~ 1370° C S 500 ~1750° C T -100 ~ 400° C B 500 ~1800° C E 0 ~ 1000° C TVS/ESD Protection Zero Drift Built-in ±6 µV/° C Common Specification General Dimensions Connectors 13-16 Enclosure Mounting Power Input Watchdog Timer 70 x 122 x 30 mm 2 x Plug-in terminal block (#14~22 AWG) ABS+PC DIN 35 rail, stack, wall Unregulated 10~30 VDC 1.6 sec. (system) Remote DA&C Modules General Power Consumption 1.0 W @ 24 VDC Analog Input Accuracy Bandwidth ±0.1% of voltage input 13.1 Hz @ 50 Hz, 15.72 Hz @ 60 Hz Burn-out Detection +4~20mA & all T/C Channels 8 differential channels for individual input type CMR @ 50/60 Hz 92 dB min. Resolution 16 bits Input Range +/-1V, +/-2.5V, +/-5V, +/-10V, +/- 100mV, +/-500mV, +/-20mA, +4~20mA Input Impedance Voltage: 20 MΩ Current: 120 Ω Input Type T/C, mV, V,mA Isolation Protection 3000 VDC Overvoltage Protection ±35 V T/C Type and Temperature Range J 0 ~ 760 °C K 0 ~ 1370 °C T -100 ~ 400 °C E 0 ~ 1000 °C R 500 ~ 1750 °C S 500 ~ 1750 °C B 500 ~ 1800 °C Span Drift ±25 ppm/°C Zero Drift ±6 µV/°C Ordering Information Environment ADAM-4017 Humidity 5 ~ 95% RH Operating Temperature -10~70° C (14~158° F) Storage Temperature -25~85°C (-13~185° F) ADAM-4017+ ADAM-4018 ADAM-4018+ ADAM-4019+ 8-channel Analog Input Module 8-channel Differential Analog Input Module w/Modbus® 8-channel Thermocouple, mV, V, mA Input Module 8-channel Differential, mA and Thermocouple Input Module w/Modbus® 8-channel Universal Analog Input Module w/Modbus® ADAM 4000/4100 Series Common Specifications Unit: mm Communication RS-485 (2-wire) to host Speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps (ADAM-4080, ADAM-4080D only support up to 38400 bps) Max. communication distance: 4000 feet (1.2 km) Power and communication LED indicator ASCII command/response protocol Communication error checking with checksum Asynchronous data format: Advantech protocol: 1 start bit, 8 data bits, 1 stop bit, no parity Modbus protocol: 1 start bit, 8 data bits, 1 or 2 stop bit, parity check (none, odd, even) (ADAM-4100 series only) Up to 256 multidrop modules per serial port Online module insertion and removal Transient suppression on RS-485 communication lines 13-24 Dimensions Remote DA&C Modules