p083.

SURGE PROTECTORS
RAV-BWZ-2A/RAV-BXZ-2ASERIES
●RAV-BWZ-2A:
Designed specifically for use in AC power line
applications. This model uses specially treated
discharge electrodes for greatly enhanced noise
immunity test and surge life making it optimum for the
protection of single-phase power supply circuits.
Safety Approvals
: UL1449
: C22.2, No. 8
UL
CSA
File No .
E143446
LR 105073
●RAV-BXZ-2A:
SURGE ABSORBERS
This model is designed for use in three phase
power circuit applications. Combining multiple RAVs
with specially treated electrodes for greatly enhanced
noise immunity test and surge life, this model is
constructed in a unit-molded body.
ELECTRICAL SPECIFICATIONS
Peak Surge
Clamp*
Current
Voltage
8/20 s(A)
V1.0±10%
RAV-401BWZ-2A
403
2500
RAV-781BWZ-2A
783
RAV-781BXZ-2A
783
* Equivalent Varistor Voltage @ 1MA
Model No.
Peak Surge
Voltage
1.2/50 s(V)
Response
Time(ns)
20K
50
Capacitance
(PF)Max.
100
83
50
Max. Line
Voltage
(Vrms)
145
300
300
Weight
(g)
60
100
Operating
Temp.
Range(℃)
−20℃ to +70℃
RAV-BWZ-2A/RAV-BXZ-2ASERIES
AC POWER LINES
●BWZ-2A
●BXZ-2A
●Use of Surge Protectors:
Okaya Surge protectors in combination with Okaya
XYE series filter capacitors offer superb lightning
surge suppression. Capacitor XYE-104332 will
equalize excessive currents aiding the surge pro-tector
in absorbing the lightning surge. This parts
combination is equally effective against severe noise.
Surge protectors can be connected to protect
machines using 208/240VAC 3-phase power supplies.
The combination of the 3XYG series of high pulse
capacitors with the RAV-781BXZ-2A surge protec-tor,
is an effective countermeasure against exces-sive
surge and noise.
●Noise Margin Test:
Noise margin testing usually requires the physical
disconnection of lightning surge protection
components. Such disconnection often is difficult, and
time consuming. Okaya's RAV-BWZ-2A and BXZ-2A
series allow noise margin testing without any such
disconnection as they are designed to withstand the
rigors of testing.
Model Number
Power source
Impulse width
Impulse voltage(+,−)
Applied period(Hours)
RAV-401BWZ-2A
RAV-781BWZ-2A
Single-phase 135VAC 50//60Hz
Single-phase 270VAC 50//60Hz
1us
1us
2kV
2kV
1.5Hrs Max.
1.5Hrs Max.
Impulse Condition
84
RAV-781BXZ-2A
3-wire 270VAC 50/60Hz
1us
2kV
1.5Hrs Max.