Cutler-Hammer Series Rating Chart

Cutler-Hammer Series Rating Chart
Switchboards: PRL-C / PRL-i
(See Notes on Page 3)
Panelboards: PRL 5P, PRL 4, PRL 3A & Pow-R-Command Panelboards
Max System
Voltage
Maximum
SCCR
100kA
120/240
200kA
100kA
Line Side
Fuse
LPN-RK
Max Fuse
Current Rating
200
JJN, LPJ
400
LPN-RK
100
JJN, LPJ
200
JJN, LPJ
400
LPN-RK
200
JJN, LPJ
400
JJN
KRP-C
600
6000
KRP-C
6000
LPN-RK
100
240
200kA
65kA
480/277
100kA
200kA
480
100kA
200kA
LPN-RK
200
JJN, LPJ
200
JJN, LPJ
400
JJS, LPJ
JJS, LPJ
LPS-RK
LPJ
200
100
200
600
JJS
600
LPS-RK
JJS, LPJ
LPS-RK
JJS, LPJ
KRP-C
KRP-C
100
400
100
200
1200
800
100
LPS-RK
100kA
600
JJS, LPJ
200kA
© 2000 Cooper Bussmann, Inc.
KRP-C
LPS-RK
JJS, LPJ
200
400
600
200
400
1200
400
600
Page1 of 3
Load Side
Circuit Breaker
GB, GHB
BA, BAB, HQP, QBHW,
QPHW
BA, BAB, HQP, QBHW,
QPHW, GB, GHB
BA, BAB, HQP, QBHW,
QPHW
GB, GHB
GHB
GB, CA
BAB_H, QBHW_H, HQP_H,
QPHW_H
CA, CAH, HCA
EHD, FD
FDB, ED, JDB, JD, DK, KDB,
KD
GHB
BAB_H, QBHW_H, HQP_H,
QPHW_H, CAH, HCA, GB
GB, GHB
BAB_H, HQP_H, QBHW_H,
QPHW_H, CA, CAH, HCA
GHB
GB
GHBS
GHBS
GHB
EHD, FD, HFD, FDC
GHB, EHD, FD, HFD, FDC,
JD, HJD, JDC
Amps
ALL
Poles
1,2
ALL
1,2
ALL
1,2
ALL
1,2
ALL
ALL
ALL
1,2
1,2,3
2,3
ALL
2,3
ALL
ALL
2,3
1,2,3
ALL
2,3
ALL
1,2,3
ALL
2,3
ALL
2,3
ALL
2,3
ALL
ALL
ALL
ALL
ALL
ALL
1,2,3
2,3
1,2
1,2
1,2,3
2,3
ALL
2,3
GHB
ALL
1,2,3
EHD
EHD, FD, HFD,FDC
MC, HMC, NC, HNC
MC, HMC
FD, HFD
FDC
JD, HJD, JDC
KD, HKD, KDC
LC
FD, HFD
FDC
JD, HJD, JDC
LC
LC
KD, HKD, KDC, LC
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
2,3
10/3/00
Cutler-Hammer Series Rating Chart
Panelboards: PRL 1A, PRL 2A, PRL 1A-LX, PRL 2A-LX
Max System
Voltage
Maximum
SCCR
100kA
120/240
200kA
100kA
Line Side
Fuse
LPN-RK
Max Fuse
Current Rating
200
JJN, LPJ
400
LPN-RK
100
JJN, LPJ
200
JJN, LPJ
400
LPN-RK
200
JJN, LPJ
400
JJN
KRP-C
600
6000
KRP-C
6000
LPN-RK
100
LPN-RK
200
JJN, LPJ
200
JJN, LPJ
400
JJS, LPJ
JJS, LPJ
LPS-RK
LPJ
200
100
200
600
JJS
600
LPS-RK
JJS, LPJ
100
400
240
200kA
65kA
480/277
100kA
200kA
(See Notes Below & Page 3)
Load Side
Circuit Breaker
GB, GHB
BA, BAB, HQP, QBHW,
QPHW
BA, BAB, HQP, QBHW,
QPHW, GB, GHB
BA, BAB, HQP, QBHW,
QPHW
GB, GHB
GHB
GB, CA
BAB_H, QBHW_H, HQP_H,
QPHW_H
CA, CAH, HCA
EHD, FD
FDB, ED, JDB, JD, DK, KDB,
KD
GHB
BAB_H, QBHW_H, HQP_H,
QPHW_H, CAH, HCA, GB
GB, GHB
BAB_H, HQP_H, QBHW_H,
QPHW_H, CA, CAH, HCA
GHB
GB
GHBS
GHBS
GHB
EHD, FD, HFD, FDC
GHB, EHD, FD, HFD, FDC,
JD, HJD, JDC
GHB
Amps
ALL
Poles
1,2
ALL
1,2
ALL
1,2
ALL
1,2
ALL
ALL
ALL
1,2
1,2,3
2,3
ALL
2,3
ALL
ALL
2,3
1,2,3
ALL
2,3
ALL
1,2,3
ALL
2,3
ALL
2,3
ALL
2,3
ALL
ALL
ALL
ALL
ALL
ALL
1,2,3
2,3
1,2
1,2
1,2,3
2,3
ALL
2,3
ALL
1,2,3
Notes for above Table:
1) The HQP & QPHW are not listed for use in the PRL1A-LX Panel.
2) PRL1A & PRL1A-LX are for use at 240V maximum.
3) Branch breakers for maximum 120/240V systems include: BAB, HQP, QBHW & QPHW.
4) Branch breakers for maximum 240V systems include: BAB_H, HQP_H, QBHW_H & QPHW_H.
5) PRL2A & PRL2A-LX, branch breakers include: GHB, GHBS & GB.
6) PRL1A-LX & PRL2A-LX Main & Sub-feed breakers include: ED, FD, HFD, FDC.
7) PRL1A & PRL2A Main & Sub-feed breakers include: CA, CAH, HCA, ED, FD, HFD, FDC, JD, HJD, JDC, KD, HKD & KDC.
© 2000 Cooper Bussmann, Inc.
Page2 of 3
10/3/00
Cutler-Hammer Series Rating Chart
(See Comments Below)
Triple Series Rating - Switchboards: PRL-C & PRL-i
Panelboard Types: PRL 5P, PRL 4, PRL 3A, PRL 2A, PRL 2A-LX, PRL 1A, PRL 1A-LX
& Pow-R-Command Panels
Max System
Voltage
Maximum
SCCR
Line Side
Fuse
120/240
100kA
KRP-C
(Max Fuse
Size - 6000A)
Tenant
Main Type
DK, KDB, KD
JD, JDB
FD
FD, FDB
EHD
DK, KDB, KD
240
100kA
KRP-C
(Max Fuse
Size - 6000A)
JD, JDB
FD
FD, FDB
EHD
Branch Type
Circuit Breaker
GB, GHB
GB, GHB
GB, GHB
HQP
BA, BAB
BA, BAB, HQP
GHB
GB, EHD
CA, CAH, HCA
FD, FDB
JD, JDB
GHB
GB
GHB
GB
BAB_H, QBHW_H, HQP_H,
QPHW_H
BAB_H, HQP_H
Amps
ALL
ALL
ALL
15-70
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
ALL
Poles
1,2
1,2
1,2
1,2
1,2
1,2
1,2,3
2,3
2,3
2,3
2,3
1,2,3
2,3
1,2,3
2,3
ALL
2,3
ALL
2,3
NOTE (1): The data in these charts was compiled from information in Cutler-Hammer, Series Rating Information
Manual, catalog reference number 1C96944H01 Rev. E, pages 18-24, and Cutler-Hammer Consulting Application
Catalog 12th Edition, pages F1-11 - F1-12. Cooper Bussmann assumes no responsibility for the accuracy or
reliability of the information. The information contained in the tables may change without notice due to equipment
design modifications.
NOTE (2): The line-side fused switch may be in a separate enclosure or in the same enclosure as the load-side
circuit breaker. A line-side fused switch may be integral or remote.
NOTE (3): Max fuse current rating denotes the largest amperage fuse that may be used for that series rated
combination. A lower amperage fuse may be substituted for the listed fuse.
© 2000 Cooper Bussmann, Inc.
Page3 of 3