GE Series Rating Chart

GE Series Rating Chart
Spectra Series
Maximum
Maximum
System Voltage SCCR
42kA
Line Side
Fuse
JJN, LPJ
KRP-C
Max Fuse
Current Rating
600
2000
400
LPJ, JJN
600
100kA
KRP-C
240 Vac
LPN-RK
200kA
LPJ, JJN
KRP-C
800
1200
2000
2500
200
400
600
2000
100
LPS-RK
200
277Vac
100kA
400
LPJ, JJS
600
65kA
LPJ
LPS-RK
600
100
200
400
480 Vac
100kA
LPJ, JJS
600
JJS
KRP-C
600 Vac
200kA
KRP-C
200kA
KRP-C
800
1200
2000
2000
2500
2000
2500
(See Notes on Page 4)
Load Side
Circuit Breaker
Amps
Poles
TJD
250-400
2, 3
TJD
250-400
2, 3
TQD
125-225
2, 3
THHQB
40-100
3
TQD
100-225
2
TQD
125-225
3
TJD
250-400
2, 3
SFH
70-250
2, 3
TJD
250-400
2, 3
THJK
250-600
2, 3
TEB, TED
15-100
1, 2, 3
SFH, SFL
70-250
2, 3
SED, SEH, SEL
15-150
2, 3
TEB
15-100
1, 2
TEB, TED
15-100
2, 3
TJD
250-400
2, 3
SFH, SFL
70-250
2, 3
SED, SEH, SEL
15-150
2, 3
SGD, SGH, SGL
125-600
2, 3
TED
15-50
1
THED
15-30
1
TEY
15-100
1
SED, SEH, SEL
15-150
2, 3
TEY
15-100
1
TED
15-50
1
TED
15-50
1
THED
15-30
1
SED, SEH, SEL
15-150
2, 3
TEY
15-100
1
SED, SEH, SEL
15-150
2, 3
TED, THED
15-150
2, 3
TED, THED6
15-100
2, 3
TEY
15-100
2, 3
SED, SEH, SEL
15-150
2, 3
TED
15-50
1
TED, THED6
15-100
2, 3
SFH, SFL
70-250
2, 3
SGH, SGL
125-600
2, 3
TEY
15-100
2, 3
SED, SEH, SEL
15-150
2, 3
SKH, SKL
300-1200
2, 3
THJK
125-600
2, 3
SKH, SKL
300-1200
2, 3
SGH, SGL
125-600
2, 3
TPV, THPV
800A FRAME (1)
3
TPV, THPV
2500A FRAME (1)
3
TPV, THPV
800A FRAME (1)
3
TPV, THPV
2500A FRAME (1)
3
(1) Includes all sensor/rating plug or setting values within stated frame size.
© 2000 Cooper Bussmann, Inc.
Page 1 of 4
10/3/00
GE Series Rating Chart
AL / AQ PANELBOARD
Maximum
Maximum
System Voltage SCCR
42kA
65kA
100kA
240 Vac
200kA
(See Notes on Page 4)
Max Fuse
Load Side
Current Rating Circuit Breaker
Amps
THQL-GF
15-30
JJN
600
THQL
15-100 (2)
JJN, LPJ
600
TJD
250-400
KRP-C
2000
TJD
250-400
THHQL
15-70
JJN
600
THHQL
15-125
TFJ
70-225
JJN, LPJ, LPN-RK
600
TFJ
70-225
KRP-C
3000
THQL
15-100 (2)
LPN-RK
200
THQP
15-50
JJN
200
THQL
15-100 (2)
400
TQD
125-225
THHQL, THHQB
40-100
LPJ, JJN
TFJ
70-225
600
TQD
100-225
TQD
125-225
TJD
250-400
800
TFJ
70-225
1200
KRP-C
SFH
70-250
TJD
250-400
2000
THQL
15-100 (2)
TFJ
70-200
LPN-RK
200
SFH, SFL
70-250
SED, SEH, SEL
15-150
THQL
15-100 (2)
TFJ
70-225
400
LPJ, JJN
TJD
250-400
SFH, SFL
70-250
SED, SEH, SEL
15-150
600
SGD, SGH, SGL
125-600
KRP-C
2000
Line Side
Fuse
Poles
1
1, 2, 3
2, 3
2, 3
1
2
2, 3
2, 3
1, 2, 3
1, 2
1, 2, 3
2, 3
3
2, 3
2
3
2, 3
2, 3
2, 3
2, 3
1, 2
2, 3
2, 3
2, 3
1, 2
2, 3
2, 3
2, 3
2, 3
2, 3
(2) THQL 1 pole rating is 70 amperes maximum. Maximum system voltage is 120/240VAC.
THQL 2 pole 110-125A ratings are also series rated on 120/240VAC maximum services.
ALC / AQC Panelboard
Maximum
Maximum
System Voltage SCCR
42kA
65kA
100kA
240 Vac
200kA
(See Notes on Page 4)
Max Fuse
Load Side
Current Rating Circuit Breaker
Amps
THQL-GF
15-30
JJN
600
THQL
15-100 (2)
THHQL
15-70
JJN
600
THHQL
15-125
TFJ
70-225
JJN, LPJ, LPN-RK
600
TFJ
70-225
KRP-C
3000
THQL
15-100 (2)
LPN-RK
200
THQP
15-50
JJN
200
THQL
15-100 (2)
400
TQD
125-225
THHQL, THHQB
40-100
LPJ, JJN
TFJ
70-225
600
TQD
100-225
TQD
125-225
TFJ
70-225
KRP-C
1200
SFH
70-250
THQL
15-100 (2)
TFJ
70-200
LPN-RK
200
SFH, SFL
70-250
SED, SEH, SEL
15-150
THQL
15-100 (2)
400
TFJ
70-225
LPJ, JJN
SFH, SFL
70-250
SED, SEH, SEL
15-150
600
Line Side
Fuse
Poles
1
1, 2, 3
1
2
2, 3
2, 3
1, 2, 3
1, 2
1, 2, 3
2, 3
3
2, 3
2
3
2, 3
2, 3
1, 2
2, 3
2, 3
2, 3
1, 2
2, 3
2, 3
2, 3
(2) THQL 1 pole rating is 70 amperes maximum. Maximum system voltage is 120/240VAC.
THQL 2 pole 110-125A ratings are also series rated on 120/240VAC maximum services.
© 2000 Cooper Bussmann, Inc.
Page 2 of 4
10/3/00
GE Series Rating Chart
AE / AD PANELBOARD
Maximum
Maximum
System Voltage SCCR
Line Side
Fuse
LPS-RK
277Vac
100kA
LPJ, JJS
65kA
LPJ
LPS-RK
480 Vac
100kA
LPJ, JJS
JJS
KRP-C
AEC PANELBOARD
Maximum
Maximum
System Voltage SCCR
Line Side
Fuse
LPS-RK
277Vac
100kA
LPJ, JJS
65kA
LPJ
LPS-RK
480 Vac
100kA
LPJ, JJS
© 2000 Cooper Bussmann, Inc.
(See Notes on Page 4)
Max Fuse
Load Side
Current Rating Circuit Breaker
Amps
TED
15-50
100
THED
15-30
TEY
15-100
SED, SEH, SEL
15-150
200
TEY
15-100
TED
15-50
TED
15-50
400
THED
15-30
SED, SEH, SEL
15-150
TEY
15-100
600
SED, SEH, SEL
15-150
TED, THED
15-150
600
TED, THED6
15-100
100
TEY
15-100
200
SED, SEH, SEL
15-150
TED
15-50
TED, THED6
15-100
TFJ
70-225
400
TJJ
125-400
SFH, SFL
70-250
SGH, SGL
125-600
TEY
15-100
600
SED, SEH, SEL
15-150
SKH, SKL
300-1200
800
TJJ
125-400
1200
SKH, SKL
300-1200
2000
SGH, SGL
125-600
Poles
1
1
1
2, 3
1
1
1
1
2, 3
1
2, 3
2, 3
2, 3
2, 3
2, 3
1
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
(See Notes on Page 4)
Max Fuse
Load Side
Current Rating Circuit Breaker
Amps
TED
15-50
100
TEY
15-100
SED, SEH, SEL
15-150
200
TEY
15-100
TED
15-50
TED
15-50
400
SED, SEH, SEL
15-150
TEY
15-100
600
SED, SEH, SEL
15-150
TED
15-150
600
TED
15-100
100
TEY
15-100
200
SED, SEH, SEL
15-150
TED
15-50
TED
15-100
TFJ
70-225
400
SFH, SFL
70-250
SGH, SGL
125-600
TEY
15-100
600
SED, SEH, SEL
15-150
Poles
1
1
2, 3
1
1
1
2, 3
1
2, 3
2, 3
2, 3
2, 3
2, 3
1
2, 3
2, 3
2, 3
2, 3
2, 3
2, 3
Page 3 of 4
10/3/00
GE Series Rating Chart
Note: The following circuit breakers may be substituted for the circuit breakers shown in the series rating
tabulations. Devices with MicroVersaTrip Plus and PM trip units may also be substituted, provided the short
circuit rating is equal to or greater than series connected rating. Ref. GE publication DET-008A.
Breaker
Substitute Breaker(s)
THQL
THHQL
THQL-GF
TED
SED
SEH
SEL
TQD
TFJ
SFH
SFL
TJJ
THJK
SGD
SGH
SGL
SKH
SKL
TPV
THPV
THQB, THQC, THQE, THHQL, THHQB, THHQC
THHQB, THHQC
THQB-GF, THQC-GF
THED
SEH, SEL, SEP
SEL, SEP
SEP
THQD
TFK, THFK
SFL, SFP
SFP
TJK, THJK, TJ4V, THJ4V, THJ9V, TJH
THJ4V, THJ9V, TJH, TJL
SGH, SGL, SGP
SGL, SGP
SGP
SKL, SKP
SKP
SS, SH, TP, TC, TCV, THP, THC, THCV
SH, THP, THC, THCV
NOTE 1: The data in these charts was compiled from information in GE Electrical
Distribution & Control publication, catalog reference number GEP-1100P and GE
Electrical Distribution & Control publication - UL Component Recognized Series
Ratings, publication reference number DET-008A. Cooper Bussmann assumes no
responsibility for the accuracy or reliability of the information. The information contained
in the tables may change without notice due to equipment design modifications.
NOTE 2: The line-side fused switch may be in a separate enclosure or in the same enclosure as the loadside circuit breaker. A line-side fused switch may be integral or remote.
NOTE 3: Max fuse current rating denotes the largest amperage fuse that may be used for that series rated
combination. A lower amperage fuse may be substituted for the listed fuse.
© 2000 Cooper Bussmann, Inc.