1000V (IEC/U.L.) 315-1400A

Bussmann®
Square Body – DIN 43 653
1000V (IEC/U.L.)
Size
3
Rated
Voltage
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
900
315-1400A
Electrical Characteristics
I2t (A2s)
Rated
Clearing
Current
at Rated
RMS-Amps
Pre-arc
Voltage
315
350
400
450
500
550
630
700
800
900
1000
1100
1250
1400
9200
13000
19000
27000
37500
52000
82500
115000
170000
250000
340000
460000
575000
795000
54500
77500
115000
160000
225000
310000
490000
700000
1050000
1500000
2050000
2750000
3400000
4200000
R
®
Ordering Information
Watts
Loss
-KN/110
Type K
Indicator for
Micro
-TN/110
Type T
Indicator for
Micro
90
95
105
107
110
115
120
125
135
145
150
155
175
185
170M8614
170M8615
170M8616
170M8617
170M8618
170M8619
170M8620
170M8621
170M8622
170M8623
170M8624
170M8625
170M8626
170M8627
170M8629
170M8630
170M8631
170M8632
170M8633
170M8634
170M8635
170M8636
170M8637
170M8638
170M8639
170M8640
170M8641
170M8642
Curves
Carton
Qty.
Carton
Weight
(kg)
See Page
or
(Datasheet)
1
1.5
Page 76
or
(720061)
1 kg = 2.2 lbs. 1 lb = 0.45 kg
I Interrupting rating 150kA (Estimated 300kA) RMS Symmetrical.
I Watts loss provided at rated current.
I Microswitch ordered separately.
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition
uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications.
Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the
right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible
applications.
2-25-02
SB01407
Form No. 170M
Page 1 of 4
BIF Doc #720061
Bussmann®
Square Body – DIN 43 653
1000V (IEC/U.L.)
315-1400A
R
®
Electrical Characteristics
Total clearing I2t
Arc Voltage
Power Losses
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
This curve gives the peak arc voltage,
UL, which may appear across the fuse during its operation as a function of the
applied working voltage Eg, (RMS) at a
power factor of 15%.
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor, Kp,
is given as a function of the RMS load
current, Ib, in % of the rated current.
*Rated voltage 900V
1,5
3
UL
2,5
2
1,8
1,6
1,4
1,2
103
K
*
1,0
0,5
0,8
0,7
0,6
0,5
0,3
0,3
0,2
0,15
4
0,2
Eg
600
700
800
900
Eg
3
1000
Kp
0,4
8
7
6
5
0,4
500
1,0
500
600
700
800
900
1000
0,1
30
Ib
40
50
60
70
80
90 100%
Dimensions
DIN 43 653 Type –KN/110 and –TN/110
Size
1*KN/110
1KN/110
2KN/110
3KN/110
A
80
80
80
81
C Max D1
108
61
108
69
108
77
108
92
E
43
51
59
74
G
6
6
6
6
H
22
25
25
30
I
11
11
11
11
Size
A
B
C Max D2
1*TN/110
80
138 108
61
1TN/110
80
138 108
69
2TN/110
80
138 108
75
3TN/110
81
139 108
90
Dimensions in mm
1 mm = 0.0394”
1” = 25.4 mm
E
43
51
59
74
G
6
6
6
6
H
22
25
25
30
I
11
11
11
11
KN/110
2-25-02
B
138
138
138
139
TN/110
SB01407
Form No. 170M
Page 2 of 4
BIF Doc #720061
BIF Document
Semiconductor Fuse
315-1400A, 1000 Volts
720061
104
The partial dotted curves
are for fuses designed to
give part range protection
(aR protection). Loading
or operation above the
curve indicated at A on
the curves must in general be avoided. Please see
technical guidance
170K…
for further information.
Curves that are not dotted
are for fuses designed to
give full range protection.
103
10
1s
*
1400A 1250A
1100A 1000A
900A 800A
700A 630A
550A 500A
450A 400A
350A 315A
Virtual Pre-arcing Time In Seconds
102
10-1
10-2
10-3
10-4
102
103
104
105
Prospective Current In Ampere RMS
Pre-Arcing
Time-Current Characteristic Curves
TYPOWER ZILOX
2-25-02
SB01407
BUSSMANN
P.O. Box 14460
St. Louis, MO 63178-4460
U.S.A.
Phone: 636-394-2877
Fax:
800-544-2570
Int’l Fax: 636-527-1413
Approved:
PK
Rev. Date:
NOV-01
BUSSMANN U.K.
Burton-on-the-Wolds
Leicestershire LE12 5TH
England
Phone: 44-1509-882737
Fax:
44-1509-882786
Page
Pub. Date:
BUSSMANN DENMARK
5 Literbuen
DK-2740 Skovlunde
Copenhagen, Denmark
Phone: 45-4485-0900
Fax:
45-4485-0901
Bussmann reserves the right without notice to change design and/or discontinue distribution of this product.
3 of 4
NOV-01
BIF Document
Semiconductor Fuse
315-1400A, 1000 Volts
720061
3
Size
Peak Let-Through Current In Amperes
105
*11205000AA
A
1400 A
1100
900A
700A
550A
450A
350A
800A
630A
500A
400A
315A
104
103
2x102
102
103
104
105
Amp
106
Prospective Short-Circuit Current symmetrical RMS
Peak Let-Through
Cut-Off Current Characteristic Curves
TYPOWER ZILOX
2-25-02
SB01407
Approved:
PK
Rev. Date:
NOV-01
Page
Pub. Date:
4 of 4
NOV-01
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition
uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann
reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to
change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.