COOPER ECSR125

ECSR
Class RK5 600Vac, 70 to 600A
Dual-Element, Time-Delay Fuses
Dimensions (inches)
Catalog Symbol: ECSR
Dual-Element, Time-Delay – 10 seconds (minimum) at 500%
rated current
Current-Limiting
Volts: 600Vac (or less)
Amps: 65 to 600A
IR: 200kA RMS Sym.
Agency Information: CE, UL. Listed, Std. 248-12, Class
RK5, Guide JDDZ, File E162363 CSA Certified, HRCI-R
C22.2 No. 248.12, Class 1422-01, File 53787
Features
• Provides motor overload, ground fault and short-circuit
protection. When used in circuits subject to surge
currents such as those caused by motors, transformers
and other inductive components, these fuses can be
sized close to full-load Amps to give maximum
overcurrent protection.
• The time-delay feature makes it possible to use fuse
Amp ratings, which are much smaller than those of
non-time-delay fuses. Considerable cost saving occurs
by permitting the use of smaller size switches, panels
and fuses themselves.
• Provides a good degree of short-circuit protection
(greater current-limitation) to help protect downstream
components from high fault currents.
• Gives motor running back-up protection to motors
without extra costs.
• Helps protect motors against burnout from overloads
and single phasing when sized properly.
07-10-07
BU-SB07255
• Simplifies and improves blackout prevention (selective
coordination ratios).
• Dual-element fuses can be applied in circuits subject to
temporary motor overloads and surge currents to
provide both high-performance, short-circuit and
overload protection.
Catalog Numbers (amps)
ECSR70
ECSR110
ECSR75
ECSR125
ECSR80
ECSR150
ECSR90
ECSR175
ECSR100
ECSR200
ECSR225
ECSR250
ECSR300
ECSR350
ECSR400
ECSR450
ECSR500
ECSR600
Carton Quantity and Weight
Carton
Weight per Carton
Amps
Quantity
lbs
kg
65–100
1
0.54
0.24
101–200
1
1.22
0.54
201–400
1
3.00
1.36
401–600
1
5.00
2.27
Class R Fuse Blocks (600V) Catalog Data
(Clip Retaining Spring Standard, Suffix “R”)
Amps
70
to
100
to 200
to 400
to 600
Poles
1
2
3
1
1
1
Terminal Type (Suffix No.)
Basic Box Lug w/
Catalog
—
Reinforced Clip
Number
CU only
R60100-1
CR
COR
R60100-2
CR
COR
R60100-3
CR
COR
R60200-1
CR
—
R60400-1
CR
—
R60600-1
CR
—
Form No. ESCR 70-600
Page 1 of 2
Data Sheet #1318
ECSR
Class RK5 600Vac, 70 to 600A
Dual-Element, Time-Delay Fuses
Current Limitation Curves
Time-Current Characteristic Curves– Average
Melt
Current-Limiting Effects
ECSR Apparent RMS Symmetrical Let-Through Current
Prosp.
SCC
30A
60A 100A
200A 400A
600A
5000
1400 2000 2900
3950
5000
5000
10,000
1850 2650 3600
5100
8550 10,000
15,000
2200 3200 4100
5950
9750 13,700
20,000
2450 3550 4500
6600 10,700 15,000
25,000
2700 3900 4850
7150 11,500 16,100
30,000
2900 4280 5150
7650 12,200 17,050
35,000
3100 4400 5400
8100 12,800 17,900
40,000
3300 4760 5600
8500 13,400 18,700
50,000
3550 5150 6050
9250 14,400 20,050
60,000
3800 5500 6400
9850 15,250 21,250
80,000
4300 6100 7000 10,950 16,750 23,300
100,000
4500 6600 7550 11,900 18,000 25,000
150,000
5200 8000 8600 13,800 20,550 28,450
200,000
5800 8500 9400 15,350 22,550 31,200
Fuse Reducers For Class R Fuses
Equipment
Desired Fuse
Catalog Number
Fuse Clips
(Case) Size
(Pairs) 600V
200A
100A
No. 2621-R
400A
100A
No. 2641-R
200A
No. 642-R
100A
No. 2661-R
600A
200A
No. 2662-R
400A
No. 2664-R*
*Single reducer only (pair not required).
The only controlled copy of this document is the electronic read-only version maintained by Cooper Bussmann. All other copies of this document are by definition uncontrolled. This bulletin
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without
notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
07-10-07
BU-SB07255
Form No. ESCR 70-600
Page 2 of 2
Data Sheet #1318