Motor Circuit Protection Tables NEC® Article 430 and Tables Explanation Columns 1 & 2 Motor horsepower ratings are listed in Column 1. Full load amps from Tables 430.247 through 430.250 are provided in Column 2. Column 3 Various fuse types are listed in Column 3. The LPJ_SP is a 600Vac, 0 - 600 amp, time-delay, Class J, “Low-Peak fuse, with a 300,000 amp interrupting rating. The TCF is a 600Vac, 1 - 100 amp dual-element, time-delay, IP-20 finger-safe fuse with Class J performance. The LP-CC is a 600Vac, 0 - 30 amp, time-delay, Class CC, Low-Peak fuse with a 200,000 amp interrupting rating. The LPS-RK_SP and LPNRK_SP are 600 and 250Vac, 0 - 600 amp, time-delay, Class RK1, Low-Peak fuses with interrupting ratings of 300,000 amps. FRS-R and FRN-R are 600 and 250Vac, 0 - 600 amp, time-delay, Class RK5, Fusetron Dual-Element fuses with interrupting ratings of 200,000 amps. The KRP-C_SP is a 600Vac, 601 - 6000 amp, time-delay, Class L, Low-Peak fuse, with a 300,000 amp AC interrupting rating. The DC listed ratings for these fuses are: LPJ TCF LP-CC LP-CC LP-CC 1 to 600SP 1 to 100 1 ⁄2 to 2 8⁄10 3 to 15 20 to 30 300Vdc 300Vdc 300Vdc 150Vdc 300Vdc LPN-RK LPN-RK LPS-RK FRN-R FRS-R 0 to 60SP 70 to 600SP 0 to 600SP 0 to 600 0 to 600 125Vdc 250Vdc 300Vdc 125Vdc 300Vdc Column 4 - Optimal Branch Circuit Protection There are two distinct levels of protection philosophy provided in this Column. LPSRK_SP, LPN-RK_SP, FRS-R and FRN-R fuses are sized for motor running “back-up” protection and provide superb short circuit protection at the same time. LPJ_SP, TCF, and LP-CC fuses are sized a little larger but are even more current limiting, providing an even greater degree of short circuit protection for the motor circuit. All the fuses selected from this column provide short circuit and ground-fault protection for motor branch circuits (430.52), but typically are not the maximum allowed. Fuses sized in accordance with Column 4 must be used in conjunction with properly sized motor overload protection such as overload relays or solid state motor controllers (430.32). This fuse sizing is normally large enough to allow the overload protective device to operate on overloads without opening the fuse. Yet for many cases, this fuse amp rating selection is smaller than the maximums allowed per Columns 5 or 6 (430.52). In some cases, this smaller amp rating selection may provide the benefits of a smaller size disconnect and better short circuit protection. If a motor has a long starting time, high starting current profile or is cycled frequently, it may be necessary to use Column 5 or 6. The LPS-RK_SP, LPN-RK_SP, FRS-R and FRN-R fuses sized per this column provide short circuit and ground-fault protection for motor branch circuits (430.52) as discussed in the previous paragraph. In addition, these dual-element fuses exhibit longer time-delay characteristics and can therefore be sized to provide back-up motor overload protection. The fuse sizing in Column 4 for LPS-RK_SP, LPNRK_SP, FRS-R and FRN-R fuses provides a degree of motor and circuit overload protection to back-up the normal motor overload protective device. Note: This level of protection requires a well-designed, true dual-element fuse. The Fusetron Fuses, FRS-R and FRN-R, and Low-Peak Fuses, LPS-RK_SP and LPN-RK_SP, are the industry leading dual-element fuses with excellent over-load time-delay characteristics and current-limiting short circuit ability. The Low-Peak Dual-Element Fuses have better current-limiting ability than Fusetron Dual-Element Fuses. The amp ratings in Column 4 are determined by using Column 2 motor ampacity values and the following: LPJ_SP & TCF: 150% or the next larger Cooper Bussmann amp rating if 150% does not correspond to a Cooper Bussmann fuse amp rating. LP-CC 1⁄2 to 15A: 200% (150% for DC) or the next larger Cooper Bussmann size if 200% (150% for DC) does not correspond to a Cooper Bussmann fuse amp rating. ©2005 Cooper Bussmann LP-CC 20 to 30A: 300% (150% for DC) or the next larger Cooper Bussmann size if 300% (150% for DC) does not correspond to a Cooper Bussmann fuse amp rating. LPS-RK_SP and LPN-RK_SP: 130% or the next larger Cooper Bussmann amp rating if 130% does not correspond to a Cooper Bussmann fuse amp rating. FRS-R and FRN-R: 125% or the next larger Cooper Bussmann amp rating if 125% does not correspond to a Cooper Bussmann fuse amp rating. Column 5 - Branch Circuit Protection, Max. General Applications Fuses selected from this column are intended to provide short circuit and groundfault protection for motor branch circuits. Fuses sized in accordance with Column 5 must be used in conjunction with properly sized motor overload protection such as overload relays or solid state motor controllers (430.32). Column 5 fuse sizing provides the maximum NEC® Table 430.52 amp ratings for general purpose applications. It takes into account 430.52(C)(1) Exception No. 1, which allows the next standard amp rating fuse (per standard fuse amp ratings in 240.6) to be used if the maximum percentage in Table 430.52 does not correspond to a standard fuse amp rating. If this Column 5 fuse sizing does not allow the motor to start, then Column 6 may provide a larger amp rating. The amp ratings in Column 5 are deter-mined by using Column 2 motor ampacity values and the following: LPJ_SP, TCF, LPS-RK_SP, LPN-RK_SP, FRS-R, FRN-R and KRP-C_SP: 175% (150% for DC motors) or the next larger 240.6 standard fuse amp rating if 175% (150% for DC motors) does not correspond to a standard fuse amp rating. LP-CC: 300% (150% for DC motors) or the next larger 240.6 standard fuse amp rating if 300% (150% for DC motors) does not correspond to a standard fuse amp rating. Sizes shown for the LP-CC can also be used for non-time delay fuses such as JKS, KTN-R, KTS-R, JJN, JJS, and KTK-R. Column 6 - Branch Circuit Protection, Max. Heavy Start When the amp rating shown in Column 5 is not sufficient to start a motor, a larger amp rating is often available by utilizing 430.52(C)(1) Exception No. 2. The amp ratings in Column 6 are the larger of the amp rating allowed by 430.52(C)(1) Exception No. 1, or 430.52(C)(1) Exception No. 2. These amp ratings will often be required when acceleration times are greater than 5 seconds, when plugging or jogging applications exist, or where there are high inrush currents (such as Design E or energy efficient Design B motors). (In a few cases, the amp rating in Column 6 may be smaller than the maximum permitted due to the limitation of the fuse type, such as LP-CC, Class CC fuses that are only available in ratings up to 30 amps. In these cases, if the amp rating shown is not sufficient to start the motor, select a different family of fuses that meet the requirements.) The amp ratings in Column 6 are determined by using Column 2 motor ampacity values and the following: LPJ_SP, TCF, LPS-RK_SP, LPN-RK_SP, FRS-R, and FRN-R: 225% or the next smaller Cooper Bussmann amp rating if 225% does not correspond to a Cooper Bussmann fuse amp rating. LP-CC: 400% or the next smaller Cooper Bussmann amp rating if 400% does not correspond to a Cooper Bussmann fuse amp rating. KRP-C_SP: 300% or the next smaller Cooper Bussmann amp rating, if 300% does not correspond to a Cooper Bussmann amp rating. Sizes shown for the LP-CC can also be used for non-time delay fuses such as JKS, KTN-R, KTS-R, JJN, JJS, AND KTK-R. Column 7 Horsepower-rated switch sizes given in Column 7 are based on 115% (430.110) of Column 2. Switch sizes need to be increased when, because of starting requirements, the fuses are sized above the rating of the switch shown in this column. Column 8 Sizes listed are for general-purpose magnetic controllers (single speed, fullvolt-age for limited plugging and jogging-duty) as shown in NEMA Standards Publication ICS-2-2000. 145 Motor Circuit Protection Tables NEC® Article 430 and Tables Explanation Column 9 Column 10 Copper wire sizes are based upon 125% (430.22) of values shown in Column 2 and ampacities listed in Table 310.16 for 75°C terminals. Although the NEC® allows 60°C terminations for equipment rated 100 amp or less, most equipment terminations have been rated for 75°C conductors. If equipment terminations are rated for 60°C conductors only, the 60°C ampacities must be utilized and therefore larger conductor sizes may be required than those shown in this column. See 110.14(C) (1)(a)(4). These rigid metallic conduit sizes are based upon copper conductors with THWN or THHN insulation, Table C8 of Annex C, and 75°C equipment terminals. 200Vac Three-Phase Motors & Circuits 1 Motor Size Table 430.250 HP 2 Motor FLA Table 430.250 AMPS ⁄2 2.5 3 ⁄4 3.7 1 4.8 1 1⁄2 6.9 2 7.8 3 11 5 17.5 7 1⁄2 25.3 10 32.2 15 48.3 20 62.1 1 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 AMPS1 4 6 5 3 1⁄2 3 2⁄10 5 6⁄10 6 7 1⁄2 5 5 8 10 10 6 1⁄4 6 12 15 15 9 9 12 15 25 12 10 17 1⁄2 17 1⁄2 25 15 15 30 30 25 25 40 40 35 35 50 50 45 45 80 80 70 70 100 100 90 80 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 6 6 10 6 6 10 10 15 10 10 10 10 15 10 10 15 15 25 15 15 15 15 25 15 15 20 20 – 20 20 35 35 35 35 45 45 45 45 60 60 60 60 90 90 90 90 110 – 110 110 Conduit sizes are for three conductors per circuit for three phase motors and two conductors per circuit for single phase and DC motors. Conduit sizes may need to be increased if equipment grounding conductors or neutrals are also installed in the conduit. If equipment terminations are rated for 60°C conductors only, the 60°C ampacities must be utilized and therefore larger conductor sizes and conduit sizes may be required. Conductors operated in a high ambient temperature may need to be derated. (See correction factor table at the bottom of Table 310.16.) 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 6 6 10 6 6 10 10 15 10 10 10 10 15 10 10 15 15 25 15 15 17 1⁄2 17 1⁄2 30 17 1⁄2 17 1⁄2 20 20 – 20 20 35 35 35 35 50 50 50 50 70 – 70 70 100 100 100 100 125 – 125 125 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 00 14 1 30 00 14 1 30 00 14 1 30 00 14 1 30 0 14 1 30 0 14 1 30* 1 12 1 60 1 10** 1 60* 2 8** 1 100 3 6** 3 100* 3 4** ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2** ⁄2** ⁄4** 1 * Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. ƒ Class J performance, special finger-safe dimensions. 146 ©2005 Cooper Bussmann Motor Circuit Protection Tables 200Vac Three-Phase Motors & Circuits continued 1 Motor Size Table 430.250 HP 2 Motor FLA Table 430.250 AMPS 25 78.2 30 92 40 120 50 150 60 177 75 221 100 285 125 359 150 414 200 552 * 1 ** 2 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R KRP-C_SP LPJ_SP LPN-RK_SP FRN-R KRP-C_SP LPJ_SP LPN-RK_SP FRN-R KRP-C_SP LPN-RK_SP FRN-R KRP-C_SP KRP-C_SP J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 L J RK1 RK5 L J RK1 RK5 L RK1 RK5 L L AMPS 1 125 110 100 150 125 125 200 175 150 225 200 200 300 250 225 350 300 300 – 450 400 400 – 600 500 450 – 600 600 – – 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS 1 150 150 150 175 175 175 225 225 225 300 300 300 350 350 350 400 400 400 – 500 500 500 – – – – 700 – – 800 1000 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS 1 175 175 175 200 200 200 250 250 250 300 300 300 350 350 350 450 450 450 650 600 600 600 800 – – – 1000 – – 1200 1600 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 100* 3 3** 1** 200 4 2** 1** 200* 4 1/0 1 1⁄4 200* 5 3/0 1 1⁄2 400 5 4/0 2 400* 5 300 2 400* 6 500 3 600* 6 4/0 2/PHASE (2)2 600* 6 300 2/PHASE (2)2 1200 72 500 2/PHASE (2)3 Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. These sizes are typical. They are not shown in NEMA ICS 2-2000. 208Vac Three-Phase Motors & Circuits 1 Motor Size Table 430.250 HP 2 Motor FLA Table 430.250 AMPS ⁄2 2.4 3 ⁄4 3.5 1 4.6 1 1⁄2 6.6 1 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 AMPS1 4 6 5 3 1⁄2 3 5 6⁄10 6 7 5 4 1⁄2 7 10 10 6 6 10 10 15 9 9 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 6 6 10 6 6 10 10 15 10 10 10 10 15 10 10 15 15 20 15 15 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 6 6 10 6 6 10 10 15 10 10 10 10 15 10 10 15 15 25 15 15 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 00 14 1 30 00 14 1 30 00 14 1 30 00 14 1 ⁄2 ⁄2 ⁄2 ⁄2 *Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. **If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000. ƒ Class J performance, special finger-safe dimensions. ©2005 Cooper Bussmann 147 Motor Circuit Protection Tables 208Vac Three-Phase Motors & Circuits continued 1 Motor Size Table 430.250 HP 2 Motor FLA Table 430.250 AMPS 2 7.5 3 10.6 5 16.7 7 1⁄2 24.2 10 30.8 15 46.2 20 59.4 25 74.8 30 88 40 114 50 143 60 169 75 211 100 273 125 343 150 396 200 528 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R KRP-C_SP LPJ_SP LPN-RK_SP FRN-R KRP-C_SP LPJ_SP LPN-RK_SP FRN-R KRP-C_SP LPJ_SP LPN-RK_SP FRN-R KRP-C_SP KRP-C_SP J Jƒ CC RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 L J RK1 RK5 L J RK1 RK5 L J RK1 RK5 L L AMPS1 12 15 15 10 10 17 1⁄2 17 1⁄2 15 15 30 30 25 25 40 40 35 35 50 50 45 40 70 70 70 60 90 90 80 80 125 100 100 150 125 110 175 150 150 225 200 200 300 225 225 350 300 300 – 450 400 350 – 600 450 450 – 600 600 500 – – 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 15 15 25 15 15 20 20 20 20 30 30 30 30 45 45 45 45 60 60 60 60 90 90 90 90 110 – 110 110 150 150 150 175 175 175 200 200 200 300 300 300 300 300 300 400 400 400 – 500 500 500 – – – – 601 – – – 700 1000 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 15 15 30 15 15 20 20 20 20 35 35 35 35 50 50 50 50 60 60 60 60 100 100 100 100 125 – 125 125 150 150 150 175 175 175 250 250 250 300 300 300 350 350 350 450 450 450 601 600 600 600 800 – – – 1000 – – – 1100 1500 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 0 14 1 30 0 14 1 30* 1 12 1 60 1 10** 1 60 2 8 1 60* 3 6** 3 100* 3 4** 1 100* 3 3** 1** 200 4 2** 1** 200* 4 1/0 1 1⁄4 200* 5 3/0 1 1⁄2 400 5 4/0 2 400* 5 300 2 400* 6 500 3 600* 6 4/0 2/PHASE (2)2 600* 6 250 2/PHASE (2)2 1200* 7 400 2/PHASE (2)2-2 1⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2** ⁄4** *Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. **If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000. ƒ Class J performance, special finger-safe dimensions. 148 ©2005 Cooper Bussmann Motor Circuit Protection Tables 230Vac Three-Phase Motors & Circuits (220-240Vac Systems) 1 Motor Size Table 430.250 HP 2 Motor FLA Table 430.250 AMPS ⁄2 2.2 3 ⁄4 3.2 1 4.2 1 1 1⁄2 6 2 6.8 3 9.6 5 15.2 7 1⁄2 22 10 28 15 42 20 54 25 68 30 80 40 104 50 130 60 154 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 AMPS1 3 1⁄2 6 4 1⁄2 3 2 8/10 5 6 7 4 1⁄2 4 7 10 9 5 6⁄10 5 8⁄10 9 10 12 8 7 1⁄2 12 15 15 9 9 15 15 30 15 12 25 25 20 20 35 34 30 30 45 45 40 35 70 70 60 60 90 90 80 70 110 90 90 125 110 100 175 150 150 200 175 175 250 225 200 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 6 6 10 6 6 6 6 10 6 6 10 10 15 10 10 15 15 20 15 15 15 15 25 15 15 20 20 30 20 20 30 30 30 30 40 40 40 40 50 50 50 50 80 80 80 80 100 100 100 100 125 125 125 150 150 150 200 200 200 250 250 250 300 300 300 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 6 6 10 6 6 7 6 12 7 7 10 10 15 10 10 15 15 20 15 15 15 15 25 15 15 20 20 30 20 20 30 30 30 30 45 45 45 45 60 60 60 60 90 90 90 90 110 – 110 110 150 150 150 175 175 175 225 225 225 250 250 250 300 300 300 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 00 14 1 30 00 14 1 30 00 14 1 30 00 14 1 30 0 14 1 30 0 14 1 30 1 14 1 30* 1 10 1 60 2 10** 1 60* 2 6 3 100* 3 4 1 100* 3 4** 1 100* 3 3** 1** 200* 4 1** 1 1⁄4** 200* 4 2/0 1 1⁄2 200* 5 3/0 1 1⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄4 *Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. **If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000. ƒ Class J performance, special finger-safe dimensions. 4 Limited by 600 amp being the largest amp rating for FRN-R and LPN-RK_SP. ©2005 Cooper Bussmann 149 Motor Circuit Protection Tables 230Vac Three-Phase Motors & Circuits (220-240Vac Systems) continued 1 Motor Size Table 430.250 HP 2 Motor FLA Table 430.250 AMPS 75 192 100 248 125 312 150 360 200 480 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R KRP-C_SP LPJ_SP LPN-RK_SP FRN-R KRP-C_SP LPJ_SP LPN-RK_SP FRN-R KRP-C_SP FRN-R KRP-C_SP J RK1 RK5 J RK1 RK5 L J RK1 RK5 L J RK1 RK5 L RK5 L AMPS1 300 250 250 400 350 350 – 500 450 400 – 600 500 450 – 600 – 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 350 350 350 450 450 450 – 600 600 600 — – 6004 6004 700 – 1000 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 400 400 400 500 500 500 700 – – – 900 – – – 1000 – 1400 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 400 5 250 2 400* 5 350 2 1⁄2 400* 6 3/0 2/PHASE (2) 1 1⁄2 600* 6 4/0 2/PHASE (2) 2 600* 6 350 2/PHASE (2) 2-2 1⁄2 *Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. **If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000. 4 Limited by 600 amp being the largest amp rating for FRN-R and LPN-RK_SP. 460Vac Three-Phase Motors & Circuits (440-480Vac Systems) 1 Motor Size Table 430.250 HP 2 Motor FLA Table 430.250 AMPS ⁄2 1.1 3 ⁄4 1.6 1 2.1 1 1 1⁄2 3 2 3.4 3 4.8 5 7.6 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 AMPS1 1 8⁄10 3 2 1⁄4 1 11⁄2 1 4⁄10 2 1⁄2 3 3 2⁄10 2 1⁄4 2 3 2⁄10 6 4 1⁄2 2 8⁄10 2 8⁄10 4 1⁄2 6 6 4 4 5 6⁄10 6 71 4 1⁄2 4 1⁄2 8 10 10 6 1⁄4 6 12 15 25 10 10 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 3 3 6 3 3 3 3 6 3 3 6 6 10 6 6 6 6 10 6 6 6 6 5 6 6 10 10 15 10 10 15 15 25 15 15 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 3 3 6 3 3 3 1⁄2 3 6 1⁄4 3 1⁄2 3 1⁄2 6 6 10 6 6 6 6 12 6 1⁄4 6 1⁄4 7 6 15 7 7 1⁄2 10 10 15 10 10 15 15 30 15 15 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 00 14 1 30 00 14 1 30 00 14 1 30 00 14 1 30 00 14 1 30 0 14 1 30 0 14 1 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 * Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. ƒ Class J performance, special finger-safe dimensions. 150 ©2005 Cooper Bussmann Motor Circuit Protection Tables 460Vac Three-Phase Motors & Circuits (440-480Vac Systems) continued 1 Motor Size Table 430.250 HP 2 Motor FLA Table 430.250 AMPS 1 7 ⁄2 11 10 14 15 21 20 27 25 34 30 40 40 52 50 65 60 77 75 96 100 124 125 156 150 180 200 240 250 302 300 361 350 414 400 477 450 500 515 590 * 1 ** 4 ƒ 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R KRP-C_SP LPJ_SP LPS-RK_SP FRS-R KRP-C_SP LPJ_SP LPS-RK_SP FRS-R KRP-C_SP LPS-RK_SP FRS-R KRP-C_SP KRP-C_SP FRS-R KRP-C_SP KRP-C_SP J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 L J RK1 RK5 L J RK1 RK5 L RK1 RK5 L L RK5 L L AMPS1 17 1⁄2 17 1⁄2 15 15 25 25 20 17 1⁄2 35 35 30 30 45 45 40 35 60 60 45 45 60 60 60 50 80 80 70 70 100 100 90 90 125 110 100 150 125 125 200 175 175 250 225 200 300 250 225 400 350 300 – 500 400 400 – 600 500 500 – 600 600 – – 600 – – 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 20 20 20 20 25 25 25 25 40 40 40 40 50 50 50 50 60 60 60 60 70 70 70 70 100 100 100 100 125 – 125 125 150 150 150 175 175 175 225 225 225 300 300 300 350 350 350 450 450 450 – 600 600 600 – – 6004 6004 700 – – 800 1000 – 1000 1200 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 20 20 20 20 30 30 30 30 45 45 45 45 60 60 60 60 70 70 70 70 90 90 90 90 110 – 110 110 125 – 125 125 150 150 150 200 200 200 250 250 250 350 350 350 400 400 400 500 500 500 700 – – – 900 – – – 1000 – – 1200 1400 – 1500 1600 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 1 14 1 30 1 14 1 30* 2 10 1 60 2 10** 1 60* 2 8** 1 60* 3 8** 1 100* 3 6** 3 100* 3 4** 1 100* 4 3** 1** 200 4 1** 1 1⁄4** 200* 4 2/0 1 1⁄2 200* 5 3/0 1 1⁄2 400 5 4/0 2 400* 5 350 2 1⁄2 400* 6 3/0 2/PHASE (2) 1 1⁄2 600* 6 4/0 2/PHASE (2) 2 600* 6 300 2/PHASE (2) 2 600* 6 350 2/PHASE (2 )2 1⁄2 1200* 1200* 7 7 400 2/PHASE 500 2/PHASE (2) 2 1⁄2 (2) 3 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2** ⁄2** ⁄4** Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. Limited by 600 amp being the largest amp rating for FRS-R and LPS-RK_SP. Class J performance, special finger-safe dimensions. ©2005 Cooper Bussmann 151 Motor Circuit Protection Tables 575Vac Three-Phase Motors & Circuits (550-600Vac Systems) 1 Motor Size Table 430.250 HP 2 Motor FLA Table 430.250 AMPS ⁄2 0.9 3 ⁄4 1.3 1 1.7 1 1⁄2 2.4 2 2.7 3 3.9 5 6.1 1 7 1⁄2 9 10 11 15 17 20 22 25 27 30 32 40 41 50 52 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 AMPS1 1 4⁄10 3 1 8⁄10 1 1⁄4 1 1⁄8 2 3 2 8⁄10 1 8⁄10 1 8⁄10 2 8⁄10 3 3 1⁄2 2 1⁄4 2 1⁄4 4 6 5 3 2⁄10 3 4 1⁄2 6 5 6⁄10 4 3 1⁄2 6 6 5 5 6⁄10 5 10 10 15 8 8 15 15 30 12 12 17 1⁄2 17 1⁄2 15 15 30 30 25 25 35 35 30 30 45 45 40 35 50 50 45 40 70 70 60 60 80 80 70 70 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 3 3 3 3 3 3 3 6 3 3 3 3 6 3 3 6 6 10 6 6 6 6 10 6 6 10 10 15 10 10 15 15 20 15 15 20 20 30 20 20 20 20 20 20 30 30 30 30 40 40 40 40 50 50 50 50 60 60 60 60 80 80 80 80 100 100 100 100 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 3 3 3 1⁄2 3 3 3 3 6 3 3 3 1⁄2 3 6 1⁄4 3 1⁄2 3 1⁄2 6 6 10 6 6 6 6 10 6 6 10 10 15 10 10 15 15 20 15 15 20 20 30 20 20 20 20 20 20 35 35 35 35 45 45 45 45 60 60 60 60 70 70 70 70 90 90 90 90 110 – 110 110 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 0 14 1 30 0 14 1 30 0 14 1 30 0 14 1 30 0 14 1 30 0 14 1 30 0 14 1 30 1 14 1 30 1 14 1 30* 2 12 1 30* 2 10 1 60 2 10** 60* 3 8 1 60* 3 6 3 100* 3 6** ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2** 1 ⁄2 ⁄4 ⁄4** 3 *Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. **If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. 2 These sizes are typical. They are not shown in NEMA ICS 2-2000. ƒ Class J performance, special finger-safe dimensions. 152 ©2005 Cooper Bussmann Motor Circuit Protection Tables 575Vac Three-Phase Motors & Circuits (550-600Vac Systems) continued 1 Motor Size Table 430.250 HP 2 Motor FLA Table 430.250 AMPS 60 62 75 77 100 99 125 125 150 144 200 192 250 242 300 289 350 336 400 382 450 412 500 472 * 1 ** 2 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R LPJ_SP LPS-RK_SP FRS-R KRP-C_SP LPJ_SP LPS-RK_SP FRS-R KRP-C_SP LPJ_SP LPS-RK_SP FRS-R KRP-C_SP LPJ_SP LPS-RK_SP FRS-R KRP-C_SP LPS-RK_SP FRS-R KRP-C_SP FRS-R KRP-C_SP J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 L J RK1 RK5 L J RK1 RK5 L J RK1 RK5 L RK1 RK5 L RK5 L AMPS1 100 90 80 125 110 100 150 150 125 200 175 175 225 200 200 300 250 250 400 350 350 – 450 400 400 – 600 450 450 – 600 500 500 – 600 600 – 600 – 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 110 110 110 150 150 150 175 175 175 225 225 225 300 300 300 350 350 350 450 450 450 – 600 600 600 – 600 600 600 601 – – – 700 – – 800 – 1000 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 125 125 125 150 150 150 200 200 200 250 250 250 300 300 300 400 400 400 500 500 500 700 600 600 600 800 – – – 1000 – – – 1100 – – 1200 – 1400 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 100* 4 4** 1 100* 4 3** 1** 200 4 1** 1 1⁄4** 200* 5 2/0 1 1⁄2 200* 5 3/0 1 1⁄2 400 5 250 2 400* 6 350 2 1⁄2 400* 6 500 3 600* 6 4/0 2/PHASE (2) 2 600* 6 250 2/PHASE (2) 2 600* 7 300 2/PHASE (2) 2 600* 7 350 2/PHASE (2) 2 1⁄2 Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. These sizes are typical. They are not shown in NEMA ICS 2-2000. ©2005 Cooper Bussmann 153 Motor Circuit Protection Tables 115Vac Single-Phase Motors & Circuits (110-120Vac Systems) 1 Motor Size Table 430.248 HP 2 Motor FLA Table 430.248 AMPS ⁄6 4.4 ⁄4 5.8 ⁄3 7.2 ⁄2 9.8 3 ⁄4 13.8 1 16 1 1⁄2 20 2 24 3 34 5 56 7 1⁄2 80 10 100 1 1 1 1 * 1 ** 2 ƒ 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J RK1 RK5 J RK1 RK5 AMPS1 8 10 9 6 5 6/10 9 10 12 8 7 1⁄2 12 15 15 10 9 15 15 30 15 15 25 25 20 17 1⁄2 25 25 25 20 30 30 30 25 40 40 35 30 60 60 45 45 90 90 80 70 125 110 100 150 150 125 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 10 10 15 10 10 15 15 20 15 15 15 15 25 15 15 20 20 30 20 20 25 25 25 25 30 30 30 30 35 35 35 35 45 45 45 45 60 60 60 60 100 100 100 100 150 150 150 175 175 175 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 10 10 15 10 10 15 15 20 15 15 15 15 25 15 15 20 20 30 20 20 30 30 30 30 35 35 35 35 45 45 45 45 50 50 50 50 70 70 70 70 125 – 125 125 175 175 175 225 225 225 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 00 14 1 30 00 14 1 30 00 14 1 30 0 14 1 30 0 14 1 30* 0 14 1 30* 1 12 1 30* 1 10 1 60* 2 8** 1 100* 3 4 3 100* 3 3** 1** 200* 42 1 1 1⁄4 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2** ⁄4** Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. These sizes are typical. They are not shown in NEMA ICS 2-2000. Class J performance, special finger-safe dimensions. 154 ©2005 Cooper Bussmann Motor Circuit Protection Tables 230Vac Single-Phase Motors & Circuits (220-240Vac Systems) 1 Motor Size Table 430.248 HP 2 Motor FLA Table 430.248 AMPS ⁄6 2.2 ⁄4 2.9 ⁄3 3.6 ⁄2 4.9 3 ⁄4 6.9 1 8 1 1⁄2 10 2 12 3 17 5 28 7 1⁄2 40 10 50 1 1 1 1 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 AMPS1 3 1⁄2 6 4 1⁄2 3 2 8⁄10 4 1⁄2 6 6 4 4 5 6⁄10 6 7 5 4 1⁄2 8 10 10 8 6 1⁄4 12 15 15 9 9 12 15 25 12 10 15 15 30 15 15 20 20 25 17 1⁄2 15 30 30 25 25 45 45 40 35 60 60 60 50 80 80 70 70 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 6 6 10 6 6 6 6 10 6 6 10 10 15 10 10 10 10 15 10 10 15 15 25 15 15 15 15 25 15 15 20 20 30 20 20 25 25 – 25 25 30 30 30 30 50 50 50 50 70 70 70 70 90 90 90 90 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 6 6 10 6 6 6 6 10 6 1⁄4 6 1⁄4 10 10 15 10 10 10 10 15 10 10 15 15 25 15 15 17 1⁄2 17 1⁄2 30 17 1⁄2 17 1⁄2 20 20 30 20 20 25 25 – 25 25 35 35 35 35 60 60 60 60 90 90 90 90 110 – 110 110 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 00 14 1 30 00 14 1 30 00 14 1 30 00 14 1 30 00 14 1 30 00 14 1 30 0 14 1 30 0 14 1 30* 1 12 1 60 2 10** 1 60* 2 8** 1 100* 3 6** 1 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2** ⁄2** * Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. 1 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. ** If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. ƒ Class J performance, special finger-safe dimensions. ©2005 Cooper Bussmann 155 Motor Circuit Protection Tables 90Vdc3 Motors & Circuits 1 Motor Size Table 430.257 HP 2 Motor FLA Table 430.257 AMPS ⁄4 4.0 ⁄3 5.2 ⁄2 6.8 ⁄4 9.6 1 1 1 3 1 ** 2 3 ƒ 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LPC_CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 AMPS1 6 6 6 6 5 8 10 10 8 7 12 15 15 9 9 15 15 15 15 12 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 6 6 6 6 6 10 10 10 10 10 15 15 15 15 15 15 15 15 15 15 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 6 6 15 9 9 10 10 20 10 10 15 15 25 15 15 20 20 30 20 20 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 1 14 1 30 1 14 1 30 1 14 1 30 1 14 1 ⁄2 ⁄2 ⁄2 ⁄2 Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. These sizes are typical. They are not shown in NEMA ICS 2-2000. All equipment manufacturers should be consulted about DC voltage ratings of their equipment. Class J performance, special finger-safe dimensions. 156 ©2005 Cooper Bussmann Motor Circuit Protection Tables 120Vdc3 Motors & Circuits 1 Motor Size Table 430.257 HP 2 Motor FLA Table 430.257 AMPS ⁄4 3.1 ⁄3 4.1 ⁄2 5.4 3 ⁄4 7.6 1 9.5 1 1⁄2 13.2 1 1 1 2 17 3 25 5 40 7 1⁄2 58 10 76 * 1 ** 2 3 5 ƒ 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LP-CC LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP TCF LPN-RK_SP FRN-R LPJ_SP LPN-RK_SP FRN-R J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J RK1 RK5 AMPS1 5 6 6 4 1⁄2 4 7 10 9 5 6⁄10 5 6⁄10 9 10 10 7 1⁄2 7 12 15 15 10 10 15 15 15 15 12 20 20 20 17 1⁄2 17 1⁄2 30 30 30 25 25 40 40 35 35 60 60 60 50 90 90 80 80 125 100 100 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 6 6 6 6 6 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15 15 15 15 15 20 20 20 20 20 30 30 30 30 30 40 40 40 40 60 60 60 60 90 90 90 90 125 125 125 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 6 6 12 6 1⁄4 6 1⁄4 10 10 15 10 10 12 10 20 12 12 15 15 30 15 15 20 20 305 20 20 25 25 305 25 25 35 35 305 35 35 50 50 50 35 90 60 90 90 125 – 125 125 150 150 150 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 1 14 1 30 1 14 1 30 1 14 1 30 1 14 1 30 1 14 1 30 1 14 1 30* 1 12 1 60 1 10** 1 60* 2 8** 1 100* 3 4** 3 100* 3 3** ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2** ⁄4** 1 Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. Reduced voltage magnetic controller ratings All equipment manufacturers should be consulted about DC voltage ratings of their equipment. Largest LP-CC Fuse 30 amp. With other type fuse, could use larger amp rating in this application. Class J performance, special finger-safe dimensions. ©2005 Cooper Bussmann 157 Motor Circuit Protection Tables 180Vdc3 Motors & Circuits 1 Motor Size Table 430.257 HP 2 Motor FLA Table 430.257 AMPS ⁄4 2.0 ⁄3 2.6 ⁄2 3.4 3 ⁄4 4.8 1 6.1 1 1⁄2 8.3 2 10.8 3 16 5 27 1 1 1 * 1 ** 2 3 ƒ 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ RK1 RK5 AMPS1 3 3 2 8⁄10 2 1⁄2 4 6 3 1⁄2 3 1⁄2 5 6⁄10 6 4 1⁄2 4 1⁄2 8 10 6 1⁄4 6 10 10 8 8 15 15 – 12 12 15 15 20 15 15 25 25 25 20 20 40 40 40 35 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 3 3 3 3 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10 15 15 – 15 15 20 20 20 20 20 25 25 25 25 25 45 45 45 45 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 4 1⁄2 3 4 1⁄2 4 1⁄2 6 6 6 6 6 6 6 1⁄4 7 1⁄2 10 10 10 10 12 10 12 12 17 1⁄2 15 30 17 1⁄2 17 1⁄2 20 20 30 20 20 35 35 30 35 35 60 60 60 60 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 1 14 1 30 1 14 1 30 1 14 1 30 1 14 1 30 1 14 1 30 1 14 1 30 1 14 1 30* 1 14 1 60 2 10** 1 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. These sizes are typical. They are not shown in NEMA ICS 2-2000. All equipment manufacturers should be consulted about DC voltage ratings of their equipment. Class J performance, special finger-safe dimensions. 240Vdc3 Motors & Circuits 1 Motor Size Table 430.257 HP 2 Motor FLA Table 430.257 AMPS ⁄4 1.6 ⁄3 2.0 1 1 * 1 ** 2 3 ƒ 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LPN-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R J Jƒ RK1 RK5 J Jƒ RK1 RK5 AMPS1 2 1⁄2 3 2 1⁄4 2 3 3 2 8⁄10 2 1⁄2 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 3 3 3 3 3 3 3 3 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 3 1⁄2 3 3 1⁄2 3 1⁄2 4 1⁄2 3 4 1⁄2 4 1⁄2 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 1 14 1 30 1 14 1 ⁄2 ⁄2 Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. Reduced voltage magnetic DC controller ratings. All equipment manufacturers should be consulted about DC voltage ratings of their equipment. Class J performance, special finger-safe dimensions. 158 ©2005 Cooper Bussmann Motor Circuit Protection Tables 240Vdc3 Motors & Circuits continued 1 Motor Size Table 430.257 HP 2 Motor FLA Table 430.257 AMPS ⁄2 2.7 3 ⁄4 3.8 1 4.7 1 1⁄2 6.6 2 8.5 3 12.2 5 20 7 1⁄2 29 10 38 15 55 20 72 25 89 30 106 40 140 50 173 60 206 75 255 100 341 1 * 1 ** 2 3 ƒ 3 Fuse 4 Optimal Branch Ckt Protection Type Class LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LP-CC LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPS-RK_SP FRS-R LPJ_SP TCF LPN-RK_SP FRS-R LPJ_SP LPN-RK_SP FRS-R LPJ_SP LPN-RK_SP FRS-R LPJ_SP LPN-RK_SP FRS-R LPJ_SP LPN-RK_SP FRS-R LPJ_SP LPN-RK_SP FRS-R LPJ_SP LPN-RK_SP FRS-R LPJ_SP LPN-RK_SP FRS-R LPJ_SP LPN-RK_SP FRS-R J Jƒ RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ CC RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J Jƒ RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 J RK1 RK5 AMPS1 4 1⁄2 6 4 3 1⁄2 6 6 — 5 5 8 10 6 1⁄4 6 10 10 9 9 15 15 12 12 20 20 20 17 1⁄2 17 1⁄2 30 30 30 30 25 45 45 40 40 60 60 50 50 90 90 80 70 110 100 90 150 125 125 175 150 150 225 200 175 300 225 225 350 300 300 400 350 350 600 450 450 5 NEC® Max for Gen. Applic 430.52(C)(1) Exc. No. 1 AMPS1 6 6 6 6 6 6 — 6 6 10 10 10 10 10 10 10 10 15 15 15 15 20 20 20 20 20 30 30 30 30 30 45 45 45 45 60 60 60 60 90 90 90 90 110 110 110 150 150 150 175 175 175 225 225 225 300 300 300 350 350 350 400 400 400 600 600 600 6 NEC® Max for Heavy Start 430.52(C)(1) Exc. No. 2 AMPS1 6 6 6 6 8 6 15 8 8 10 10 10 10 12 10 12 12 17 1⁄2 15 17 1⁄2 17 1⁄2 25 25 30 25 25 45 45 30 45 45 60 60 60 60 80 60 80 80 110 – 110 110 150 150 150 200 200 200 225 225 225 300 300 300 350 350 350 450 450 450 500 500 500 – – – 7 Minimum Switch Size 430.110 AMPS 8 Minimum NEMA Starter NEMA ICS 22000 Size2 9 Minimum Copper Wire THWN or THHN AWG or KCMIL Table 310.16 Size 10 Minimum Rigid Metallic Conduit Annex C Table C8 Inches 30 1 14 1 30 1 14 1 30 1 14 1 30 1 14 1 30 1 14 1 30 1 14 1 30* 1 12 1 60 2 8 1 60* 2 8** 100* 3 4 3/4** 100* 3 3** 1 200 3 2** 1** 200* 4 1/0** 1 1⁄4 200* 4 2/0** 1 1⁄4** 400 5 4/0** 1 1⁄2** 400* 5 300** 2** 400* 5 400** 2** 600 6 4/0 2/PHASE (2) 1 1⁄2** ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2 ⁄2** 1 Switch size must be increased if the amp rating of the fuse exceeds the amp rating of the switch. Per 430.52(C)(2), if the motor controller manufacturer’s overload relay tables state a maximum branch circuit protective device of a lower rating, that lower rating must be used in lieu of the sizes shown in Columns 4, 5, or 6. If equipment terminations are rated for 60°C conductors only, the 60°C conductor ampacities must be utilized and therefore larger conductor sizes or conduit sizes may be required. Reduced voltage magnetic DC controller ratings. All equipment manufacturers should be consulted about DC voltage ratings of their equipment. Class J performance, special finger-safe dimensions. ©2005 Cooper Bussmann 159 Motor Protection Tips For Electricians & Maintenance Crews Recommendations for Electrician and Maintenance Crews Often, for various reasons, motors are oversized for applications. For instance, a 5Hp motor is installed when the load demand is only 3Hp. In these cases a much higher degree of protection can be obtained by sizing the overload relay elements and/or Fusetron and Low-Peak dual-element, time-delay fuses based on the actual full-load current draw. 460V. 5 Amperes 1. Preferable – With a clamp-on meter, determine running RMS current when the motor is at normal full-load. (Be sure this current does not exceed nameplate current rating.) The advantage of this method is realized when a lightly loaded motor (especially those over 50 HP) experiences a single-phase condition. Even though the relays and fuses may be sized correctly based on motor nameplate, circulating currents within the motor may cause damage. READ NAMEPLATE 5 Amperes 460V. Alternate – if unable to meter the motor current, then take the current rating off the nameplate. FRS-R 61/4 460V. 2. Then size the overload relay elements and Fusetron FRS-R and FRN-R or LowPeak LPS-RK_SP and LPN-RK_SP dual-element fuses based on this current. For optimum motor circuit protection offering a high degree of “back-up overload” protection, use the table that follows to assist in sizing dual-element fuses. The other fuses in the table LPJ_SP, TCF and LP-CC can provide excellent short circuit protection when sized for Optimum Motor Circuit Protection. However, they typically can not be sized close enough to provide motor back-up overload protection. 3. Use a labeling system to mark the type and amp rating of the fuse that should be in the fuse clips, such as FRS-R 6 1/4. This simple step makes it easy to run spot checks for proper fuse replacement. When installing the proper fuses in the switch to give the desired level of protection, it often is advisable to leave spare fuses on top of the disconnect, the starter enclosure or in a cabinet adjacent to the motor control center. In this way, should the fuses open, the problem can be corrected and proper size fuses easily reinstalled. * Abnormal installations may require Fusetron or Low-Peak dual-element fuses of a larger size than shown providing only short circuit protection. These applications include: (a) Fusetron or Low-Peak dual-element fuses in high ambient temperature environments. (b) A motor started frequently or rapidly reversed. Selection of Fusetron or Low-Peak Dual-Element Fuses based upon Motor FLA for Optimum Motor Circuit Protection* Fusetron or Low-Peak DualElement Fuse Size 1 ⁄10 1 ⁄8 15 ⁄100 2 ⁄10 1 ⁄4 3 ⁄10 4 ⁄10 1 ⁄2 6 ⁄10 8 ⁄10 1 1 1⁄8 1 1⁄4 1 4⁄10 1 1⁄2 1 6⁄10 1 8⁄10 2 2 1⁄4 2 1⁄2 2 8⁄10 3 3 2⁄10 3 1⁄2 4 4 1⁄2 5 5 6⁄10 6 6 1⁄4 7 7 1⁄2 8 9 10 12 15 17 1⁄2 20 25 30 35 40 45 50 60 70 75 80 90 100 110 125 150 175 200 225 250 300 350 400 450 500 600 FRN-R FRS-R Class RK5 0-0.08 0.09-0.10 0.11-0.12 0.13-0.16 0.17-0.20 0.21-0.24 0.25-0.32 0.33-0.40 0.41-0.48 0.49-0.64 0.65-0.80 0.81-0.90 0.91-1.00 1.01-1.12 1.13-1.20 1.21-1.28 1.29-1.44 1.45-1.60 1.61-1.80 1.81-2.00 2.01-2.24 2.25-2.40 2.41-2.56 2.57-2.80 3.81-3.20 3.21-3.60 3.61-4.00 4.01-4.48 4.49-4.80 4.81-5.00 5.01-5.60 5.61-6.00 6.01-6.40 6.41-7.20 7.21-8.00 8.01-9.60 9.61-12.00 12.01-14.00 14.01-16.00 16.01-20.00 20.01-24.00 24.01-28.00 28.01-32.00 32.01-36.00 36.01-40.00 40.01-48.00 48.01-56.00 56.01-60.00 60.01-64.00 64.01-72.00 72.01-80.00 80.01-88.00 88.01-100.00 100.01-120.00 120.01-140.00 140.01-160.00 160.01-180.00 180.01-200.00 200.01-240.00 240.01-280.00 280.01-320.00 320.01-360.00 360.01-400.00 400.01-480.00 Motor Current LPN-RK_SP LPS-RK_SP LPJ_SP Class RK1 Class J 0.0000-0.0769 — 0.0770-0.0961 — 0.0962-0.1153 — 0.1154-0.1538 — 0.1539-0.1923 — 0.1924-0.2307 — 0.2308-0.3076 — 0.3077-0.3846 — 0.3847-0.4615 — 0.4616-0.6153 — 0.6154-0.7692 0.0-0.6666 0.7693-0.8653 0.6667-0.7500 0.8654-0.9615 0.7501-0.8333 0.9616-1.076 0.8334-0.9333 1.077-1.153 0.9334-1.000 1.154-1.230 1.001-1.066 1.231-1.384 1.067-1.200 1.385-1.538 1.201-1.333 1.539-1.730 1.334-1.500 1.731-1.923 1.501-1.666 1.924-2.153 1.667-1.866 2.154-2.307 1.867-2.000 2.308-2.461 2.001-2.133 2.462-2.692 2.134-2.333 2.693-3.076 2.334-2.666 3.077-3.461 2.667-3.000 3.462-3.846 3.001-3.333 3.847-4.307 3.334-3.733 4.308-4.615 3.734-4.000 4.616-4.807 — 4.808-5.384 4.001-4.666 — — 5.385-6.153 4.667-5.333 6.154-6.923 5.334-6.000 6.924-7.692 6.001-6.666 7.693-9.230 6.667-8.000 9.231-11.53 8.001-10.00 11.54-13.46 10.01-11.66 13.47-15.38 11.67-13.33 15.39-19.23 13.34-16.66 19.24-23.07 16.67-20.00 23.08-26.92 20.01-23.33 26.93-30.76 23.34-26.66 30.77-34.61 26.67-30.00 34.62-38.46 30.01-33.33 38.47-46.15 33.34-40.00 46.16-53.84 40.01-46.66 — — 53.85-61.53 46.67-53.33 61.54-69.23 53.34-60.00 69.24-76.92 60.01-66.66 76.93-84.61 66.67-73.33 84.62-96.15 73.34-83.33 96.16-115.3 83.34-100.0 115.4-134.6 100.1-116.6 134.7-153.8 116.7-133.3 153.9-173.0 133.4-150.0 173.1-192.3 150.1-166.6 192.4-230.7 166.7-200.0 230.8-269.2 200.1-233.3 269.3-307.6 233.4-266.6 307.7-346.1 266.7-300.0 346.2-384.6 300.1-333.3 384.7-461.5 333.4-400.0 LP-CC Class CC — — — — — — — 0.0000-0.2500 0.2501-0.3000 0.3001-0.4000 0.4001-0.5000 0.5001-0.5625 0.5626-0.6250 0.6251-0.7000 0.7001-0.7500 0.7501-0.8000 0.8001-0.9000 0.9001-1.000 1.001-1.125 1.126-1.250 1.251-1.400 1.401-1.500 1.501-1.600 1.601-1.750 1.751-2.000 2.001-2.250 2.251-2.500 2.501-2.800 2.801-3.000 3.001-3.125 3.126-3.500 3.501-3.750 3.751-4.000 4.001-4.500 4.501-5.000 5.001-6.000 6.001-7.500 7.501-8.750 8.751-10.00 10.01-12.50 12.51-15.00 — — — — — — — — — — — — — — — — — — — — — — — (c) Motor is directly connected to a machine that cannot be brought up to full speed quickly (large fans, centrifugal machines such as extractors and pulverizers, machines having large fly wheels such as large punch presses.) (d) Motor has a high Code Letter (or possibly no Code Letter) with full voltage start. (e) WYE delta open transition start. (f) Motor has a large inrush current, such as a Design B. 160 ©2005 Cooper Bussmann