Type 2 "No Damage" Motor Starter Protection

Type 2 "No Damage" Motor Starter Protection
Component Protection — Low Voltage Motor Controllers
It should be noted that these are basic short-circuit requirements. Higher, combination ratings are attainable if tested to an
applicable standard. However, damage is usually allowed.
430.52 of the National Electrical Code ® allows dualelement, time-delay fuses and other overcurrent protective devices
to be sized for branch circuit protection (short-circuit protection
only). Controller manufacturers often affix labels to the inside of the
motor starter cover which recommend the maximum size fuse for
each overload relay size.
A paragraph in NEC® 430.52 states:
Motor Controller Protection
The diagram below shows a Size 2, combination motor controller
supplying a 460 volt, 3Ø, 20HP motor. The short-circuit withstand
of this and other motor controllers are established so that they may
be properly protected from short-circuit damage.
Short-Circuit Protection of Motor Controller
40,000 RMS
Symmetrical
Available
3Ø, 460V
20HP
M 3Ø, 460V
27 F.L.A.
LOW-PEAK
Dual-Element,
Time-Delay Fuse
®
Where maximum branch circuit short-circuit and ground fault
protective device ratings are shown in the manufacturer’s overload
relay table for use with a motor controller or are otherwise marked
on the equipment, they shall not be exceeded even if higher values are allowed as shown above.**
Typical Size 2 Controller
There are several independent organizations engaged in regular testing of motor controllers under short-circuit conditions. One
of these, Underwriter’s Laboratories, tests controllers rated one
horsepower or less and 300V or less with 1000 amperes short-circuit current available to the controller test circuit. Controllers rated
50HP or less are tested with 5000 amperes available and controllers rated above 50HP to 200HP are tested with 10,000
amperes available. See the table below for these values.*
Motor Controller
HP Rating
1HP or less and 300V or less
50HP or less
Greater than 50HP to 200HP
201HP to 400HP
401HP to 600HP
601HP to 900HP
901HP to 1600HP
** “Above” refers to other portions of 430-52 not shown here.
This paragraph means that the branch circuit overcurrent protection for overload relays in motor controllers must be no greater
than the maximum size as shown in the manufacturer’s overload
relay table. These maximum branch circuit sizes must be observed
even though other portions of 430.52 allow larger sizing of branch
circuit overcurrent protection.
The reason for this maximum overcurrent device size is to
provide short-circuit protection for the overload relays and motor
controller.
Test Short-Circuit
Current Available*
1,000A
5,000A
10,000A
18,000A
30,000A
42,000A
85,000A
Type 1 vs. Type 2 Protection
UL has developed a short-circuit test procedure designed to verify
that motor controllers will not be a safety hazard and will not cause
a fire.
Compliance to the standard allows deformation of the enclosure, but the door must not be blown open and it must be possible
* From Industrial Control Equipment, UL 508.
126
Component Protection — Low Voltage Motor Controllers
to open the door after the test. In the standard short-circuit tests,
the contacts must not disintegrate, but welding of the contacts is
considered acceptable. Tests allow the overload relay to be damaged with burnout of the current element completely acceptable.
For short-circuit ratings in excess of the standard levels listed
in UL 508, the damage allowed is even more severe. Welding or
complete disintegration of contacts is acceptable and complete
burnout of the overload relay is allowed. Therefore, a user cannot
be certain that the motor starter will not be damaged just because
it has been UL Listed for use with a specific branch circuit protective device. UL tests are for safety, with the doors closed but do
allow a significant amount of damage as long as it is contained
within the enclosure.
In order to properly select a branch circuit protective device
that not only provides motor branch circuit protection, but also protects the circuit components from damage, the designer must look
beyond mere safety standards. Coordination (protection) of the
branch circuit protective device and the motor starter is necessary
to insure that there will be no damage or danger to either the
starter or the surrounding equipment. There is an “Outline of
Investigation”, (UL508E) and an IEC (International Electrotechnical
Commission) Standard IEC Publication 60947, “Low Voltage
Switchgear and Control, Part 4-1: Contactors and Motor Starters”,
that offer guidance in evaluating the level of damage likely to occur
during a short-circuit with various branch circuit protective
devices. These standards address the coordination (protection)
between the branch circuit protective device and the motor starter.
They provide a method to measure the performance of these
devices should a short-circuit occur. They define two levels of protection (coordination) for the motor starter:
Type 1. Considerable damage to the contactor and overload
relay is acceptable. Replacement of components or a completely
new starter may be needed. There must be no discharge of parts
beyond the enclosure.
Type 2. No damage is allowed to either the contactor or overload relay. Light contact welding is allowed, but must be easily
separable.
Where Type 2 protection is desired, the controller manufacturer must verify that Type 2 protection can be achieved by using a
specified protective device. U.S. manufacturers have both their
NEMA and IEC motor controllers verified to meet the Type 2
requirements outlined in UL508E and IEC 60947-4. As of this writing only current-limiting devices have been able to provide the current-limitation necessary to provide verified Type 2 protection. In
many cases, Class J, Class RK1, or Class CC fuses are required,
because Class RK5 fuses and circuit breakers aren’t fast enough
under short-circuit conditions to provide Type 2 protection.
Photo 1 Before Test: MCP as motor branch circuit protection for
10HP, IEC Starter with 22,000 amps available at 480V.
Tables: Type 2 Motor Starter / Bussmann® Fuses
On the following pages are motor starters of several manufacturers
that have been verified by testing for Type 2 protection using the
fuses denoted. These are maximum fuse sizes; for specific applications, it may be desirable to size closer. In some cases, the fuse
type/ampere rating shown is greater than that permitted for branch
circuit protection for a single motor per 430.52 (footnoted); however, the size may be applicable for group motor protection applications. In a few cases, the fuse type/ampere rating may be too small
for typical motor starting applications (footnoted). It is recommended to use these fuse types/ampere ratings in conjunction with
the fuse type/sizing philosophy (backup motor overload, optimal or
maximum branch circuit protection - see Motor Protection Table
explanation in Motor Circuit Protection Section of this book.) This
data was obtained from the manufacturers or their web sites.
Photo 2: Same as Photo 1, but during the test with MCP as the
motor branch circuit protection. The heater elements vaporized and
the contacts were severely welded. Extensive starter repair or total
starter replacement would be required. This level of damage is permissible by UL508 or UL508E/IEC60947-4-1 Type 1 protection.
The following pages have Fuse/Starter (IEC & NEMA) Type 2 “no
damage” Tables for:
General Electric
Rockwell Automation/Allen-Bradley
Square D Co.
Siemens
Cutler-Hammer
Photo 3 During Test: same test circuit and same type starter during
short-circuit interruption. The difference is current-limiting fuses
provide the motor branch circuit protection. This illustrates the
level of protection required by UL 508E and IEC 60947-4-1 for
Type 2 “no damage” protection. The heaters and overload relays
maintained calibration, which is extremely important to retain circuit overload protection. This starter could be put back into service
without any repair.
127
128 to 132
133 to 134
135 to 136
137 to 138
139 to 141
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/General
Electric Co.
IEC
230 Volt, Three-Phase Motors
200 Volt, Three-Phase Motors
MAX. FUSE
MAX. FUSE
HP(FLC)
CONTACTOR
OLR
RT*1J
LPJ_SP
CLASS J
4
.5(2.2)
RT*1J
RT*1K
8†
.75(3.2)
RT*1K
8†
RT*1K
8
1(4.2)
RT*1L
10
RT*1L
10
1.5(6.0)
RT*1L
10
RT*1M
12
2(6.8)
RT*1M
12
RT*1N
20†
3(9.6)
RT*1N
20
RT*1P
20
RT*1S
RT*2B
RT*1T
RT*1U
RT*2D
RT*1V
RT*1W
RT*2E
RT*2G
RT*2H
RT*3B
RT*3C
35
35
45†
45
60†
60†
70
70
100
125
125
150
5(15.2)
5(15.2)
7.5(22.0)
7.5(22.0)
7.5(22.0)
10(28.0)
10(28.0)
10(28.0)
15(42.0)
20(54.0)
20(54.0)
25(68.0)
25(68.0)
30(80.0)
25(68.0)
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL02, CL03, CL04, CL25, CL45
CL06, CL07, CL08, CL09, CL10
CL03, CL04, CL45
CL06, CL07, CL08, CL09, CL10
CL03, CL04, CL45
CL04
CL45
CL06, CL07, CL08, CL09, CL10
CL06, CL07, CL08, CL09, CL10
CL07, CL08, CL09, CL10
CL07, CL08, CL09, CL10
CK08, CK09, CK95
CL08, CL09, CL10
CK08, CK09, CK95
CK08, CK09
LPJ_SP
CLASS J
4
RT*1S
RT*2B
RT*1T
RT*2C
RT*1U
RT*1V
RT*1V
RT*2D
RT*2F
RT*2G
RT*2H
RT*3B
RT*2J
RT*3B
RT*3C
35†
35†
45
45
45
60
60
60
90
100
125†
125
125
125
150
HP(FLC)
CONTACTOR
OLR
.5(2.5)
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL02, CL03, CL04, CL25, CL45
CL06, CL07, CL08, CL09, CL10
CL03, CL04, CL45
CL04, CL05
CL06, CL07, CL08, CL09, CL10
CL04, CL45
CL45
CL06, CL07, CL08, CL09, CL10
CL07, CL08, CL09, CL10
CL08, CL09, CL10
CK08, CK09, CK95
CK08, CK09
.5(2.5)
.75(3.7)
1(4.8)
1.5(6.9)
2(7.8)
3(11.0)
5(17.5)
5(17.5)
5(17.5)
7.5(25.3)
7.5(25.3)
7.5(25.3)
10(32.2)
10(32.2)
15(48.3)
20(62.1)
20(62.1)
25(78.2)
* Replace * with “A” or “M”
†
Sized larger than code max for single motor.
128
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/General
Electric Co.
IEC
460 Volt, Three-Phase Motors
575 Volt, Three-Phase Motors
MAX. FUSE
HP(FLC)
CONTACTOR
OLR
.5(1.1)
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL02, CL03, CL04, CL25, CL45
CL06, CL07, CL08, CL09, CL10
CL03, CL04, CL45
CL06, CL07, CL08, CL09, CL10
CL04, CL45
CL06, CL07, CL08, CL09, CL10
CL45
CL06, CL07, CL08, CL09, CL10
CL06, CL07, CL08, CL09, CL10
CL06, CL07, CL08, CL09, CL10
CL07, CL08, CL09, CL10
CL08, CL09, CL10
CL08, CL09, CL10
CL08, CL09, CL10
CL09, CL10
CL09, CL10
.5(1.1)
.75(1.6)
1(2.1)
1.5(3.0)
2(3.4)
3(4.8)
5(7.6)
7.5(11.0)
10(14.0)
10(14.0)
15(21.0)
15(21.0)
20(27.0)
20(27.0)
25(34.0)
25(34.0)
30(40.0)
30(40.0)
40(52.0)
50(65.0)
50(65.0)
50(65.0)
60(77.0)
60(77.0)
MAX. FUSE
HP(FLC)
CONTACTOR
OLR
RT*1F
LPJ_SP
CLASS J
1.5♦
.5(0.9)
RT*1F
RT*1G
2
.75(1.3)
RT*1G
2
RT*1H
4†
.75(1.3)
RT*1H
4†
RT*1J
4
1(1.7)
RT*1H
4†
RT*1K
8†
1.5(2.4)
RT*1J
4
RT*1K
8†
2(2.7)
RT*1J
4
RT*1L
10
2(2.7)
RT*1K
8†
RT*1N
20†
3(3.9)
RT*1K
8
RT*1P
20
5(6.1)
RT*1L
10
RT*1R
RT*2A
RT*1T
RT*2C
RT*1V
RT*2D
RT*1W
RT*2E
RT*2E
RT*2F
RT*2G
RT*2H
RT*3B
RT*2J
RT*3B
RT*2K
25
30
45
45
60
60
70
70
70
90
100
125
125
125
125
150
5(6.1)
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL00, CL01, CL02, CL03, CL04,
CL25, CL45
CL02, CL03, CL04, CL25, CL45
CL06, CL07, CL08, CL09, CL10
CL03, CL04, CL45
CL06, CL07, CL08, CL09, CL10
CL03, CL04, CL45
CL04, CL45
CL06, CL07, CL08, CL09, CL10
CL04, CL45
CL06, CL07, CL08, CL09, CL10
CL45
CL06, CL07, CL08, CL09, CL10
CL06, CL07, CL08, CL09, CL10
CL06, CL07, CL08, CL09, CL10
CL07, CL08, CL09, CL10
CL07, CL08, CL09, CL10
CK08, CK09, CK95
CK08, CK09, CK95
CK08, CK09
LPJ_SP
CLASS J
1.5
RT*1M
12
RT*1N
20
RT*1P
20
RT*1S
RT*2B
RT*1T
RT*2C
RT*1U
RT*1V
RT*2D
RT*1V
RT*2D
RT*1W
RT*2E
RT*2E
RT*2F
RT*2G
RT*2H
RT*3B
RT*3B
RT*3C
35
35
45
45
45
60
60
60
60
70
70
70
90
100
125
125
125
150
7.5(9.0)
10(11.0)
15(17.0)
15(17.0)
20(22.0)
20(22.0)
20(22.0)
25(27.0)
25(27.0)
30(32.0)
30(32.0)
30(32.0)
30(32.0)
40(41.0)
40(41.0)
50(52.0)
60(62.0)
60(62.0)
75(77.0)
75(77.0)
* Replace * with “A” or “M”
♦
May be too small to allow some motors to start.
†
Sized larger than code max for single motor.
129
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/General Electric Co.
NEMA
200 Volt, Three-Phase Motors
HP(FLC)
.5(2.5)
.5(2.5)
.75(3.7)
.75(3.7)
1(4.8)
1(4.8)
1.5(6.9)
1.5(6.9)
1.5(6.9)
2(7.8)
2(7.8)
3(11.0)
3(11.0)
5(17.5)
5(17.5)
5(17.5)
5(17.5)
5(17.5)
230 Volt, Three-Phase Motors
OLR
CR324CXE
CR123C326A
CR123C356A
CR324CXF
CR324CXF
CR123C526A
CR324CXG
CR123C778A
CR123C695A
CR324CXG
CR123C867A
CR324CXG
CR123C125B
CR234CXH
CR234FXK
CR123C180B
CR123C198B
CR123F233B
MAX. Fuse
LPJ_SP
Class J
6
6
8
10
10
10
15
15
15
17.5
17.5
20
20
35
35
35
35
35
OLR
CR123C131A
CR324CXD
CR324CXD
CR123C196A
CR123C268A
CR324CXE
CR324CXE
CR123C356A
CR324CXF
CR123C379A
CR324CXF
CR123C526A
CR324CXG
CR324DXG
CR123C867A
CR324CXG
CR324DXG
CR123C125B
CR234CXH
CR234DXH
CR123C163B
CR324CXH
CR324DXH
CR324FXK
CR123C228B
CR123F243B
MAX. Fuse
LPJ_SP
Class J
2.5
3
3.5
3.5
5
6
6
6
7
7
10
10
15
15
15
20
20
20
30
30
30
45
45
45
45
45
HP(FLC)
.5(2.2)
.5(2.2)
.75(3.2)
.75(3.2)
1(4.2)
1(4.2)
1.5(6.0)
1.5(6.0)
2(6.8)
2(6.8)
2(6.8)
3(9.6)
3(9.6)
3(9.6)
5(15.2)
5(15.2)
5(15.2)
7.5(22.0)
7.5(22.0)
7.5(22.0)
7.5(22.0)
7.5(22.0)
460 Volt, Three-Phase Motors
HP(FLC)
.5(1.1)
.5(1.1)
.75(1.6)
.75(1.6)
1(2.1)
1(2.1)
1.5(3.0)
1.5(3.0)
2(3.4)
2(3.4)
3(4.8)
3(4.8)
5(7.6)
5(7.6)
5(7.6)
7.5(11.0)
7.5(11.0)
7.5(11.0)
10(14.0)
10(14.0)
10(14.0)
15(21.0)
15(21.0)
15(21.0)
15(21.0)
15(21.0)
OLR
CR123C268A
CR324CXE
CR324CXF
CR123C356A
CR324CXF
CR123C466A
CR324CXF
CR123C695A
CR324CXG
CR324DXG
CR123C778A
CR324CXG
CR324DXG
CR123C104B
CR234CXH
CR234DXH
CR123C163B
CR324DXH
CR324FXK
CR123C228B
CR123C250B
CR123C270B
MAX. Fuse
LPJ_SP
Class J
5
6
7
7
10
10
15
15
15
15
15
20
20
20
30
30
30
45
45
45
45
45
OLR
CR123C109A
MAX. Fuse
LPJ_SP
Class J
2
575 Volt, Three-Phase Motors
HP(FLC)
.5(0.9)
130
.5(0.9)
CR324CXD
3
.75(1.3)
.75(1.3)
1(1.7)
1(1.7)
1(1.7)
1.5(2.4)
1.5(2.4)
2(2.7)
2(2.7)
3(3.9)
3(3.9)
5(6.1)
5(6.1)
7.5(9.0)
7.5(9.0)
7.5(9.0)
7.5(9.0)
10(11.0)
10(11.0)
10(11.0)
15(17.0)
15(17.0)
15(17.0)
20(22.0)
20(22.0)
20(22.0)
20(22.0)
20(22.0)
CR324CXD
CR123C163A
CR324CXD
CR123C196A
CR324CXE
CR324CXE
CR123C301A
CR324CXE
CR123C326A
CR324CXF
CR123C419A
CR324CXF
CR123C695A
CR324CXG
CR324DXG
CR123C104B
CR123C955A
CR123C125B
CR324CXG
CR324DXG
CR234DXH
CR234FXK
CR123C180B
CR324DXH
CR324FXK
CR123C228B
CR123C250B
CR123C270B
3
3
3.5
3.5
3.5
6
6
6
6
10
10
15
15
20
20
20
20
20
20
20
35
35
35
45
45
45
45
45
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/General Electric Co.
NEMA
200 Volt, Three-Phase Motors
HP(FLC)
7.5 (25.3)
7.5 (25.3)
7.5 (25.3)
7.5 (25.3)
7.5 (25.3)
10 (32.2)
10 (32.2)
10 (32.2)
10 (32.2)
15 (48.3)
15 (48.3)
15 (48.3)
20 (62.1)
20 (62.1)
25 (78.2)
25 (78.2)
25 (78.2)
30 (92.0)
30 (92.0)
30 (92.0)
40 (120.0)
40 (120.0)
40 (120.0)
50(150.0)
50(150.0)
60(177.0)
60(177.0)
75(221.0)
75(221.0)
100(285.0)
125(359.0)
150(414.0)
OLR
CR324DXH
CR324FXK
CR123C273B
CR123C303B
CR123F300B
CR324DXJ
CR324FXK
CR123C330B
CR123F395B
CR324DXJ
CR324FXL
CR123F614B
CR324FXL
CR123F772B
CR234FXM
CR324GXP
CR123F104C
CR234FXM
CR324GXP
CR123F118C
CR234FXM
CR324GXP
CR123F161C
CR324GXQ
CR324HXS
CR324GXQ
CR324HXS
CR324GXQ
CR324HXS
CR324HXT
CR324HXT
CR324HXT
230 Volt, Three-Phase Motors
LPJ_SP
Class J
50
50
50
50
50
70
70
70
70
100
100
100
125
125
175
175
175
200
200
200
250
250
250
300
300
350
350
450
450
600
MAX. Fuse
KRP-C_SP
Class L
HP(FLC)
10(28.0)
10(28.0)
10(28.0)
10(28.0)
15(42.0)
15(42.0)
15(42.0)
15(42.0)
15(42.0)
20(54.0)
20(54.0)
25(68.2)
25(68.2)
25(68.2)
25(68.2)
25(68.2)
30(80.0)
30(80.0)
30(80.0)
40(104.0)
40(104.0)
40(104.0)
50(130.0)
50(130.0)
50(130.0)
60(145.0)
60(145.0)
75(192.0)
75(192.0)
100(248.0)
100(248.0)
125(312.0)
150(360.0)
200(480.0)
1000
1000
131
OLR
CR324DXJ
CR324FXK
CR123C303B
CR123F327B
CR324DXJ
CR324FXL
CR123F567B
CR123F487B
CR123F440B
CR324FXL
CR123F719B
CR324FXL
CR324FXM
CR324GXP
CR123F848B
CR123F914B
CR234FXM
CR324GXP
CR123F104C
CR234FXM
CR324GXP
CR123F133C
CR234FXM
CR324GXP
CR123F161C
CR324GXQ
CR324HXS
CR324GXQ
CR324HXS
CR324GXQ
CR324HXS
CR324HXT
CR324HXT
CR324HXT
LPJ_SP
Class J
60
60
60
60
90
90
90
90
90
110
110
150
150
150
150
150
175
175
175
225
225
225
250
250
250
300
300
400
400
500
500
MAX. Fuse
KRP-C_SP
Class L
900
1000
1000
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/General Electric Co.
NEMA
460 Volt, Three-Phase Motors
HP(FLC)
20(27.0)
20(27.0)
20(27.0)
20(27.0)
20(27.0)
20(27.0)
25(34.0)
25(34.0)
25(34.0)
25(34.0)
30(40.0)
30(40.0)
30(40.0)
30(40.0)
30(40.0)
40(52.0)
40(52.0)
40(52.0)
50(65.0)
50(65.0)
50(65.0)
50(65.0)
50(65.0)
60(77.0)
60(77.0)
60(77.0)
60(77.0)
75(96.0)
75(96.0)
75(96.0)
100(124.0)
100(124.0)
100(124.0)
125(156.0)
125(156.0)
150(180.0)
150(180.0)
200(240.0)
200(240.0)
250(302.0)
300(361.0)
350(414.0)
400(477.0)
450(515.0)
OLR
CR324DXH
CR324DXJ
CR324FXK
CR123C303B
CR123F327B
CR123C330B
CR324DXJ
CR324FXK
CR123C366B
CR123F430B
CR324DXJ
CR324FXL
CR123C400B
CR123F487B (SIZE 3)
CR123F487B (SIZE 4)
CR324FXL
CR123F658B (SIZE 3)
CR123F658B (SIZE 4)
CR324FXL
CR123F772B
CR324FXM
CR324GXP
CR123F848B
CR324FXM
CR324GXP
R123F104C (SIZE 3)
R123F104C (SIZE 4)
CR234FXM
CR324GXP
CR123F118C
CR234FXM
CR324GXP
CR123F161C
CR324GXQ
CR324HXS
CR324GXQ
CR324HXS
CR324GXQ
CR324HXS
CR324HXT
CR324HXT
CR324HXT
CR324HXT
CR324HXT
575 Volt, Three-Phase Motors
LPJ_SP
Class J
60
60
60
60
60
60
70
70
70
70
90
90
90
90
90
110
110
110
125
125
125
125
125
150
150
150
150
200
200
200
250
250
250
350
350
400
400
500
500
MAX. Fuse
KRP-C_SP
Class L
HP(FLC)
25(27.0)
25(27.0)
25(27.0)
25(27.0)
25(27.0)
25(27.0)
30(32.0)
30(32.0)
30(32.0)
30(32.0)
40(41.0)
40(41.0)
40(41.0)
40(41.0)
40(41.0)
50(52.0)
50(52.0)
50(52.0)
60(62.0)
60(62.0)
75(77.0)
75(77.0)
75(77.0)
75(77.0)
100(99.0)
100(99.0)
100(99.0)
125(125.0)
125(125.0)
125(125.0)
150(144.0)
150(144.0)
200(192.0)
200(192.0)
250(242.0)
250(242.0)
300(289.0)
350(336.0)
400(382.0)
450(412.0)
500(472.0)
900
1000
1000
1000
1000
132
OLR
CR324DXH
CR324DXJ
CR324FXK
CR123C303B
CR123F327B
CR123C330B
CR324DXJ
CR324FXK
CR123C330B
CR123F395B
CR324DXJ
CR324FXL
CR123C400B
CR123F567B
CR123F487B
CR324FXL
CR123F658B (SIZE 3)
CR123F658B (SIZE 4)
CR324FXL
CR123F772B
CR324FXM
CR324GXP
R123F104C (SIZE 3)
R123F104C (SIZE 4)
CR234FXM
CR324GXP
CR123F118C
CR234FXM
CR324GXP
CR123F161C
CR324GXQ
CR324HXS
CR324GXQ
CR324HXS
CR324GXQ
CR324HXS
CR324HXT
CR324HXT
CR324HXT
CR324HXT
CR324HXT
LPJ_SP
Class J
60
60
60
60
60
60
70
70
70
70
90
90
90
90
90
110
110
110
125
125
150
150
150
150
200
200
200
250
250
250
300
300
400
400
500
500
MAX. Fuse
KRP-C_SP
Class L
800
1000
1000
1000
1000
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/Rockwell
Automation, Allen-Bradley
IEC
230 Volt, Three-Phase Motors
200 Volt, Three-Phase Motors
HP(FLC)
0.5(2.5)
0.75(3.7)
1(4.8)
1.5(6.9)
2(7.8)
3(11)
5(17.5)
7.5(25.3)
10(32.2)
15(48.3)
20(62.1)
25(78.2)
Contactor
Basic Cat. No.
(a)
100-C09
100-C09
100-C09
100-C09
100-C09
100-C12
100-C23
100-C30
100-C37
100-C60
100-C72
100-C85
Overload Relay
Basic Cat. No.
(b)
193-E**EB
193-E**EB
193-E**FB
193-E**FB
193-E**FB
193-E**FB
193-E**GB
193-E**HC
193-E**HC
193-E**KE
193-E**KE
193-E**KE
Max. Fuse Rating
LPJ_SP
LP-CC
Class J
Class CC
6
6
10
10
15†
15
15
15
15
15♦
20
20♦
30
30♦
40
50
80
100
100♦
HP(FLC)
0.5(2.2)
0.75(3.2)
1(4.2)
1.5(6)
2(6.8)
3(9.6)
5(15.2)
7.5(22)
10(28)
15(42)
20(54)
25(68)
30(80)
460 Volt, Three-Phase Motors
HP(FLC)
0.5(1.1)
0.75(1.6)
1(2.1)
1.5(3)
2(3.4)
3(4.8)
5(7.6)
7.5(11)
10(14)
15(21)
20(27)
25(34)
30(40)
40(52)
50(65)
60(77)
Contactor
Basic Cat. No.
(a)
100-C09
100-C09
100-C09
100-C09
100-C09
100-C09
100-C09
100-C12
100-C16
100-C23
100-C30
100-C37
100-C43
100-C60
100-C72
100-C85
Contactor
Basic Cat. No.
(a)
100-C09
100-C09
100-C09
100-C09
100-C09
100-C12
100-C16
100-C23
100-C30
100-C43
100-C60
100-C72
100-C85
Overload Relay
Basic Cat. No.
(b)
193-E**DB
193-E**EB
193-E**FB
193-E**FB
193-E**FB
193-E**FB
193-E**GB
193-E**GB
193-E**HC
193-E**JD
193-E**KE
193-E**KE
193-E**KE
Max. Fuse Rating
LPJ_SP
LP-CC
Class J
Class CC
6
6
10†
10
15†
15
15
15
15
15
20
20
20♦
20♦
30♦
30♦
40♦
50♦
80♦
100
100♦
Overload Relay
Basic Cat. No.
(b)
193-E**DB
193-E**DB
193-E**DB
193-E**DB
193-E**EB
193-E**FB
193-E**FB
193-E**FB
193-E**FB
193-E**FB
193-E**GB
193-E**HC
193-E**HC
193-E**HC
193-E**KE
193-E**KE
193-E**KE
Max. Fuse Rating
LPJ_SP
LP-CC
Class J
Class CC
3
3
3
3
6†
6
6
6
10†
10
10
10
15
15
15
15♦
15
15♦
20
20♦
30
30♦
40
50
50
80
100
100
575 Volt, Three-Phase Motors
Overload Relay
Basic Cat. No.
(b)
193-E**DB
193-E**DB
193-E**DB
193-E**EB
193-E**EB
193-E**FB
193-E**FB
193-E**FB
193-E**GB
193-E**GB
193-E**HC
193-E**HC
193-E**JD
193-E**KE
193-E**KE
193-E**KE
Max. Fuse Rating
LPJ_SP
LP-CC
Class J
Class CC
3
3
6†
6
6
6
10†
10
10†
10
15†
15
15
15♦
20
20♦
20♦
20♦
30♦
30♦
40
50
50♦
80
100
100♦
HP(FLC)
0.5(0.9)
0.75(1.3)
1(1.7)
1.5(2.4)
2(2.7)
3(3.9)
5(6.1)
5(7.6)
7.5(9)
10(11)
15(17)
20(22)
25(27)
30(32)
40(41)
50(52)
60(62)
(a) Catalog number is not complete, add coil voltage code and auxiliary contact description.
(b) Catalog number is not complete, replace ** with trip class and reset mode.
♦
May be too small to allow some motors to start.
†
Sized larger than code max for single motor.
133
Contactor
Basic Cat. No.
(a)
100-C09
100-C09
100-C09
100-C09
100-C09
100-C09
100-C09
100-C09
100-C09
100-C12
100-C23
100-C30
100-C37
100-C37
100-C60
100-C72
100-C85
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/Rockwell
Automation, Allen-Bradley
NEMA
200 Volt, Three-Phase Motors
230 Volt, Three-Phase Motors
MAXIMUM
(1)
HP(FLC)
1.5(6.9)
2(7.8)
3(11.0)
5(17.5)
7.5(25.3)
10(32.2)
15(48.3)
20(62.1)
25(78.2)
30(92.0)
40(120.0)
50(150.0)
60(177.1)
75(221.0)
STARTER
SIZE
CAT. #
0
509-A
0
509-A
0
509-A
1
509-B
2
509-C
3
509-D
3
509-D
3
509-D
3
509-D
4
509-E
4
509-E
5
509-F
5
509-F
5
509-F
HEATER
ELEMENT
W48
W50
W53
W59
W63
W65
W68
W71
W75
W77
W81
W37
W39
W41
MAXIMUM
LPN-RK_SP/LPJ_SP
CLASS RK1/J
15
15
20
30
50
60
100
100
150
175
200
200♦
250♦
350
HP(FLC)
2(6.8)
3(9.6)
5(15.2)
7.5(22.0)
10(28.0)
15(42.0)
20(54.0)
25(68.2)
30(80.0)
40(104.0)
50(130.0)
60(154.0)
75(192.0)
100(248.0)
(1)
HEATER
ELEMENT
W48
W52
W57
W61
W64
W66
W69
W73
W75
W79
W83
W37
W40
W43
LPN-RK_SP/LPJ_SP
CLASS RK1/J
15
20
30
45
60
90
100
100♦
150
175
200
200♦
300
400
(1)
HEATER
ELEMENT
W47
W51
W53
W58
W63
W64
W66
W69
W71
W74
W78
W35
W36
W40
LPS-RK_SP/LPJ_SP
CLASS RK1/J
12
20
20
35
60
70
90
100
100
125
175
200
200♦
300
STARTER
SIZE
CAT. #
0
509-A
0
509-A
1
509-B
2
509-C
3
509-C
3
509-D
3
509-D
3
509-D
3
509-D
4
509-E
4
509-E
5
509-F
5
509-F
5
509-F
575 Volt, Three-Phase Motors
460 Volt, Three-Phase Motors
MAXIMUM
MAXIMUM
(1)
HP(FLC)
5(7.6)
7.5(11.0)
10(14.0)
15(21.0)
20(27.0)
25(34.0)
30(40.0)
40(52.0)
50(65.0)
60(77.0)
75(96.0)
100(124.0)
125(156.0)
150(180.0)
200(240.0)
STARTER
SIZE
CAT. #
0
509-A
1
509-B
1
509-B
2
509-C
2
509-C
3
509-D
3
509-D
3
509-D
3
509-D
4
509-E
4
509-E
4
509-E
5
509-F
5
509-F
5
509-F
HEATER
ELEMENT
W49
W53
W56
W61
W63
W66
W66
W69
W72
W74
W77
W82
W37
W39
W42
LPS-RK_SP/LPJ_SP
CLASS RK1/J
15
20
30
45
60
60
90
100
100
125
175
200
200♦
250♦
400
HP(FLC)
5(6.1)
7.5(9.0)
10(11.0)
15(17.0)
25(27.0)
30(32.0)
40(41.0)
50(52.0)
60(62.0)
75(77.0)
100(99.0)
125(125.0)
150(144.0)
200(192.0)
(1) Catalog number is not complete. Refer to Bulletin 509 Section of A-B Industrial Control
Catalog to specify complete catalog starter number.
♦
May be too small to allow some motors to start.
134
STARTER
SIZE
CAT. #
0
509-A
1
509-B
1
509-B
2
509-C
2
509-C
3
509-D
3
509-D
3
509-D
4
509-E
4
509-E
4
509-E
5
509-F
5
509-F
5
509-F
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/Square D Co. IEC
230 Volt, Three Phase Motors
200 Volt, Three Phase Motors
MAXIMUM FUSE
MAXIMUM FUSE
HP(FLC)
CONTACTOR
OLR
.5(2.5)
.75(3.7)
1(4.8)
1.5(6.9)
2(7.8)
2(7.8)
3(11.0)
5(17.5)
5(17.5)
7.5(25.3)
10(32.2)
15(48.3)
15(48.3)
15(48.3)
20(62.1)
20(62.1)
30(92.0)
40(120.0)
50(150.0)
50(150.0)
60(177.0)
60(177.0)
75(221.0)
100(285.0)
100(285.0)
125(359.0)
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D012
LC1D018
LC1D025
LC1D032
LC1D040
LC1D050
LC1D050
LC1D065
LC1D050
LC1D065
LC1F115
LC1F150
LC1F185
LC1F185
LC1F265
LC1F265
LC1F400
LC1F400
LC1F400
LC1F500
LR2D 1307
LR2D 1308
LR2D 1310
LR2D 1312
LR2D 1312
LR2D 1314
LR2D 1316
LR2D 1321
LR2D 1322
LR2D 2353
LR2D 3355
LR2D 3357
LR2D 3359
LR2D 3359
LR2D 3359
LR2D 3359
LR2F 5367
LR2F 5569
LR2F 5569
LR2F 5571
LR2F 6573
LR2F 5571
LR2F 6575
LR2F 6575
LR2F 6577
LR2F 6577
LPJ_SP
CLASS J
4
6
10
15
15
15
20
25♦
35
40
60
70♦
80
100
80♦
100
200
250
300
300
350
500
600
600
LPN-RK_SP KRP-C_SP
CLASS RK1 CLASS L
200
250
250
300
350
350
450
500
601
800
460 Volt, Three Phase Motors
HP(FLC)
CONTACTOR
OLR
.5(2.2)
.75(3.2)
1(4.2)
1.5(6.0)
1.5(6.0)
2(6.8)
3(9.6)
3(9.6)
5(15.2)
7.5(22.0)
10(28.0)
15(42.0)
20(54.0)
20(54.0)
40(104.0)
40(104.0)
50(130.0)
60(154.0)
60(154.0)
75(192.0)
75(192.0)
100(248.0)
125(312.0)
125(312.0)
150(360.0)
200(480.0)
250(600.0)
300(720.0)
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D012
LC1D018
LC1D032
LC1D032
LC1D050
LC1D050
LC1D065
LC1F115
LC1F115
LC1F150
LC1F185
LC1F185
LC1F265
LC1F265
LC1F400
LC1F400
LC1F400
LC1F500
LC1F500
LC1F630
LC1F630
LR2D 1307
LR2D 1308
LR2D 1310
LR2D 1310
LR2D 1312
LR2D 1312
LR2D 1314
LR2D 1316
LR2D 1321
LR2D 1322
LR2D 2353
LR2D 3357
LR2D 3359
LR2D 3359
LR2F 5367
LR2F 5369
LR2F 5569
LR2F 5569
LR2F 5571
LR2F 6571
LR2F 6573
LR2F 6575
LR2F 6575
LR2F 6577
LR2F 6577
LR2F 7579
LR2F 7581
LR2F 8583
LPJ_SP
CLASS J
4
6
10
10
15
15
15
20
25
35
40♦
70
80♦
100
225
225
250
300
300
400
400
500
500
600
600
LPN-RK_SP KRP-C_SP
CLASS RK1 CLASS L
200
225
250
250
300
350
400
500
500
700
800
1000
1350
1600
MAXIMUM FUSE
575 Volt, Three Phase Motors
HP(FLC)
CONTACTOR
OLR
.5(1.1)
.75(1.6)
1(2.1)
1.5(3.0)
2(3.4)
3(4.8)
5(7.6)
5(7.6)
7.5(11.0)
10(14.0)
15(21.0)
20(27.0)
25(34.0)
30(40.0)
30(40.0)
40(52.0)
40(52.0)
50(65.0)
50(65.0)
75(96.0)
100(124.0)
125(156.0)
125(156.0)
150 (180.0)
150 (180.0)
200 (240.0)
200 (240.0)
250 (302.0)
250 (302.0)
300 (361.0)
350 (414.0)
400 (477.0)
500 (590.0)
600 (720.0)
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D012
LC1D018
LC1D032
LC1D032
LC1D040
LC1D040
LC1D050
LC1D050
LC1D065
LC1D050
LC1D065
LC1F115
LC1F150
LC1F185
LC1F185
LC1F265
LC1F265
LC1F400
LC1F400
LC1F400
LC1F400
LC1F500
LC1F500
LC1F500
LC1F630
LC1F630
LR2D 1306
LR2D 1306
LR2D 1307
LR2D 1308
LR2D 1308
LR2D 1310
LR2D 1312
LR2D 1314
LR2D 1316
LR2D 1321
LR2D 1322
LR2D 2353
LR2D 3355
LR2D 3355
LR2D 3357
LR2D 3359
LR2D 3359
LR2D 3359
LR2D 3359
LR2F 5367
LR2F 5569
LR2F 5569
LR2F 5571
LR2F 6571
LR2F 6573
LR2F 6573
LR2F 6575
LR2F 6575
LR2F 6577
LR2F 6577
LR2F 7579
LR2F 7579
LR2F 7581
LR2F 8583
♦
LPJ_SP
CLASS J
3
3
4
6
6
10
15
15
20
25
35
40
60
60
70
80
100
80♦
100
200
250
300
350
400
400
450
500
500
600
600
LPS-RK_SP KRP-C_SP
CLASS RK1 CLASS L
MAXIMUM FUSE
200
250
250
350
350
400
500
500
500
650
800
800
1000
1350
1600
May be too small to allow some motors to start.
135
HP(FLC)
CONTACTOR
OLR
.75(1.3)
1(1.7)
1.5(2.4)
2(2.7)
3(3.9)
5(6.1)
7.5(9.0)
7.5(9.0)
10(11.0)
15(17.0)
15(17.0)
20(22.0)
30(32.0)
40(41.0)
50(52.0)
50(52.0)
60(62.0)
60(62.0)
75(77.0)
100(99.0)
125(125.0)
150(144.0)
150(144.0)
200(192.0)
200(192.0)
250(242.0)
300(289.0)
300(289.0)
350(336.0)
400(382.0)
500(472.0)
600(576.0)
800(770.0)
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D09
LC1D012
LC1D018
LC1D018
LC1D025
LC1D032
LC1D032
LC1D040
LC1D050
LC1D065
LC1D080
LC1D065
LC1D080
LC1F115
LC1F115
LC1F150
LC1F185
LC1F185
LC1F265
LC1F265
LC1F400
LC1F400
LC1F400
LC1F500
LC1F500
LC1F500
LC1F630
LC1F630
LR2D 1306
LR2D 1306
LR2D 1307
LR2D 1308
LR2D 1308
LR2D 1312
LR2D 1314
LR2D 1316
LR2D 1316
LR2D 1321
LR2D 1322
LR2D 1322
LR2D 3355
LR2D 3357
LR2D 3359
LR2D 3359
LR2D 3359
LR2D 3359
LR2D 3363
LR2F 5367
LR2F 5569
LR2F 5569
LR2F 5571
LR2F 5571
LR2F 6573
LR2F 6575
LR2F 6575
LR2F 6577
LR2F 6577
LR2F 6577
LR2F 7579
LR2F 7581
LR2F 8583
LPJ_SP
CLASS J
3
3
4
6
6
10
15
20
20
25
35
35
45♦
70
80
90
80♦
90♦
150
200
250
300
300
400
400
500
500
600
600
600
LPS-RK_SP KRP-C_SP
CLASS RK1 CLASS L
125
200
250
250
300
350
400
500
500
601
700
800
1000
1200
1600
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/Square D Co.
NEMA
200 Volt, Three-Phase Motors
230 Volt, Three Phase Motors
MAXIMUM FUSE
MAXIMUM FUSE
HP(FLC)
STARTER
SIZE
CATALOG #
HEATER
LPN-RK_SP
CLASS RK1
LPJ_SP
CLASS J
1.5(6.9)
2(7.8)
3(11.0)
5(17.5)
7.5(25.3)
10(32.2)
15(48.3)
20(62.1)
25(78.2)
30(92.0)
40(120.0)
50(150.0)
60(177.0)
75(221.0)
0
0
0
1
1
2
3
3
3
4
4
5
5
5
SB02V02S
SB02V02S
SB02V02S
SC03V02S
SC03V02S
SD01V02S
SE01V02S
SE01V02S
SE01V02S
SF01V02S
SF01V02S
SG01V02S**
SG01V02S**
SG01V02S**
B11.5*
B12.8
B19.5
B32
B50
B62
CC81.5
CC112
CC180
CC156
CC208
B3.70
B4.15
B5.50
12
15
17.5
25
40
50
70
100
125
150
175
225
300
350
15
15
20
30
45
60
80
100
125
150
200
250
300
400
HP(FLC)
1.5(6.0)
2(6.8)
3(9.6)
5(15.2)
7.5(22.0)
10(28.0)
15(42.0)
20(54.0)
25(68.0)
30(80.0)
40(104.0)
50(130.0)
60(154.0)
75(192.0)
100(248.0)
460 Volt, Three Phase Motors
STARTER
SIZE
0
0
0
1
1
2
3
3
3
3
4
5
5
5
5
CATALOG #
HEATER
SB02V02S
SB02V02S
SB02V02S
SC03V02S
SC03V02S
SD01V02S
SE01V02S
SE01V02S
SE01V02S
SE01V02S
SF01V02S
SG01V02S**
SG01V02S**
SG01V02S**
SG01V02S**
B10.2
B11.5*
B15.5
B28.0
B45
B50
CC68.5
CC94.0
CC132
CC196
CC180
B3.30
B3.70
B4.15
B6.25
3(4.8)
5(7.6)
7.5(11.0)
10(14.0)
15(21.0)
20(27.0)
25(34.0)
30(40.0)
40(52.0)
50(65.0)
60(77.0)
75(96.0)
100(124.0)
125(156.0)
150(180.0)
200(240.0)
STARTER
SIZE
0
0
1
1
2
2
2
3
3
3
4
4
5
5
5
5
CATALOG #
HEATER
SB02V02S
SB02V02S
SC03V02S
SC03V02S
SD01V02S
SD01V02S
SD01V02S
SE01V02S
SE01V02S
SE01V02S
SF01V02S
SF01V02S
SG01V02S**
SG01V02S**
SG01V02S**
SG01V02S**
B7.70*
B12.8
B19.5
B25
B36
B45
B70
CC64.3
CC87.7
CC121
CC121
CC167
B3.00
B3.70
B4.15
B6.25
LPS-RK_SP
CLASS RK1
8
15
17.5
20
30
40
50
60
80
100
125
150
200
225
300
400
MAXIMUM FUSE
LPJ _SP
CLASS J
9
15
20
25
35
45
60
70
90
110
125
175
200
250
300
400
HP(FLC)
3(3.9)
5(6.1)
7.5(9.0)
10(11.0)
15(17.0)
20(22.0)
25(27.0)
30(32.0)
40(41.0)
50(52.0)
60(62.0)
75(77.0)
100(99.0)
125(125.0)
150(144.0)
200(192.0)
* These overloads were not tested. Maximum fuse sizes are for the lower value of overload which was tested.
** Y500
†
LPJ _SP
CLASS J
12
15
17.5
30
50†
50
70
90
125
150
175
200
250
300
400
575 Volt, Three Phase Motors
MAXIMUM FUSE
HP(FLC)
LPN-RK_SP
CLASS RK1
10
12
17.5
25
35
45
70
80
110
125
175
200
225
300
400
Sized larger than code max for single motor.
136
STARTER
SIZE
0
0
1
1
2
2
2
3
3
3
4
4
4
5
5
5
CATALOG #
HEATER
SB02V02S
SB02V02S
SC03V02S
SC03V02S
SD01V02S
SD01V02S
SD01V02S
SE01V02S
SE01V02S
SE01V02S
SF01V02S
SF01V02S
SF01V02S
SG01V02S**
SG01V02S**
SG01V02S**
B6.25
B10.2
B15.5
B19.5
B28.0
B40
B45
CC50.1
CC68.5
CC87.7
CC103
CC121
CC167
B3.00
B3.70
B4.15
LPS-RK_SP
CLASS RK1
6
10
15
17.5
25
35
40
50
60
80
100
125
150
200
225
300
LPJ _SP
CLASS J
8
12
17.5
20
30
40
45
50
70
90
100
125
175
200
250
300
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/Siemens
IEC
200 Volt, Three-Phase Motors
230 Volt, Three-Phase Motors
MAXIMUM FUSE
MAXIMUM FUSE
HP(FLC)
STARTER
OLR
LPN-RK_SP
CLASS RK1
LPJ_SP
CLASS J
LP-CC
CLASS CC
HP(FLC)
STARTER
OLR
LPN-RK_SP
CLASS RK1
LPJ_SP
CLASS J
LP-CC
CLASS CC
.5(2.5)
.75(3.7)
1(4.8)
1(4.8)
1.5(6.9)
2(7.8)
3(11.0)
3(11.0)
5(17.5)
7.5(25.3)
10(32.2)
15(48.3)
20(62.1)
25(78.2)
30(92.0)
40(120.0)
50(150.0)
75(221.0)
75(221.0)
100(285.2)
125(359.0)
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF31/41
3TF31/41
3TF32/42
3TF34/44
3TF46
3TF46
3TF47
3TF48
3TF50
3TF50
31T52
3TF54
3TF54
3TF56
3TF56
3UA5000-1D
3UA5000-1E
3UA5000-1F
3UA5000-1G
3UA5000-1H
3UA5000-1J
3UA5000-1K
3UA5000-2S
3UA5200-2B
3UA5500-2D
3UA5800-2E
3UA5800-2T
3UA5800-2V
3UA5800-8W
3UA6000-2X
3UA6000-3J
3UA6200-3L
3UA6600-3C
3UA6600-3D
3UA6600-3D
3UA6600-3E
6
6
8
10
15
15
20
25†
30
50
60
90
125
175
200
250
300
400
450
500
500
6
6
8
10
15
15
20
25†
30
50
60
90
125
175
200
250
300
400
450
500
500♦
6
6♦
10
10
20
20
30
30
30♦
.5(2.2)
.75(3.2)
1(4.2)
1.5(6.0)
2(6.8)
3(9.6)
3(9.6)
5(15.2)
7.5(22.0)
10(28.0)
15(42.0)
20(54.0)
25(68.0)
30(80.0)
40(104.0)
50(130.0)
60(154.0)
75(192.0)
100(248.0)
125(312.0)
150(360.0)
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF31/41
3TF32/42
3TF33/43
3TF34/44
3TF46
3TF46
3TF47
3TF48
3TF50
3TF50
31T52
3TF54
3TF54
3TF56
3TF56
3UA5000-1C
3UA5000-1E
3UA5000-1F
3UA5000-1G
3UA5000-1H
3UA5000-1J
3UA5000-1J
3UA5200-2A
3UA5200-2C
3UA5500-2D
3UA5800-2F
3UA5800-2T
3UA5800-2V
3UA5800-8W
3UA6000-2X
3UA6000-3J
3UA6200-3L
3UA6600-3C
3UA6600-3D
3UA6600-3D
3UA6600-3E
2.8
6
8
10
15
15
15
25
40
50
70
90
125
175
200
250
300
400
450
500
500
3♦
6
8
10
15
15
15
25
40
50
70
90
125
175
200
250
300
400
450
500
500♦
3♦
6♦
10
10♦
20
20
20
30
30♦
460 Volt, Three-Phase Motors
MAXIMUM FUSE
HP(FLC)
STARTER
OLR
LPS-RK_SP
CLASS RK1
LPJ_SP
CLASS J
LP-CC
CLASS CC
.5(1.1)
.75(1.6)
1(2.1)
1.5(3.0)
2(3.4)
3(4.8)
3(4.8)
5(7.6)
5(7.6)
7.5(11.0)
7.5(11.0)
10(14.0)
15(21.0)
20(27.0)
25(34.0)
30(40.0)
40(52.0)
50(65.0)
60(77.0)
75(96.0)
100(124.0)
125(156.0)
150(180.0)
200(240.0)
250(302.0)
300(361.0)
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF30/40
3TF31/41
3TF31/41
3TF32/42
3TF33/43
3TF34/44
3TF46
3TF46
3TF46
3TF47
3TF48
3TF50
3TF50
31T52
3TF54
3TF54
3TF56
3TF56
3UA5000-1A
3UA5000-1A
3UA5000-1C
3UA5000-1D
3UA5000-1E
3UA5000-1F
3UA5000-1G
3UA5000-1H
3UA5000-1J
3UA5000-1K
3UA5000-2S
3UA5200-2A
3UA5200-2C
3UA5500-2D
3UA5800-2E
3UA5800-2F
3UA5800-2T
3UA5800-2V
3UA5800-8W
3UA6000-2X
3UA6000-3J
3UA6200-3L
3UA6600-3B
3UA6600-3C
3UA6600-3D
3UA6600-3E
1.6
1.6♦
2.8
6
6
8
10
15
15
20
25†
25
40
50
60
70
90
125
175†
200
250
300
300
400
500
500
2
2♦
3♦
6
6
8
10
15
15
20
25†
25
40
50
60
70
90
125
175†
200
250
300
300
400
500
500♦
2.25
2.25♦
3♦
6
6♦
10
10
20
20
30
30
30
30♦
♦
May be too small to allow some motors to start.
†
Sized larger than code max for single motor.
137
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/Siemens
NEMA
230 Volt, Three-Phase Motors
200 Volt, Three-Phase Motors
MAXIMUM FUSE
MAXIMUM FUSE
HP(FLC)
STARTER
OLR
LPN-RK_SP
CLASS RK1
LPJ_SP
CLASS J
LP-CC
CLASS CC
.5(2.5)
.75(3.7)
1(4.8)
1.5(6.9)
2(7.8)
3(11.0)
5(17.5)
7.5(25.3)
10(32.2)
15(48.3)
20(62.1)
25(78.2)
30(92.0)
40(120.0)
50(150.0)
60(177.0)
75(221.0)
SXLA
SXLA
SXLA
SXLA
SXLB
SXLB
SXLC
SXLC
SXLD
SXLE
SXLE
SXLE
SXLF
SXLF
SXLG
SXLG
SXLG
3UA5000-1D
3UA5000-1E
3UA5000-1F
3UA5000-1H
3UA5400-1J
3UA5400-1K
3UA5400-2B
3UA5400-2D
3UA5800-2E
3UA5800-2T
3UA5800-2V
3UA5800-8W
3UA6200-2X
3UA6200-3J
3UA6600-3B
3UA6600-3C
3UA6600-3D
6
6
8
15
15
20
30
50
60
90
125
175
200
250
300
400†
500†
6
6
8
15
15
20
30
50
60
90
125
175
200
250
300
400†
450
6
6♦
10
20
20
30
30♦
460 Volt, Three-Phase Motors
MAXIMUM FUSE
HP(FLC)
STARTER
OLR
LPS-RK_SP
CLASS RK1
LPJ_SP
CLASS J
LP-CC
CLASS CC
.5(1.1)
.75(1.6)
1(2.1)
1.5(3.0)
2(3.4)
3(4.8)
5(7.6)
7.5(11.0)
10(14.0)
15(21.0)
20(27.0)
25(34.0)
30(40.0)
40(52.0)
50(65.0)
60(77.0)
75(96.0)
100(124.0)
125(156.0)
150(180.0)
200(240.0)
SXLA
SXLA
SXLA
SXLA
SXLA
SXLB
SXLB
SXLC
SXLC
SXLD
SXLD
SXLD
SXLE
SXLE
SXLE
SXLF
SXLF
SXLF
SXLG
SXLG
SXLG
3UA5000-1A
3UA5000-1A
3UA5000-1C
3UA5000-1D
3UA5000-1E
3UA5400-1G
3UA5400-1H
3UA5400-1K
3UA5400-2A
3UA5800-2C
3UA5800-2D
3UA5800-2E
3UA5800-2F
3UA5800-2T
3UA5800-2V
3UA6200-2W
3UA6200-2X
3UA6200-3J
3UA6600-3B
3UA6600-3C
3UA6600-3D
1.6
1.6
2.8
6
6
10
15
20
25
40
50
60
70
90
125
175†
200
250
300
400
500
2
2♦
3♦
6
6
10
15
20
25
40
50
60
70
90
125
175†
200
250
300
400
450
2.25
2.25♦
3♦
6
6♦
10
20
30
30
30♦
♦
May be too small to allow some motors to start.
†
Sized larger than code max for single motor.
138
HP(FLC)
STARTER
OLR
LPN-RK_SP
CLASS RK1
LPJ_SP
CLASS J
LP-CC
CLASS CC
.5(2.2)
.75(3.2)
1(4.2)
1.5(6.0)
2(6.8)
3(9.6)
5(15.2)
7.5(22.0)
10(28.0)
15(42.0)
20(54.0)
25(68.0)
30(80.0)
40(104.0)
50(130.0)
60(154.0)
75(192.0)
100(248.0)
SXLA
SXLA
SXLA
SXLA
SXLB
SXLB
SXLC
SXLC
SXLD
SXLD
SXLE
SXLE
SXLE
SXLF
SXLF
SXLG
SXLG
SXLG
3UA5000-1C
3UA5000-1E
3UA5000-1F
3UA5000-1G
3UA5400-1H
3UA5400-1K
3UA5400-2B
3UA5400-2C
3UA5800-2D
3UA5800-2F
3UA5800-2T
3UA5800-2U
3UA5800-8W
3UA6200-3H
3UA6200-3J
3UA6600-3B
3UA6600-3C
3UA6600-3D
2.8
6
8
10
15
20
30
40
50
70
90
150
175
225
250
300
400
500
3♦
6
8
10
15
20
30
40
50
70
90
150
175
225
250
300
400
450
3♦
6♦
10
10♦
20
30
30
30♦
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/Cutler-Hammer
Freedom Series
IEC
230 Volt, Three-Phase Motors
200 Volt, Three-Phase Motors
HP(FLC)
STARTER
NUMBER
HEATER
ELEMENT
.5(2.5)
.75(3.7)
1(4.8)
1.5(6.9)
2(7.8)
3(11.0)
5(17.5)
7.5(25.3)
10(32.2)
15(48.3)
20(62.1)
25(78.2)
30(92.0)
40(119.6)
AE16ANSO_C
AE16ANSO_C
AE16ANSO_C
AE16ANSO_C
AE16BNSO_C
AE16CNSO_C
AE16DNSO_C
AE16ENSO_B
AE16HNSO_B
AE16JNSO_B
AE16KNSO_B
AE16LNSO_
AE16MNSO_
AE16NNSO_
H2106B-3
H2107B-3
H2108B-3
H2109B-3
H2110B-3
H2111B-3
H2112B-3
H2114B-3
H2115B-3
H2116B-3
H2117B-3
H2022-3
H2023-3
H2024-3
MAX. FUSE
LPJ_SP
LP-CC
CLASS J
CLASS CC
6
6
10
15
17.5
20
35
50
70
100
110
150
200
200
6
6♦
15
20
25
HEATER
ELEMENT
.5(2.2)
.75(3.2)
1(4.2)
1.5(6.0)
2(6.8)
3(9.6)
5(15.2)
7.5(22.0)
10(28.0)
15(42.0)
20(54.0)
25(68.2)
30(80.0)
40(104.0)
50(130.0)
AE16ANSO_C
AE16ANSO-C
AE16ANSO-C
AE16ANSO-C
AE16BNSO_C
AE16BNSO_C
AE16DNSO_C
AE16ENSO_C
AE16FNSO_B
AE16HNSO_B
AE16JNSO_B
AE16KNSO_B
AE16LNSO_
AE16MNSO_
AE16NNSO_
H2106B-3
H2107B-3
H2108B-3
H2109B-3
H2109B-3
H2110B-3
H2112B-3
H2113B-3
H2114B-3
H2116B-3
H2117B-3
H2117B-3
H2022-3
H2023-3
H2024-3
MAX. FUSE
LPJ_SP
LP-CC
CLASS J
CLASS CC
6
6
10
15
15
20
30
45
50
90
110
110
150
200
200
6
6♦
15
20
20
575 Volt, Three-Phase Motors
460 Volt, Three-Phase Motors
HP(FLC)
STARTER
NUMBER
HEATER
ELEMENT
.5(1.1)
.75(1.6)
1(2.1)
1.5(3.0)
2(3.4)
3(4.8)
5(7.6)
7.5(11.0)
10(14.0)
15(21.0)
20(27.0)
25(34.0)
30(40.0)
40(52.0)
50(65.0)
60(77.0)
75(96.0)
100(124.0)
AE16ANSO_C
AE16ANSO_C
AE16ANSO_C
AE16ANSO_C
AE16ANSO_C
AE16ANSO_C
AE16BNSO_C
AE16CNSO_C
AE16DNSO_C
AE16ENSO_C
AE16FNSO_B
AE16GNSO_B
AE16HNSO_B
AE16JNSO_B
AE16KNSO_B
AE16LNSO_
AE16MNSO_
AE16NNSO_
H2104B-3
H2105B-3
H2106B-3
H2106B-3
H2107B-3
H2108B-3
H2110B-3
H2111B-3
H2111B-3
H2113B-3
H2114B-3
H2115B-3
H2116B-3
H2116B-3
H2117B_3
H2022-3
H2023-3
H2024-3
MAX. FUSE
LPJ_SP
LP-CC
CLASS J
CLASS CC
3
3
6
6
6
10
15
20
30
45
50
70
90
100
110
150
200
200
3
3♦
6
6
6♦
15
25
“-” - Empty space designates where coil suffix must be added.
♦
HP(FLC)
STARTER
NUMBER
May be too small to allow some motors to start.
139
HP(FLC)
STARTER
NUMBER
HEATER
ELEMENT
.75(1.3)
1(1.7)
1.5(2.4)
2(2.7)
3(3.9)
5(6.1)
7.5(9.0)
10(11.0)
15(17.0)
20(22.0)
25(27.0)
30(32.0)
40(41.0)
50(52.0)
60(62.0)
75(77.0)
100(99.0)
125(125.0)
AE16ANSO_C
AE16ANSO_C
AE16ANSO_C
AE16ANSO_C
AE16ANSO_C
AE16ANSO_C
AE16BNSO_C
AE16CNSO_C
AE16DNSO_C
AE16ENSO_C
AE16FNSO_B
AE16GNSO_B
AE16HNSO_B
AE16KNSO_B
AE16LNSO_
AE16LNSO_
AE16MNSO_
AE16NNSO_
H2104B-3
H2105B-3
H2106B-3
H2107B-3
H2108B-3
H2109B-3
H2110B-3
H2111B-3
H2112B-3
H2113B-3
H2114B-3
H2115B-3
H2116B-3
H2116B-3
H2021-3
H2022-3
H2023-3
H2024-3
MAX. FUSE
LPJ_SP
LP-CC
CLASS J
CLASS CC
3
3
6
6
10
15
20
20
35
45
50
70
90
100
110
150
200
200
3
3♦
6
6
15
20
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/Cutler-Hammer
Freedom Series
IEC
230 Volt, Three-Phase Motors
200 Volt, Three-Phase Motors
HP(FLC)
.5(2.5)
.75(3.7)
1(4.8)
1.5(6.9)
2(7.8)
3(11.0)
5(17.5)
7.5(25.3)
10(32.2)
15(48.3)
20(62.1)
STARTER
NUMBER
(Fixed Heaters)
AE17ANSO_FJ
AE17ANSO_FK
AE17ANSO_FL
AE17ANSO_FM
AE17BNSO_FP
AE17CNSO_FQ
AE17DNSO_FR
AE17FNSO_FT
AE17HNSO_KC
AE17JNSO_KE
AE17KNSO_KF
MAX. FUSE
LPJ_SP
LP-CC
CLASS J
CLASS CC
6
6
6
6
10
15
15
15
17.5
25
20
20♦
35
50
70
100
110
HP(FLC)
.5(2.2)
.75(3.2)
1(4.2)
1.5(6.0)
2(6.8)
3(9.6)
5(15.2)
7.5(22.0)
10(28.0)
15(42.0)
20(54.0)
25(68.2)
HP(FLC)
.5(1.0)
.75(1.6)
1(2.1)
1.5(3.0)
2(3.4)
3(4.8)
5(7.6)
7.5(11.0)
10(14.0)
15(21.0)
20(27.0)
25(34.0)
30(40.0)
40(52.0)
50(65.0)
MAX. FUSE
LPJ_SP
LP-CC
CLASS J
CLASS CC
2
2
3
3
3
3♦
6
6
6
6♦
10
15
15
15
20
20♦
30
30♦
45
60
70
90
110
110
HP(FLC)
.75(1.3)
1(1.7)
1.5(2.4)
2(2.7)
3(3.9)
5(6.1)
7.5(9.0)
10(11.0)
15(17.0)
20(22.0)
25(27.0)
30(32.0)
40(41.0)
50(52.0)
“-” - Empty space designates where coil suffix must be added.
♦
MAX. FUSE
LPJ_SP
LP-CC
CLASS J
CLASS CC
3♦
3♦
6
6♦
6♦
6♦
15
15
15
15
20
20♦
30
30♦
45
60
90
110
110
575 Volt, Three-Phase Motors
460 Volt, Three-Phase Motors
STARTER
NUMBER
(Fixed Heaters)
AE17ANSO_FF
AE17ANSO_FG
AE17ANSO_FH
AE17ANSO_FJ
AE17ANSO_FK
AE17ANSO_FM
AE17BNSO_FN
AE17CNSO_FQ
AE17DNSO_FR
AE17ENSO_FS
AE17FNSO_FT
AE17GNSO_KC
AE17HNSO_KD
AE17JNSO_KE
AE17KNSO_KF
STARTER
NUMBER
(Fixed Heaters)
AE17ANSO_FH
AE17ANSO_FK
AE17ANSO_FK
AE17ANSO_FM
AE17BNSO_FN
AE17CNSO_FP
AE17DNSO_FR
AE17ENSO_FS
AE17FNSO_FT
AE17HNSO_KD
AE17JNSO_KE
AE17KNSO_KF
May be too small to allow some motors to start.
140
STARTER
NUMBER
(Fixed Heaters)
AE17ANSO_FF
AE17ANSO_FG
AE17ANSO_FH
AE17ANSO_FJ
AE17ANSO-FL
AE17ANSO_FM
AE17BNSO-FP
AE17CNSO_FQ
AE17DNSO_FR
AE17ENSO_FS
AE17FNSO_FT
AE17GNSO_KC
AE17HNSO_KD
AE17KNSO_KE
MAX. FUSE
LPJ_SP
LP-CC
CLASS J
CLASS CC
2
2♦
3
3♦
3♦
3♦
6
6
10
15
15
15
20
20♦
20
20♦
35
45
60
70
90
110
MOTOR CONTROLLER AND FUSE
SELECTION TABLE FOR TYPE 2 PROTECTION
(UL & CSA VERIFIED)
C O O R D I N AT E D
PROTECTION
Bussmann®/Cutler-Hammer
Freedom Series
NEMA
200 Volt, Three-Phase Motors
HP(FLC)
.5(2.5)
.75(3.7)
1(4.8)
1.5(6.9)
2(7.8)
3(11.0)
7.5(25.3)
10(32.2)
15(48.3)
20(62.1)
25(78.2)
40(119.6)
50(149.5)
60(166.8)
75(220.8)
SIZE
00
00
00
0
0
0
1
2
3
3
3
4
5
5
5
STARTER
CAT. #
AN16AN0_C
AN16ANO_C
AN16ANO_C
AN16NDO_C
AN16BNO_C
AN16BNO_C
AN16DNO_B
AN16GNO_B
AN16KNO_
AN16KNO_
AN16KNO
AN16NNO_
AN16SNO_B
AN16SNO_B
AN16SNO_B
230 Volt, Three-Phase Motors
HEATER
ELEMENT
H2006B-3
H2008B-3
H2009B-3
H2010B-3
H2010B-3
H2011B-3
H2013B-3
H2015B-3
H2021-3
H2021-3
H2022-3
H2024-3
H2007B-3
H2007B-3
H2008B-3
MAX. FUSE
LPN-RK_SP
CLASS RK1
4.5
8
10
15
17.5
20
45
70
100
110
175
200
300
350
400
HEATER
ELEMENT
H2004B-3
H2005B-3
H2006B-3
H2007B-3
H2008B-3
H2009B-3
H2010B-3
H2011B-3
H2012B-3
H2013B-3
H2014B-3
H2015B-3
H2020-3
H2021-3
H2022-3
H2022-3
H2023-3
H2024-3
H2007B-3
H2007B-3
H2008B-3
MAX. FUSE
LPS-RK_SP
CLASS RK1
2
2.8
4.5
5.6
7
10
15
20
30
45
60
70
80
110
125
150
200
200
350
400
400
HP(FLC)
.5(2.2)
.75(3.2)
1(4.2)
1.5(6.0)
2(6.8)
3(9.6)
5(15.2)
7.5(22.0)
7.5(22.0)
10(28.0)
15(42.0)
20(54.0)
25(68.2)
30(80.0)
30(92.0)
40(104.0)
50(130.0)
60(145.0)
75(192.0)
100(248.0)
HP(FLC)
.5(1.1)
.75(1.6)
1(2.1)
1.5(3.0)
2(3.4)
3(4.8)
5(7.6)
7.5(11.0)
10(14.0)
15(21.0)
20(27.0)
25(34.0)
30(40.0)
40(52.0)
50(65.0)
60(77.0)
75(96.0)
100(124.0)
125(156.0)
150(180.0)
200(240.0)
SIZE
00
00
00
00
00
0
0
1
1
2
2
2
3
3
3
4
4
4
5
5
5
HEATER
ELEMENT
H2006B-3
H2007B-3
H2008B-3
H2009B-3
H2009B-3
H2011B-3
H2012B-3
H2013B-3
H2013B-3
H2014B-3
H2015B-3
H2021-3
H2022-3
H2022-3
H2023-3
H2023-3
H2024-3
H2007B-3
H2007B-3
H2008B-3
MAX. FUSE
LPN-RK_SP
CLASS RK1
4.5
5.6
8
12
12
20
30
45
45
60
70
110
150
175
200
200
200
300
400
400
HEATER
ELEMENT
H2005B-3
H2005B-3
H2006B-3
H2007B-3
H2008B-3
H2009B-3
H2010B-3
H2011B-3
H2012B-3
H2013B-3
H2014B-3
H2019-3
H2020-3
H2021-3
H2021-3
H2022-3
H2023-3
H2006B-3
H2007B-3
H2007B-3
MAX. FUSE
LPS-RK_SP
CLASS RK1
2.8
2.8
4.5
5.6
8
12
17.5
20
35
45
60
60
80
110
110
150
200
250
300
400
575 Volt, Three-Phase Motors
460 Volt, Three-Phase Motors
STARTER
CAT. #
AN16ANO_C
AN16ANO_C
AN16ANO_C
AN16ANO_C
AN16ANO_C
AN16BNO_C
AN16BNO_C
AN16DNO_B
AN16DNO_B
AN16GNO_B
AN16GNO_B
AN16GNO_B
AN16KNO_
AN16KNO_
AN16KNO_
AN16NNO_
AN16NNO_
AN16NNO_
AN16SNO_B
AN16SNO_B
AN16SNO_B
SIZE
00
00
00
00
0
0
1
1
2
2
2
3
3
3
4
4
4
5
5
5
STARTER
CAT. #
AN16ANO_C
AN16ANO_C
AN16ANO_C
AN16ANO_C
AN16BNO_C
AN16BNO_C
AN16DNO_B
AN16DNO_B
AN16GNO_B
AN16GNO_B
AN16GNO_B
AN16KNO_
AN16KNO_
AN16KNO_
AN16NNO_
AN16NNO_
AN16NNO_
AN16SNO_B
AN16SNO_B
AN16SNO_B
HP(FLC)
.75(1.3)
1(1.7)
1.5(2.4)
2(2.7)
3(3.9)
5(6.1)
7.5(9.0)
10(11.0)
15(17.0)
20(22.0)
25(27.0)
30(32.0)
40(41.0)
50(52.0)
60(62.0)
75(77.0)
100(99.0)
125(125.0)
150(144.0)
200(192.0)
“_” - Empty space designates where coil suffix must be added.
141
SIZE
00
00
00
00
0
0
1
1
2
2
2
3
3
3
4
4
4
5
5
5
STARTER
CAT. #
AN16ANO_C
AN16ANO_C
AN16ANO_C
AN16ANO_C
AN16BNO_C
AN16BNO_C
AN16DNO_B
AN16DNO_B
AN16GNO_B
AN16GNO_B
AN16GNO_B
AN16KNO_
AN16KNO_
AN16KNO_
AN16NNO_
AN16NNO_
AN16NNO_
AN16SNO_B
AN16SNO_B
AN16SNO_B