A British Standard Unenclosed Non Fused Load Break Switch 400

Bussmann
®
A British Standard Unenclosed
Non Fused Load Break Switch 400 and 630A
BDNFP
Conforms to IEC 947
Regulations, Standards
VDE 0660T100
IEC947-1
VDE 0660T107
IEC947-3
Safety Features
• clear indication ON / OFF
• quick make - break action ensures independent operation
• positive forced opening of contacts
EN 60947-1
EN 60947-3
Application
The new generation of BDNFP load break switches and load
break disconnectors have been designed for:
• distribution boards
• load centres
• MCC motor-control-centres
• control panels.
Design Features
• modular system, small dimensions
• excellent electrical performance
• high short circuit capacity
• various accessories
Dimensional Information for 400 Amp (mm) (not to scale)
25
48
45
M10
ø6.2 x 12
ø6.2 x 8
126
68
126
210
185
150
120
Ø14
98
186
33
188
Neutral Link
4
152
190
48
200
Triple Pole and Neutral
4 Pole
This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the
end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any
products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update,
without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested
by the user in all possible applications.
Bussmann Division
Cooper (U.K.) Ltd
Burton-on-the-Wolds
Leicestershire, LE12 5TH
United Kingdom
Tel: (44) (0)1509 88 27 37
Fax: (44) (0)1509 88 27 86
Head Office
St. Louis, MO, U.S.A. Tel: (314) 527-3877 Fax: (800) 544-2570 International Fax: (314) 527-1445
B i F
Bussmann Information Fax (00 1) 314 527 1450
BDNFP 04.97
Doc. No. 4205
Page 1 of 3
Bussmann
®
A British Standard Unenclosed
Non Fused Load Break Switch 400 and 630A
BDNFP
Conforms to IEC 947
Characteristics for 400A
Electrical
Rated current Ie open
enclosed
Operational current
AC21, cos ϕ 0,95
IEC947-3
Breaking capacity
AC21, cos ϕ 0,95
IEC947-3
Operational power
AC23, cos ϕ 0,35
45 deg C
500V
690V
BS 88 Fuse size
(if applicable)
Mechanical
Mechanical Endurance
Type 3-pole
Art.-No.
Net weight
Packed weight
400A Rated operational voltage
55 deg C 400A
45 deg C 400A
55 deg C 400A
415V
400A
500V
400A
690V
400A
415V
600A
500V
600A
690V
600A
415V
200kW
1000V
3500V
Operational current
415V
AC22, cos ϕ 0,65
500V
IEC947-3
690V
Breaking capacity
415V
AC22, cos ϕ 0,65
500V
IEC947-3
690V
Short circuit making capacity (Is)
400A
400A
400A
1200A
1200A
1200A
32kA
220kW Rated fused S/C current RMS with
230kW max HRC fuse type gl
Electrical endurance
415V
AC21, cos ϕ 0,95
500V
AC22, cos ϕ 0,65
690V
3 x 103 Ops
117036
4.5kg
690V Frequency
Rated insulation voltage
Test insulation voltage
Cable Size
Max. cross section
Type 3-pole+N
Art.-No.
Net weight
Packed weight
40 - 60Hz
Operational current
415V
AC23, cos ϕ 0,35
500V
IEC947-3
690V
Breaking capacity
415V
AC23, cos ϕ 0,35
500V
IEC947-3
690V
Rated short time current
400A
400A
250A
2500A
2500A
1500A
24.5kA
50kA 1 sec. RMS value
400A
300 Ops Electrical endurance
300 Ops AC23, cos ϕ 0,35
200 Ops
415V 200 Ops
500V 150 Ops
690V 100 Ops
Max. terminal torque
Max. lug width
12.5 - 20 Nm
35mm
240mm2
Accessories
Terminal Shrouds: 19130301
Red/Yellow handle: 190372
Additional extension shafts:
190503
(Standard shaft for depth up to 300mm)
Auxiliary Contacts:191403 (1NO + 1NC)
BDNFP 04.97
Doc. No. 4205
Page 2 of 3
Bussmann
®
A British Standard Unenclosed
Non Fused Load Break Switch 400 and 630A
BDNFP
Conforms to IEC 947
Dimensional Information for 630 Amp (mm) (not to scale)
25
48
45
ø14
ø6.2 x 8
ø6.2 x 8
126
68
126
220
190
150
120
Ø14
35
98
186
188
Neutral Link
6
152
190
48
200
Triple Pole and Neutral
4 Pole
Characteristics for 630A
Electrical
Rated current Ie open
enclosed
Operational current
AC21, cos ϕ 0,95
IEC947-3
Breaking capacity
AC21, cos ϕ 0,95
IEC947-3
Operational power
AC23, cos ϕ 0,35
45 deg C
Mechanical
Type 3-pole
Art.-No.
Net weight
Packed weight
690V Frequency
630A
600A
550A
630A
630A
630A
1200A
1200A
1200A
315kW
500V
690V
315kW Rated fused S/C current RMS with
295kW max HRC fuse type gl
Electrical endurance
415V
AC21, cos ϕ 0,95
500V
AC22, cos ϕ 0,65
690V
BS 88 Fuse size
(if applicable)
Mechanical Endurance
630A Rated operational voltage
55 deg C
45 deg C
55 deg C
415V
500V
690V
415V
500V
690V
415V
3 x 103 Ops
117044
4.5kg
Rated insulation voltage
Test insulation voltage
1000V
3500V
Operational current
415V
AC22, cos ϕ 0,65
500V
IEC947-3
690V
Breaking capacity
415V
AC22, cos ϕ 0,65
500V
IEC947-3
690V
Short circuit making capacity (Is)
630A
630A
630A
1890A
1890A
1890A
34.5kA
Cable Size
Max. cross section
Type 3-pole+N
Art.-No.
Net weight
Packed weight
Operational current
415V
AC23, cos ϕ 0,35
500V
IEC947-3
690V
Breaking capacity
415V
AC23, cos ϕ 0,35
500V
IEC947-3
690V
Rated short time current
50kA 1 sec. RMS value
630A
300 Ops Electrical endurance
200 Ops AC23, cos ϕ 0,35
150 Ops
2 x 240mm2
40 - 60Hz
Max. terminal torque
Max. lug width
630A
630A
400A
3600A
3600A
2400A
28.5kA
415V 150 Ops
500V 100 Ops
690V 50 Ops
20 - 30 Nm
35mm
Accessories
Terminal Shrouds: 19130301
Red/Yellow handle: 190372
Additional extension shafts:
190503
(Standard shaft for depth up to 300mm)
Auxiliary Contacts:191403 (1NO + 1NC)
BDNFP 04.97
Doc. No. 4205
Page 3 of 3