Bussmann® E-Rated Fuses For Potential & Small Power Trans. Medium Voltage JCD, JCW, JCE JCQ, JCI, & JCT • Low amperage, E-Rated medium voltage fuses are general purpose current limiting fuses. • The E rating defines the melting-time-current characteristic of the fuse and permits electrical interchangeability of fuses with the same E Rating. • For a general purpose fuse to have an E Rating the following condition must be met: The current responsive element shall melt in 300 seconds at a rms current within the range of 200% to 240% of the continuous current rating of the fuse, fuse refill, or link. (For fuses rated 100E or less)(ANSI C37.46). • Bussmann low amperage, E-Rated fuses are designed to provide primary protection for potential, small service, and control transformers. • These fuses offer a high level of fault current interruption in a self-contained non-venting package which can be mounted indoors or in an enclosure. Catalog Symbol: JCD, JCW, JCE, JCQ, JCI, AND JCT E-Rated Current Limiting Indicating/Non-Indicating Plated Ferrules Voltage Ratings: (Max. Design): 2750, 5500, 8300, 15,500 VOLT Current Ratings: 1/2E THRU 10E No Agency Listings 2-27-02 SB02090 Form No. JCD, JCW, JCE, JCQ, JCI, and JCT Page 1 of 2 Data Sheet: 6002 Bussmann® E-Rated Fuses JCD, JCW, JCE JCQ, JCI, & JCT For Potential & Small Power Trans. Medium Voltage Dimensional Data A C B Specifications Buss Catalog No. Amperage Maximum Design Voltage Dimensions (Inches) A B C Construction Maximum Interrupting Capacity Amps (Asym.) Amps (Sym.) 2400V; E-Rated Fuse; Indicating JCD-1/2E .50E 2750V 4.5 0.8 0.63 Single 100,000 63,000 JCD-1E 1.0E 2750V 4.5 0.8 0.63 Single 63,000 40,000 JCD-2E 2.0E 2750V 4.5 0.8 0.63 Single 63,000 40,000 JCD-5E 5.0E 2750V 4.5 0.8 0.63 Single 40,000 25,000 2400/4800V; E-Rated Fuse; Non-Indicating JCW-1/2E .5E 2750V/5500V 7.31 1.56 1.38 Single 60,000 40,000 JCW-1E 1E 2750V/5500V 7.31 1.56 1.38 Single 60,000 40,000 JCW-2E 2E 2750V/5500V 7.31 1.56 1.38 Single 60,000 40,000 JCW-3E 3E 2750V/5500V 7.31 1.56 1.38 Single 60,000 40,000 JCW-4E 4E 2750V/5500V 7.31 1.56 1.38 Single 60,000 40,000 JCW-5E 5E 2750V/5500V 7.31 1.56 1.38 Single 60,000 40,000 5500V; E-Rated Fuse; Non-Indicating JCE-1/2E .5E 5500V 5.6 0.81 0.63 Single 60,000 50,000 JCE-1E 1E 5500V 5.6 0.81 0.63 Single 60,000 50,000 JCE-2E 2E 5500V 5.6 0.81 0.63 Single 60,000 50,000 JCE-3E 3E 5500V 5.6 0.81 0.63 Single 60,000 50,000 JCE-4E 4E 5500V 5.6 0.81 0.63 Single 60,000 50,000 JCE-5E 5E 5500V 5.6 0.81 0.63 Single 60,000 50,000 4800V; E-Rated Fuse; Indicating JCQ-1/2E .5E 5500V 9.5 1.6 1.38 Single 130,000 80,000 JCQ-1E 1.0E 5500V 9.5 1.6 1.38 Single 130,000 80,000 JCQ-1-1/2E 1.5E 5500V 9.5 1.6 1.38 Single 130,000 80,000 JCQ-3E 3.0E 5500V 9.44 1.6 1.38 Single 130,000 80,000 JCQ-5E 5.0E 5500V 9.44 1.6 1.38 Single 130,000 80,000 JCQ-10E 10.0E 5500V 9.44 1.6 1.38 Single 130,000 80,000 7200V; E-Rated Fuse; Indicating JCI-1/2E .50E 8300V 9.5 1.6 1.38 Single 130,000 80,000 JCI-3E 3.0E 8300V 12.88 1.6 1.38 Single 130,000 80,000 JCI-5E 5.0E 8300V 12.88 1.6 1.38 Single 130,000 80,000 JCI-10E 10.0E 8300V 12.88 1.6 1.38 Single 130,000 80,000 14,400V; E-Rated Fuse; Indicating JCT-1/2E .5E 15500V 12.93 1.6 1.38 Single 130,000 80,000 JCT-1E 1.0E 15500V 12.93 1.6 1.38 Single 130,000 80,000 JCT-1-1/2E 1.5E 15500V 12.93 1.6 1.38 Single 130,000 80,000 JCT-3E 3.0E 15500V 17.5 1.6 1.38 Single 130,000 80,000 JCT-5E 5.0E 15500V 17.5 1.6 1.38 Single 130,000 80,000 JCT-10E 10.0E 15500V 17.5 1.6 1.38 Single 130,000 80,000 Fuse clip for 1.6” Diameter Fuses - 1A0835 Fuse clip for 0.81” Diameter Fuses - 1A1837 The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 2-27-02 SB02090 Form No. JCD, JCW, JCE, JCQ, JCI, and JCT Page 2 of 2 Data Sheet: 6002