Mechanical Specification DC OK Relay Contact Output

Mechanical Specification
85
124
142
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
4
5
Assignment
(1 phase)
N / AC
L / AC
Jumper 115V AC
Jumper 115V AC
FG
TB2 Terminal Pin. No Assignment
Pin No.
1,2
3,4
5,6
Assignment
DC output -V
DC output +V
DC OK relay contacts
DC OK Relay Contact
Outputs are used for preventive function monitoring of the power
supply. An electrically isolated signal contact is available. The
signal contact closes when the output power is OK and opens
when the output voltage falls below 20Vdc ±5%.
Output Derating Curve
Parallel Connection
A parallel connection with the same model
power supply can be set up to increase the
output power. The output has to be adjusted
approximately to the same value (± 20mV) while
applying a 1-2 A load to all devices before
connecting them in parallel. In PSA-600xx, for
more power, the position of the Easy Parallel
jumper needs to be changed to enable a parallel
connection. In this mode up to 4 power supplies
can be put together in parallel.
+
AC
DC
–
+
AC
DC
–
+
–
LOAD
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.