PSC-60 Series

PSC-60 Series
E361935
OUTPUT
Features:
•
•
•
•
•
•
•
•
•
•
•
•
E205412
Universal AC input (88-264V AC)
Protections: Short Circuit / Overload / Overvoltage
Brown-out protection
Installed on DIN rail TS35 / 7.5 or 15
True DC OK signal output
All wiring 105°C long life electrolytic capacitors
High operation temperature up to 70°C
Withstands 2G vibration test
High efficiency, long life and high reliability
3 year warranty
UL1310 Class 2 Power unit / LPS pass
UL508 (Industrial control equipment) listed
Cat. No.
PSC-6012
PSC-6015
PSC-6024
PSC-6048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
12V
5A
0 ~ 5A
60W
100mVp-p
15V
4A
0 ~ 4A
60W
100mVp-p
24V
2.5A
0 ~ 2.5A
60W
120mVp-p
48V
1.25A
0 ~ 1.25A
60W
180mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
10.8 ~ 13.2V
±1.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
±1.0%
±1.0%
±1.0%
±1.0%
< 800ms, < 50ms / 230VAC at full load
HOLD UP TIME (Typ.)
> 32ms / 230VAC; >16ms / 115VAC at full load
VOLTAGE RANGE
88 ~ 264VAC; 124 ~ 370VDC
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
47~63Hz
86%
87%
1.3 A / 115VAC; 0.6A / 230VAC
COLD START 30A / 115VAC; 60A / 230VAC
<1mA / 230VAC
Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor
13.5 ~ 16.5V
±1.0%
21.6 ~ 26.4V
±1.0%
43.2 ~ 52.8V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
INPUT
±1.0%
±1.0%
±1.0%
±1.0%
Length of set up time is measured at sold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
Derating may apply in low input voltage. Please check the derating curve for more details.
PROTECTION
OVER LOAD PROTECTION
87%
88%
> 102% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE PROTECTION
115% ~ 150% rated output voltage
Protection type: latch-off mode
OVER TEMPERATURE PROTECTION
Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
re-power on to recover
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP. / HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-20 ~ +70˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C; 10 ~ 95% RH
±0.03% / ˚C (0 ~ 50˚C)
10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
UL508, TUV EN60950-1:2006+A11, UL1310 NEC class 2 compliant
I/P-O/P: 4242DC, I/P-FG: 2121DC 1 minute
I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC
EN55022: 2006 Class B
EN61000-3-2: 2006 Class A, EN61000-3-3: 1995+A1: 2001+A2: 2005
EN61204-3: 2000, EN55024: 1998+A1:2001+A2: 2003 light industry level, criteria A
ENVIRONMENT
SAFETY & EMC
The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives.
OUTPUT
DC OK Signal
MTBF
DIMENSION
PACKING
CONNECTION
COOLING
Relay contact (24VDC / 1A, 120VAC / 1A)
944.6K HRS MIL-HDBK-217F
40x90x99 mm (WxHxD)
0.3kg; 27pcs / 9.3kg
I/P: 3 poles, O/P: 6 poles screw DIN terminal
Free air convection
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
16