PSC-60 Series E361935 OUTPUT Features: • • • • • • • • • • • • E205412 Universal AC input (88-264V AC) Protections: Short Circuit / Overload / Overvoltage Brown-out protection Installed on DIN rail TS35 / 7.5 or 15 True DC OK signal output All wiring 105°C long life electrolytic capacitors High operation temperature up to 70°C Withstands 2G vibration test High efficiency, long life and high reliability 3 year warranty UL1310 Class 2 Power unit / LPS pass UL508 (Industrial control equipment) listed Cat. No. PSC-6012 PSC-6015 PSC-6024 PSC-6048 DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER RIPPLE & NOISE (max) 12V 5A 0 ~ 5A 60W 100mVp-p 15V 4A 0 ~ 4A 60W 100mVp-p 24V 2.5A 0 ~ 2.5A 60W 120mVp-p 48V 1.25A 0 ~ 1.25A 60W 180mVp-p VOLTAGE ADJ. RANGE VOLTAGE TOLERANCE 10.8 ~ 13.2V ±1.0% LINE REGULATION LOAD REGULATION SETUP, RISE TIME ±1.0% ±1.0% ±1.0% ±1.0% < 800ms, < 50ms / 230VAC at full load HOLD UP TIME (Typ.) > 32ms / 230VAC; >16ms / 115VAC at full load VOLTAGE RANGE 88 ~ 264VAC; 124 ~ 370VDC FREQUENCY RANGE EFFICIENCY (Typ.) AC CURRENT (Typ.) INRUSH CURRENT (Typ.) LEAKAGE CURRENT 47~63Hz 86% 87% 1.3 A / 115VAC; 0.6A / 230VAC COLD START 30A / 115VAC; 60A / 230VAC <1mA / 230VAC Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor 13.5 ~ 16.5V ±1.0% 21.6 ~ 26.4V ±1.0% 43.2 ~ 52.8V ±1.0% Tolerance: includes set up tolerance, line regulation and load regulation. INPUT ±1.0% ±1.0% ±1.0% ±1.0% Length of set up time is measured at sold first start. Turning ON/OFF the power supply may lead to increase of the set up time. Derating may apply in low input voltage. Please check the derating curve for more details. PROTECTION OVER LOAD PROTECTION 87% 88% > 102% rated output power Protection type: Constant current limiting, recovers automatically after fault condition is removed OVER VOLTAGE PROTECTION 115% ~ 150% rated output voltage Protection type: latch-off mode OVER TEMPERATURE PROTECTION Power supply shut down at 70˚C constant current limiting / output voltage goes to 0; re-power on to recover WORKING TEMP. WORKING HUMIDITY STORAGE TEMP. / HUMIDITY TEMP. COEFFICIENT VIBRATION -20 ~ +70˚C (Refer to output load derating curve) 20 ~ 90% RH non-condensing -40 ~ +85˚C; 10 ~ 95% RH ±0.03% / ˚C (0 ~ 50˚C) 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes SAFETY STANDARDS WITHSTAND VOLTAGE ISOLATION RESISTANCE EMI CONDUCTION & RADIATION HARMONIC CURRENT EMS IMMUNITY UL508, TUV EN60950-1:2006+A11, UL1310 NEC class 2 compliant I/P-O/P: 4242DC, I/P-FG: 2121DC 1 minute I/P-O/P, I/P-FG, O/P-FG: 100M Ohms/500VDC EN55022: 2006 Class B EN61000-3-2: 2006 Class A, EN61000-3-3: 1995+A1: 2001+A2: 2005 EN61204-3: 2000, EN55024: 1998+A1:2001+A2: 2003 light industry level, criteria A ENVIRONMENT SAFETY & EMC The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. OUTPUT DC OK Signal MTBF DIMENSION PACKING CONNECTION COOLING Relay contact (24VDC / 1A, 120VAC / 1A) 944.6K HRS MIL-HDBK-217F 40x90x99 mm (WxHxD) 0.3kg; 27pcs / 9.3kg I/P: 3 poles, O/P: 6 poles screw DIN terminal Free air convection All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature. For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power. 16