Specifications
OUTPUT
Features:
Cat. No.
PS-S10012
PS-S10024
PS-S10048
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
RIPPLE & NOISE (max)
12V
7.5A
0 ~ 7.5A
90W
120mVp-p
24V
4A
0 ~ 4A
96W
150mVp-p
48V
2A
0 ~ 2A
96W
200mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
12 ~ 15V
±1.0%
24 ~ 30V
±1.0%
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
±1.0%
±1.0%
±1.0%
±1.0%
3000ms, 50ms/230VAC; 3000ms, 50ms/115VAC at full load
48 ~ 56V
±1.0%
Tolerance: includes set up tolerance, line regulation and load regulation.
±1.0%
±1.0%
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
INPUT
HOLD UP TIME (Typ.)
VOLTAGE RANGE
50ms/230VAC; 20ms/115VAC at full load
85 ~ 264VAC
120 ~ 370VDC
Derating maybe needed under low input voltages, please check the derating curve for more detail
PROTECTION
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (max)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
47~63Hz
PF ≥ 0.95/230VAC; PF ≥ 0.98/115VAC at full load
85%
86%
1.3A/115VAC; 0.8A/230VAC
COLD START: 30A/115VAC; 60A/230VAC
≤1mA/ 240VAC
88%
105% ~ 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
OVERVOLTAGE
15.6 ~ 18V
31.2 ~ 36V
57.6 ~ 64.8V
Protection type: Shut down overvoltage, re-power on to recover
OVERTEMPERATURE
90˚C ± 10˚C (RTH2) detect on heat sink of power transistor
SHORT CIRCUIT PROTECTION
Protection type: Shut down overvoltage, re-power on to recover
ENVIRONMENT
DC OK AKTIV SIGNAL (max.)
Power supply shut down at 70˚C constant current limiting / output voltage goes to 0;
re-power on to recover
Relay contact rating (max.): 30V/1A resistive
SAFETY & EMC
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MOUNTING
-10 ~ +60˚C (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85˚C, 10 ~ 95% RH
±0.03% ˚C (0 ~ 50˚C)
Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes
Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508
EN60950-1 compliant
I/P-O/P: 3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms/500VDC/25˚C/70% RH
Compliance to EN55011
EN55022 (CISPR22)
EN61204-3 Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204; EN61000-6-2; EN61204-3;
light industry level; criteria A
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
The power supply is considered a component which will installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
OTHERS
MTBF
DIMENSION
PACKING
346K hrs min. MIL-HDBK-217K (25˚C)
55x90x100mm (WxHxD)
0.42Kg; 30pcs / 13.6Kg / 0.82CUFT
All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
70
Mechanical Specification
Terminal Pin. No Assign. (TB1)
Pin No.
1
2
3
Assignment
FG
AC/N
AC/L
Terminal Pin. No Assign. (TB2)
Pin No. Assignment
1,2
DC OUTPUT +V
DC OUTPUT -V
3,4
DC OK RELAY CONTACT
5,6
Block Diagram
DC OK Relay Contact
Derating Curve
Output Derating VS Input Voltage
Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937.
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
71