PS-S100 Series • Universal AC input / full range • Protections: Short Circuit / Overload / Overvoltage / Over temperature • ZCS/ZVS technology to reduce power dissipation • Cooling by free air convection • DIN rail mountable • DC OK relay contact • No load power consumption < 1W • LED indicator for power on • 100% full load burn-in test • 3 year warranty Specifications OUTPUT Features: Cat. No. PS-S10012 PS-S10024 PS-S10048 DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER RIPPLE & NOISE (max) 12V 7.5A 0 ~ 7.5A 90W 120mVp-p 24V 4A 0 ~ 4A 96W 150mVp-p 48V 2A 0 ~ 2A 96W 200mVp-p Ripple & noise are measured at 20MHz of bandwidth by using a 12 twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor. VOLTAGE ADJ. RANGE VOLTAGE TOLERANCE 12 ~ 15V ±1.0% 24 ~ 30V ±1.0% LINE REGULATION LOAD REGULATION SETUP, RISE TIME ±1.0% ±1.0% ±1.0% ±1.0% 3000ms, 50ms/230VAC; 3000ms, 50ms/115VAC at full load 48 ~ 56V ±1.0% Tolerance: includes set up tolerance, line regulation and load regulation. ±1.0% ±1.0% Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time. INPUT HOLD UP TIME (Typ.) VOLTAGE RANGE 50ms/230VAC; 20ms/115VAC at full load 85 ~ 264VAC 120 ~ 370VDC Derating maybe needed under low input voltages, please check the derating curve for more detail PROTECTION FREQUENCY RANGE POWER FACTOR (Typ.) EFFICIENCY (Typ.) AC CURRENT (max) INRUSH CURRENT (Typ.) LEAKAGE CURRENT OVERLOAD 47~63Hz PF ≥ 0.95/230VAC; PF ≥ 0.98/115VAC at full load 85% 86% 1.3A/115VAC; 0.8A/230VAC COLD START: 30A/115VAC; 60A/230VAC ≤1mA/ 240VAC 88% 105% ~ 150% rated output power Protection type: Constant current limiting, recovers automatically after fault condition is removed OVERVOLTAGE 15.6 ~ 18V 31.2 ~ 36V 57.6 ~ 64.8V Protection type: Shut down overvoltage, re-power on to recover OVERTEMPERATURE 90˚C ± 10˚C (RTH2) detect on heat sink of power transistor SHORT CIRCUIT PROTECTION Protection type: Shut down overvoltage, re-power on to recover ENVIRONMENT DC OK AKTIV SIGNAL (max.) Power supply shut down at 70˚C constant current limiting / output voltage goes to 0; re-power on to recover Relay contact rating (max.): 30V/1A resistive SAFETY & EMC WORKING TEMP. WORKING HUMIDITY STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION MOUNTING -10 ~ +60˚C (Refer to output load derating curve) 20 ~ 90% RH non-condensing -40 ~ +85˚C, 10 ~ 95% RH ±0.03% ˚C (0 ~ 50˚C) Component: 10 ~ 500Hz, 2G 10min. / 1cycle, 60 min. each long X,Y, Z axes Compliance to IEC60068-2-6 SAFETY STANDARDS UL508 EN60950-1 compliant I/P-O/P: 3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG: ≥100M Ohms/500VDC/25˚C/70% RH Compliance to EN55011 EN55022 (CISPR22) EN61204-3 Class B Compliance to EN61000-3-2,-3 Compliance to EN61000-4-2,3,4,5,6,8,11; EN55024; ENV50204; EN61000-6-2; EN61204-3; light industry level; criteria A WITHSTAND VOLTAGE ISOLATION RESISTANCE EMI CONDUCTION & RADIATION HARMONIC CURRENT EMS IMMUNITY The power supply is considered a component which will installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. OTHERS MTBF DIMENSION PACKING 346K hrs min. MIL-HDBK-217K (25˚C) 55x90x100mm (WxHxD) 0.42Kg; 30pcs / 13.6Kg / 0.82CUFT All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature. For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power. 70 Mechanical Specification Terminal Pin. No Assign. (TB1) Pin No. 1 2 3 Assignment FG AC/N AC/L Terminal Pin. No Assign. (TB2) Pin No. Assignment 1,2 DC OUTPUT +V DC OUTPUT -V 3,4 DC OK RELAY CONTACT 5,6 Block Diagram DC OK Relay Contact Derating Curve Output Derating VS Input Voltage Note: All dimensions are in millimeters, to convert to inches multiply by 0.03937. Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 71