here - Chinfa

DRAN120 SERIES
AC - DC DIN RAIL MOUNTABLE POWER SUPPLY
INDUSTRIAL CONTROL EQUIPMENT
FEATURES
‧PFC FUNCTION AVAILABLE
‧PARALLEL FUNCTION AVAILABLE (SWITCH)
‧INPUT VOLTAGE 115/230VAC AUTO SELECT
‧SELV COMPONENTS DESIGN
‧3 YEARS WARRANTY
R
R
R
HH H
UL 1310
Class I, Div 2
EN 61558-1
EN 61558-2-16
UL 60950-1
IND. CONT. EQ.
UL 508
a
EN 60950-1
SELECTION CHART
DRAN 120 - 24 x
Wattage
A : SCREW TERMINAL TYPE
B : DETACHABLE CONNECTOR TYPE
AL / BL : CLASS 2 POWER (24V ONLY)
12 : 12V OUT
24 : 24V OUT
48 : 48V OUT
MODEL LIST
MODEL NO.
INPUT
VOLTAGE
DRAN120-12x
115 / 230 VAC
120 WATTS
+ 12 VDC
DRAN120-24x
115 / 230 VAC
120 WATTS
DRAN120-24xL
115 / 230 VAC
91 WATTS
DRAN120-48x
115 / 230 VAC
120 WATTS
OUTPUT
OUTPUT
WATTAGE
VOLTAGE
Single Output Models
SPECIFICATION
OUTPUT
CURRENT
EFF.
(min.)
EFF.
(typ.)
10A
82%
84%
+ 24 VDC
5A
84%
86%
+ 24 VDC
3.8A
83%
85%
+ 48 VDC
2.5A
85%
87%
max.
unit
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
GENERAL
Characteristics
Switching frequency
Isolation voltage
min.
Conditions
Vi nom, Io nom
Input-Output
3,000 / 4,242
KHz
VAC / VDC
Input-FG
1,500 / 2,121
VAC / VDC
500 / 710
VAC / VDC
55
Output-FG
Isolation resistance
Ambient temperature
Derating (see derating curve)
Storage temperature
Relative humidity
Input-Output, @ 500VDC
Operating at Vi nom
-40
+ 85
Vi nom, Io nom
20
95
Vi nom, Io min
Bellcore Issue 6 @40 oC, GB
Cooling
Installation position
Pollution degree
www.chinfa.com
2014.09.09
MΩ
+ 71
-35
Vi nom, from +61 to +71 C
Non operational
MTBF
Dimension
100
o
Temperature coefficient
Altitude during operation
typ.
2.5
± 0.03
o
C
% / oC
o
C
% RH
% / oC
12V
509,000
Hours
24V
AL / BL
530,000
Hours
659,000
Hours
48V
600,000
EN 60950-1
Screw terminal type
Detachable connector type
5,000
Hours
m
L124.5 x W64 x D123.6
mm
L143.5 x W64 x D123.6
mm
Free air convection
Vertical ( other direction may derating using )
2
[email protected]
P1
DRAN120 SERIES
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
INPUT SPECIFICATIONS
Characteristics
Conditions
Rated input voltage
Io nom
Absolute input max. range
Ta min ... Ta max,
Io nom
min.
typ.
90
132
AC in
230V selected
180
264
VAC
210
375
VDC
Vi : 115 / 230 VAC, Io nom
2.2 / 0.83
1.65 / 0.65
Rated input current
AL, BL models
Vi : 90 / 180 VAC, Io nom
Line frequency
AL, BL models
Vi nom, Io nom
VAC
A
A
2.8 / 1.4
47
Vi : 115 / 230 VAC , Io nom
Vi : 230 VAC, Io nom
A
2.0 / 0.8
A
63
24 / 48
Hz
A
12V
24
W
24V
AL / BL
20
W
16
W
48V
19
Input-Output
Input-FG
Power factor (Passive)
VAC
115V selected
Input current
Leakage current
unit
AC in
DC in
Inrush current
Power dissipation
max.
115 / 230 (auto select)
Vi : 230VAC, Io nom
0.25
W
mA
3.5
mA
max.
unit
+1
%
0.7
OUTPUT SPECIFICATIONS
Characteristics
min.
Conditions
Output voltage accuracy
(Adjusted before shipment)
Vi nom, Io max
0
Minimum load
Line regulation
Vi nom
Io nom, Vi min ...Vi max
Vi nom,
Io min ...Io nom
0
Load regulation
Voltage trim range
single mode
parallel mode
Vi nom, 0.8 Io nom
24V
AL / BL
22.5
28.5
VDC
22.5
24.5
VDC
45
Vi nom, Io nom
2.5 A @ 48Vdc / 2.1 A @ 55 Vdc
ms
25 / 30
12V model : with 7000μF CAP
Vi nom, Io nom
Vi nom, Io nom
VDC
3.8 A @ 24Vdc / 3.7 A @ 24.5 Vdc
24V, 48V models : with 3500μF CAP
Rise time
55
10 A @ 12Vdc / 8.2 A @ 14.5 Vdc
5 A @ 24Vdc / 4.2 A @ 28.5 Vdc
48V
Vi nom, Io nom
%
VDC
24V
AL / BL
Turn on time
%
14.5
12V
Vi : 115 / 230 VAC , Io nom
%
±1
±5
11.4
Vi nom
Hold up time
%
± 0.5
12V
48V
Rated continuous loading
typ.
12V model : with 7000μF CAP
24V, 48V models : with 3500μF CAP
1,000
ms
1,500
ms
150
ms
500
ms
150
ms
Fall time
Transient recovery time
Vi nom, Io nom
Vi nom, 1~0.5 Io nom
2
ms
Ripple & noise
Vi nom, Io nom, BW = 20MHz
50
mV
Power back immunity
Vi nom, Io nom
12V
18
VDC
24V
35
VDC
48V
63
Capacitor load
Vi nom, Io nom
12V
DC ON indicator threshold
at start up (Green LED)
Vi nom, Io nom
24V, 48V
12V
DC LOW indicator threshold
after start up (Red LED)
Vi nom, Io nom
24V
48V
Parallel operation
Efficiency
www.chinfa.com
2014.09.09
12V
24V
48V
0.1 Io min ~ 0.9 Io max (Except AL / BL models)
Vi nom, Io nom, Po / Pi
7,000
VDC
μF
3,500
μF
10
17.6
37
11.2
19.4
43
VDC
VDC
VDC
10
17.6
37
11.2
19.4
43
VDC
VDC
VDC
3
unit
Up to 87%, See model list and typ efficiency curve
[email protected]
P2
DRAN120 SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
CONTROL AND PROTECTION
Characteristics
typ.
min.
Conditions
Input fuse
max.
unit
T3.15A / 250VAC internal
Internal surge voltage protection
Varistor
IEC 61000-4-5
Vi nom (see typ current limited curve)
Rated over load protection
AL / BL
Threshold voltage of contact closed (at start up)
Power Rdy
(for 24V model only)
145
%
102
108
%
17.6
19.4
VDC
500
Electrical isolation
Contact rating at 60VDC
Over voltage protection
110
Vi nom, 0.8 Io nom (Auto Recovery)
VDC
0.3
A
12V
15
16.8
V
24V
30
33
V
48V
AL / BL
60
66
V
24.5
25.5
V
Output short circuit
Fold forward
Degree of protection
IP20
APPROVALS AND STANDARDS
UL / cUL
UL 508 Listed
UL 60950-1, UL 1310 Class 2 Power (24AL/BL models only) Recognized
ISA 12.12.01(Class I, Division 2, Groups A, B, C and D)
TUV
EN 60950-1
EN 61558-1, EN 61558-2-16 (meet EN 60204-1)
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2 Class D, EN 61000-3-3
EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3
EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L / N-FG Level 4
EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11
ENV 50204 Level 2, EN 61204-3
CCC
GB4943.1, GB9254, GB17625.1
Vibration resistance
meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis )
Shock resistance
meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
PHYSICAL CHARACTERISTICS
Case size
Screw terminal type
Detachable connector type
Case material
Weight
Metal
920g
1.02kg ; 20
Packing
124.5 x 64 x 123.6 mm (4.9 x 2.52 x 4.87 inches)
143.5 x 64 x 123.6 mm (5.65 x 2.52 x 4.87 inches)
/ 21.5kg / 2.01CUFT
MECHANISM & PIN CONFIGURATION
mm [inch]
64.00 [2.52]
64.00 [2.52]
6
6
firmly on the rail.
1
Vout ADJ.
DC LO
DC ON
P
INSTALLATION
- - ++ Rdy
DRAN120
L
Vout ADJ.
DC LO
DC ON
124.50 [4.90]
S
- - ++ Rdy
143.50 [5.65]
P
Easy snap-on mounting onto the DIN-Rail
7.00 [0.30] (TS35/7.5 or TS35/15), unit sits safeIy and
1
124.50 [4.90]
S
116.60 [4.59]
CONSTRUCTION
DRAN120
N
L
N
AC INPUT
7
9
7
9
GENERAL TOLERANCE
0.00[0.00] - 30.00[1.18]
±0.30[0.01]
30.00[1.18] - 120.00[4.72]
±0.50[0.02]
120.00[4.72] - 400.00[15.75]
±0.80[0.03]
www.chinfa.com
2014.09.09
Ventilation / Cooling
Normal convection
All sides 25mm free space
For cooling recommended
Connector size range
Screw terminal:
AWG24-10 (0.2~4mm2 ) flexible / solid cable,
-Input connector can withstand torque at
maximum 9 pound-inches.
-Output connector can withstand torque at
maximum 5.5 pound-inches.
8 m/m stripping at cable end recommends
Detachable connector:
AWG24-12 (0.2~2.5mm2 ) flexible / solid cable,
-Input connector can withstand torque at
maximum 4.5 pound-inches.
-Output connector can withstand torque at
maximum 7 pound-inches.
4~5 m/m stripping at cable end recommends
Use copper conductors only, 60 / 75oC
[email protected]
P3
DRAN120 SERIES
PIN ASSIGNMENT
Designation
PIN NO.
OUT
1
2
3, 4
5, 6
IN
7
8
OTHER
9
Description
RDY
A normal open relay contact for DC ON level control
(Never connect except 24V model)
V+
V -
Positive output terminal
Negative output terminal
L
N
DC ON
Ground this terminal to minimize high-frequency emissions
Input terminals (phase conductor, no polarity at DC input)
Input terminals (neutral conductor, no polarity at DC input)
Operation indicator LED
DC LOW voltage indicator LED
DC LO
Vout ADJ.
Trimmer-potentiometer for Vout adjustment
Single / Parallel select switch (Except AL/BL models)
S/P
CIRCUIT SCHEMATIC
‧Block diagram for DRAN120 series
L
Fuse
Filter
N
Inrush Current
Limiter,
Rectifier and
Auto Select
115 / 230 Vac
Vo +
PFC
Circuit
Smoothing
Circuit
Y
Switching
Rectifier
Device
PWM
Controller
Current
Detection
Vo Single / Parallel
Select 2)
Opto Isolation
Reference &
Error Amp.
Opto Isolation
Over Voltage
Detection
Vout
ADJ.
Output
Level
Detection
DC ON
(Green LED)
DC LOW
(Red LED)
RDY 1)
(Relay Contact)
Note: 1) For 24V Model Only
2) AL/BL Models without this function
TYP. CURRENT LIMITED CURVE
Output Voltage [ % ]
DRAN120-24x
100
75
230 Vac
115 Vac
50
25
0
100
110
120
130
140
150
160
Output Current [ % ]
DERATING CURVE
TYP. EFFICIENCY CURVE
DRAN120-24x
85
EFFICIENCY [ % ]
Power out [ % ]
100
75
Safe Operating Area
0
-35
www.chinfa.com
2014.09.09
80
75
70
230 Vac
115 Vac
65
60
61
Temperature [ oC ]
71
10
25
50
Power out [ % ]
75
100
[email protected]
P4