CHINFA WRA480-48

WRA480 SERIES
3PH AC - DC DIN RAIL MOUNTABLE POWER SUPPLY
INDUSTRIAL CONTROL EQUIPMENT
FEATURES
‧3 PHASE AC INPUT VOLTAGE
‧COMPACT DESIGN
‧PARALLEL FUNCTION AVAILABLE (SWITCH)
‧UNIVERSAL INPUT VOLTAGE
R
R
H H
EN 61558-1
EN 61558-2-17
UL 60950-1
Class I, Div 2
IND. CONT. EQ.
UL 508
a
EN 60950-1
SELECTION CHART
WRA 480 - 24
24 : 24V OUT
48 : 48V OUT
Wattage
MODEL LIST
INPUT
VOLTAGE
MODEL NO.
OUTPUT
OUTPUT
WATTAGE
VOLTAGE
Single Output Models
OUTPUT
CURRENT
EFF.
(min.)
EFF.
(typ.)
WRA480-24
3o 340~575 VAC
480 WATTS
+ 24 VDC
20 A
88%
90%
WRA480-48
3o 340~575 VAC
480 WATTS
+ 48 VDC
10 A
89%
91%
max.
max.
unit
unit
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
GENERAL
Conditions
Conditions
Characteristics
Switching frequency
Isolation voltage
Isolation resistance
Ambient temperature
Derating (see derating curve)
Storage temperature
Relative humidity
3000 / 4242
KHz
VAC / VDC
Input-FG
1500 / 2121
VAC / VDC
80
Input-Output, @ 500VDC
Operating at Vi nom
100
MΩ
+ 71
-30
o
Vi nom, from +61 to +71 C
Non operational
2.5
-40
+ 85
20
95
Vi nom, Io nom
Vi nom, Io min
MTBF
Bellcore Issue 6 @40 oC, GB
Dimension
Cooling
typ.
typ.
Vi nom, Io nom
Input-Output
Temperature coefficient
Altitude during operation
min.
min.
± 0.03
24V model
411000
48V model
423000
IEC 60068-2-13
Screw terminal type
o
C
%/ C
o
o
C
% RH
% / oC
Hours
4850
Hours
m
mm
L124 x W150 x D118.8
Free air convection
Pollution degree
2
INPUT SPECIFICATIONS
Characteristics
min.
Conditions
Absolute input max. range
max.
unit
1o or 3 o 380 / 480 VAC
Nominal voltage *1
Rated input voltage
typ.
Io nom
Ta min ... Ta max,
Io nom
Input current
Vi : 400 / 500 VAC, Io nom
Rated input current
Vi : 340 VAC, Io nom
Line frequency
Vi nom, Io nom
340
500
575
VAC
AC in
400
DC in
480
820
VDC
1.1 / 0.93
47
VAC
A
1.4
A
63
Hz
*1. Single phase input is permissible, but output load is derated to 75%
www.chinfa.com
2010.05.21
[email protected]
P1
WRA480 SERIES
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
INPUT SPECIFICATIONS
Characteristics
Conditions
Inrush current
Power dissipation
Vi nom, Io nom
Vi : 400 VAC, Io nom
Leakage current
Input-Output
min.
typ.
24V model
20
58
48V model
55
max.
Vi nom, Io nom
A
W
W
0.25
mA
3.5
mA
Input-FG
P.F.C. (Passive)
unit
25
0.65
OUTPUT SPECIFICATIONS
Characteristics
Conditions
min.
Output voltage accuracy
(Adjusted before shipment)
Vi nom, Io max
0
Minimum load
Line regulation
Vi nom
Io nom, Vi min ...Vi max
Vi nom, Io min ...Io nom
0
Load regulation
typ.
%
parallel mode
Vi nom,
0.8 Io nom
24V model
22.5
48V model
47
Rated continuous loading
Vi nom
24V model
Hold up time
Vi nom , Io nom
Turn on time
Vi nom, Io nom
Vi nom, Io nom
Vi nom, Io nom
Vi nom, Io nom
±1
%
±1
%
±5
28.5
VDC
%
56
20 A @ 24Vdc / 16.8 A @ 28.5Vdc
VDC
10 A @ 48Vdc / 8.5 A @ 56Vdc
48V model
Rise time
%
+1
single mode
Voltage trim range
unit
max.
ms
20
with 7000 μF CAP
1000
ms
1500
ms
150
ms
with 7000 μF CAP
500
ms
Fall time
Transient recovery time
Vi nom, Io nom
150
ms
Vi nom, 1~0.5 Io nom
Vi nom, Io nom, BW = 20MHz
2
100
ms
Ripple & noise
Power back immunity
Vi nom, Io nom
Capacitor load
Vi nom, Io nom
24V model
DC ON indicator threshold
at start up (Green LED)
Vi nom, Io nom
24V model
48V model
DC LOW indicator threshold
after start up (Red LED)
Vi nom, Io nom
Parallel operation
0.1 Io min ~ 0.9 Io max
Vi nom, Io nom, Po / Pi
Efficiency
24V model
35
48V model
63
mV
VDC
7000
VDC
μF
17.6
19.4
VDC
37
43
VDC
24V model
17.6
19.4
VDC
48V model
37
43
VDC
unit
2
Up to 91%, See model list and typ efficiency curve
CONTROL AND PROTECTION
Characteristics
min.
Conditions
Input fuse
typ.
max.
unit
T3.15 A / 500 VAC internal / phase
Internal surge voltage protection
Rated over load protection
IEC 61000-4-5
Vi nom (see typ current limited curve)
110
Varistor
135
%
Power Rdy
(for 24V model only)
Threshold voltage of contact closed(at start up)
17.6
19.4
VDC
Electrical isolation
500
VDC
Contact rating at 60VDC
Over voltage protection
Output short circuit
Over temperature
Degree of protection
www.chinfa.com
2010.05.21
Vi nom, Io nom
(Auto Recovery)
24V model
30
48V model
60
A
33
VDC
68
VDC
Fold forward
Continuous
Discontinuous
Detect on heat sink, shut down O/P
voltage, recovers automatically after
temperature goes down.
0.3
Delay 3S shut-down. After 30S Auto-restart
100
110
o
C
IP20
[email protected]
P2
WRA480 SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
APPROVALS AND STANDARDS
UL / cUL
UL 508 Listed
UL 60950-1 Recognized
ISA 12.12.01(Class I, Division 2, Groups A, B, C and D)
TUV
EN 60950-1, CB scheme
EN 61558-1, EN 61558-2-17 (meet EN 60204-1)
CE
EN 61000-6-3, EN 55022 class B, EN 61000-3-2, EN 61000-3-3
EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3
EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L / N-FG Level 4
EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11
ENV 50204 Level 2, EN 61204-3
CQC
GB4943, GB9254, GB17625.1
Vibration resistance
meet IEC 60068-2-6 (Mounting by rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis )
Shock resistance
meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
PHYSICAL CHARACTERISTICS
Case size
Screw terminal type 124 x 150 x 118.8 mm (4.88 x 5.91 x 4.68 inches)
Case material
Weight
Metal
1720g
2kg ; 8
Packing
/ 17.5kg / 2.17CUFT
MECHANISM & PIN CONFIGURATION
mm [inch]
CONSTRUCTION
CHINFA
Chinfa Electronics ind. Co., Ltd.
ISO 9001 Certified
INSTALLATION
24 VDC / 20A
Single
Parallel
L1 L2 L3
Continuous
Discontinuous
IND.CONT.EQ.
E196362
2JF4
3PH 400~500 VAC
1.4 phase 47-63Hz
Easy snap-on mounting onto the DIN-Rail
(TS35/7.5 or TS35/15), unit sits safeIy and
firmly on the rail.
124.00 [4.88]
WRA480
Rdy
DC
LO
DC
ON
+ +
111. 90 [4. 41]
150.00 [5.91]
8 7 6 5
6. 90 [0. 27]
106. 50 [4. 20]
4321
C/D
S/P
9,10
RDY
Ventilation / Cooling
Normal convection
All sides 25mm free space
For cooling recommended
Connector size range
AWG24-10 (0.2~4mm2 ) flexible / solid cable,
-Input connector can withstand torque at
maximum 9 pound-inches.
-Output connector can withstand torque at
maximum 5.5 pound-inches.
8 m/m stripping at cable end recommends
Use copper conductors only, 60 / 75oC
GENERAL TOLERANCE
0.00[0.00] - 30.00[1.18]
±0.30[0.01]
30.00[1.18] - 120.00[4.72]
±0.50[0.02]
120.00[4.72] - 400.00[15.75]
±0.80[0.03]
PIN ASSIGNMENT
Designation
1, 2
V -
Negative output terminal
V+
Positive output terminal
5
L3
Input terminals
6
7
IN
Description
L2
L1
Input terminals
OUT
OUT
PIN NO.
RDY
3, 4
9
OTHER
10
www.chinfa.com
2010.05.21
Input terminals
Ground this terminal to minimize high-frequency emissions
8
A normal open relay contact for DC ON level control
(Never connect except 24V model)
DC ON
Operation indicator LED
DC LO
Vout ADJ.
DC LOW voltage indicator LED
S/P
Single / Parallel select switch
C/D
Continuous / Discontinuous
Trimmer-potentiometer for Vout adjustment
[email protected]
P3
WRA480 SERIES
CIRCUIT SCHEMATIC
‧Block diagram for WRA480 series
L1
Fuse1
L2
Fuse2
L3
Fuse3
Vo +
X
Filter
X
X
Bridge
Rectifier
Filter
P.F.C
Circuit
Switching
Device
PWM
Controller
Y
Rectifier
Filter
Current
Detection
Opto Isolation
Reference &
Error Amp.
Opto Isolation
Over Voltage
Detection
Vo Single / Parallel
Select
Vout ADJ.
Continuous /
Discontinuous
DC ON(Green LED)
DC LOW(Red LED)
RDY 1)
(Relay Contact)
M.C.U
Note: 1) For 24V Model Only
TYP. CURRENT LIMITED CURVE
Output Voltage [ % ]
WRA480-24 (Continuous mode)
100
75
500 Vac
400 Vac
50
25
0
100
110
120
130
140
150
160
Output Current [ % ]
DERATING CURVE
TYP. EFFICIENCY CURVE
WRA480-24
90
EFFICIENCY [ % ]
Power out [ % ]
100
75
0
-30
2010.05.21
80
75
500 Vac
400 Vac
70
65
o
61
Temperature [ C ]
www.chinfa.com
85
71
10
25
50
75
100
Power out [ % ]
[email protected]