WRA960 SERIES

WRA960 SERIES
3PH AC - DC DIN RAIL MOUNTABLE POWER SUPPLY
INDUSTRIAL CONTROL EQUIPMENT
FEATURES
‧3 PHASE AC INPUT VOLTAGE
‧SELV COMPONENTS DESIGN
‧SHORT CIRCUIT PROTECTION
‧INTERNAL INPUT FILTER
‧OVER TEMPERATURE PROTECTION
‧3 YEARS WARRANTY
R
R
H H
EN 61558-1
EN 61558-2-16
UL 60950-1
Class I, Div 2
IND. CONT. EQ.
UL 508
a
EN 60950-1
SELECTION CHART
WRA 960 - 24
24 : 24V OUT
Wattage
48 : 48V OUT
MODEL LIST
INPUT
VOLTAGE
MODEL NO.
OUTPUT
OUTPUT
WATTAGE
VOLTAGE
Single Output Models
OUTPUT
CURRENT
EFF.
(min.)
EFF.
(typ.)
WRA960-24
3o 340~575 VAC
960 WATTS
+ 24 VDC
40 A
90%
92%
WRA960-24L
3o 340~575 VAC
960 WATTS
+ 24 VDC
40 A
90%
92%
WRA960-48
3o 340~575 VAC
960 WATTS
+ 48 VDC
20 A
91%
93%
max.
max.
unit
unit
+ 71
3.5
+ 85
95
± 0.03
KHz
VAC / VDC
VAC / VDC
VAC / VDC
MΩ
o
C
% / oC
o
C
% RH
% / oC
Hours
Hours
Hours
m
mm
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
GENERAL
Conditions
Conditions
Characteristics
Switching frequency
Isolation voltage
Isolation resistance
Ambient temperature
Derating (see derating curve)
Storage temperature
Relative humidity
Temperature coefficient
MTBF
Altitude during operation
Dimension
Cooling
Installation position
Pollution degree
Vi nom, Io nom
Input-Output
Input-FG
Output-FG
Input-Output, @ 500VDC
Operating at Vi nom
Vi nom, from +61 to +71 oC
Non operational
Vi nom, Io nom
Vi nom, Io min
Bellcore Issue 6 @40 oC, GB
min.
min.
typ.
typ.
52
3,000 / 4,242
1,500 / 2,121
500 / 710
100
-40
-40
20
355,000
380,000
396,000
24V
24L
48V
5,000
L125.9 x W275.8 x D118.8
EN 60950-1
Screw terminal type
Free air convection
Vertical ( other direction may derating using )
2
INPUT SPECIFICATIONS
Characteristics
Nominal voltage *1
Rated input voltage
Absolute input max. range
Io nom
Ta min ... Ta max,
Io nom
Input current
Vi : 400 / 500 VAC, Io nom
*1. Single phase input is permissible, but output load is derated to 75%
www.chinfa.com
2015.03.11
min.
Conditions
typ.
max.
unit
1o or 3 o 380 / 480 VAC
AC in
DC in
400
340
480
500
575
820
1.72 / 1.5
VAC
VAC
VDC
A
[email protected]
P1
WRA960 SERIES
SPECIFICATION
o
All Specifications Typical At Nominal Line, Full Load, 25 C Unless Otherwise Noticed
INPUT SPECIFICATIONS
Characteristics
Rated input current
Line frequency
Conditions
min.
Vi : 340 VAC, Io nom
Vi nom, Io nom
Inrush current
Power dissipation
Vi nom, Io nom
Leakage current
Input-Output
typ.
max.
unit
2.4
63
Hz
47
24V, 48V
30
24V
98
48V
90
Vi : 400 VAC, Io nom
35
Vi nom, Io nom
A
W
W
0.25
mA
3.5
mA
max.
unit
+1
%
Input-FG
Power factor (Passive)
A
0.8
OUTPUT SPECIFICATIONS
Characteristics
Conditions
min.
Output voltage accuracy
(Adjusted before shipment)
Vi nom, Io max
0
Minimum load
Line regulation
Vi nom
Io nom, Vi min ...Vi max
Vi nom,
Io min ...Io nom
0
Load regulation
parallel mode
Vi nom,
0.8 Io nom
24V
22.5
48V
47
Rated continuous loading
Vi nom
24V
Hold up time
Vi nom , Io nom
Turn on time
Vi nom, Io nom
with 7000μF CAP
Ripple & noise
Vi nom, Io nom, BW = 20MHz
Power back immunity
Vi nom, Io nom
Capacitor load
Vi nom, Io nom
DC ON indicator threshold
at start up (Green LED)
Vi nom, Io nom
DC LOW indicator threshold
after start up (Red LED)
Vi nom, Io nom
Parallel operation *2
0.1 Io min ~ 0.9 Io max
Vi nom, Io nom, Po / Pi
24V
35
48V
63
1,000
ms
1,500
ms
150
ms
500
ms
150
ms
2
80
mV
VDC
VDC
μF
24V
17.6
19.4
48V
37
43
VDC
VDC
24V
17.6
19.4
VDC
48V
37
43
VDC
unit
3
Up to 93%, See model list and typ efficiency curve
min.
Conditions
Input fuse
typ.
max.
unit
T5 A / 500 VAC internal / phase
Internal surge voltage protection
Rated over load protection
IEC 61000-4-5
Vi nom (see typ current limited curve)
110
Varistor
135
Power Rdy *2
(for WRA960-24 model only)
Threshold voltage of contact closed (at start up)
17.6
19.4
Electrical isolation
500
Vi nom, 0.8 Io nom (Shut-down)
24V
30
48V
60
Output short circuit
%
VDC
VDC
Contact rating at 60VDC
Over temperature
ms
7,000
CONTROL AND PROTECTION
Over voltage protection
%
VDC
ms
with 7000μF CAP
Vi nom, 1~0.5 Io nom
Characteristics
%
15
Fall time
Transient recovery time
Efficiency
%
±1
±5
28.5
56
VDC
40 A @ 24Vdc / 33.5 A @ 28.5Vdc
Vi nom, Io nom
Vi nom, Io nom
±1
20 A @ 48Vdc / 17 A @ 56Vdc
48V
Rise time
%
single mode
Voltage trim range
Vi nom, Io nom
typ.
0.3
A
33
VDC
66
VDC
Hiccup mode
Detect on heat sink, shut down O/P
voltage, recovers automatically after
100
110
o
C
temperature goes down.
Degree of protection
IP20
*2. This function is not on 24L model.
www.chinfa.com
2015.03.11
[email protected]
P2
WRA960 SERIES
SPECIFICATION
All Specifications Typical At Nominal Line, Full Load, 25oC Unless Otherwise Noticed
APPROVALS AND STANDARDS
UL / cUL
UL 508 Listed
UL 60950-1 Recognized
ISA 12.12.01(Class I, Division 2, Groups A, B, C and D)
TUV
EN 60950-1
EN 61558-1, EN 61558-2-16 (meet EN 60204-1)
CE
EN 61000-6-3, EN 55022 Class B, EN 61000-3-2, EN 61000-3-3
EN 61000-6-2, EN 55024, EN 61000-4-2 Level 4, EN 61000-4-3 Level 3
EN 61000-4-4 Level 4, EN 61000-4-5 L-N Level 3, L / N-FG Level 4
EN 61000-4-6 Level 3, EN 61000-4-8 Level 4, EN 61000-4-11
ENV 50204 Level 2, EN 61204-3
CQC
Vibration resistance
GB4943.1, GB9254, GB17625.1
meet IEC 60068-2-6 (Mounting on rail : 10-500 Hz, 2G, along X, Y, Z each Axis, 60 min for each Axis )
Shock resistance
meet IEC 60068-2-27 (15G, 11ms, 3 Axis, 6 Faces, 3 times for each Face)
PHYSICAL CHARACTERISTICS
Case size
Screw terminal type 125.9 x 275.8 x 118.8 mm (4.96 x 10.86 x 4.68 inches)
Case material
Weight
Metal
3400g
Packing
3.68kg ; 6
/ 23kg / 2.41CUFT
MECHANISM & PIN CONFIGURATION
mm [inch]
CONSTRUCTION
Easy snap-on mounting onto the DIN-Rail
(TS35/7.5 or TS35/15), unit sits safeIy and
firmly on the rail.
275.8 0 [1 0.8 6]
CHINFA
Chinfa Electronics ind. Co., Ltd.
ISO 9001 Certified
IND.CONT.EQ.
E196362
2JF4
3PH 400-500VAC
2.2 A phase 47-63 Hz
24 VDC /40A
L1 L2 L3
INSTALLATION
125.9 [4.96]
WRA960
Rdy P G
111.30 [4.38]
106.60 [4.20]
9.0 [0.35]
GENERAL TOLERANCE
0.00[0.00] - 30.00[1.18]
±0.30[0.01]
30.00[1.18] - 120.00[4.72]
±0.50[0.02]
120.00[4.72] - 400.00[15.75]
±0.80[0.03]
Ventilation / Cooling
Normal convection
All sides 25mm free space
For cooling recommended
Connector size range
Input and Rdy, P, G Control : AWG24 - 10
(0.2~4mm2 ), flexible / solid cable
Output : AWG20 - 6
(0.5~10mm2 ), flexible / solid cable
- Input connector can withstand torque at
maximum 9 pound-inches
Rdy, P, G control connector can withstand
torque at maximum 5.5 pound-inches
8m/m stripping at cable end recommends
- Output connector can withstand torque at
maximum 15.6 pound-inches
10m/m stripping at cable end recommends
Use copper conductors only, 60 / 75oC
PIN ASSIGNMENT
Designation
PIN NO.
3, 4
5
6
7
OUT
1, 2
Negative output terminal
V+
Positive output terminal
G
Parallel GND PIN for current share
P
RDY
Parallel PIN for current share
A normal open relay contact for DC ON level control
L3
(Never connect except 24V model)
Input terminals
8
10
IN
9
11
Description
V -
L2
L1
Input terminals
Input terminals
Ground this terminal to minimize high-frequency emissions
OTHER
12
DC ON
Operation indicator LED
DC LO
Vout ADJ.
DC LOW voltage indicator LED
Trimmer-potentiometer for Vout adjustment
* WRA960-24L without PIN5~ PIN8
www.chinfa.com
2015.03.11
[email protected]
P3
WRA960 SERIES
CIRCUIT SCHEMATIC
‧Block diagram for WRA960 series
L1
Fuse1
L2
Filter Fuse2
L3
Fuse3
Vo +
X
Filter
X
Bridge
Rectifier Filter
PFC
Circuit
Switching
Device
Rectifier
Current
Detection
Vo -
X
Reference &
Error Amp.
PWM
Controller
Vout ADJ.
Y
Bias
Power
Parallel
Controller
Parallel
Output
Level
Detection
DC ON(Green LED)
DC LOW(Red LED)
RDY 1)
(Relay Contact)
Note: 1) For WRA960-24 Model Only
‧Parallel connection
TYP. CURRENT LIMITED CURVE
WRA960-24 / 400Vac
Output Voltage [ % ]
125
100
75
Entering hiccup mode
after 2-5 sec of
output overload.
Continuous
50
25
0
20
40
60
80
100
120
140
160
180
200
Output Current [ % ]
DERATING CURVE
TYP. EFFICIENCY CURVE
WRA960-24
95
EFFICIENCY [ % ]
Power out [ % ]
100
65
Safe Operating Area
90
85
80
500 Vac
400 Vac
75
70
0
-40
www.chinfa.com
2015.03.11
o
61
Temperature [ C ]
71
10
25
50
Power out [ % ]
75
100
[email protected]
P4