标准继电器

Rail Mount
InstallationDIN
Sheet
AC/DC Output Single Channel &
AC Output Dual Channel SSR
PART NUMBER NOMENCLATURE
Single Channel (A)
Operating Voltage
06: 1-60 VDC
10: 1-100 VDC
24: 24-280 VAC
48: 48-600 VAC
INSTALLATION INSTRUCTIONS
Series
DR
06
D
SOLID
LAY
Dual Channel
Series
DRD
Operating Voltage
24: 24-280 VAC
48: 48-600 VAC
24
Do not forget to visit us at: www.crydom.com
D
06
Switching Type
Blank: Zero Voltage Turn-On
(AC Output Only)
R: Instantaneous Turn-On
(AC Output, D suffix Only)
R
Agency Approvals (F)
X: ATEX II 3G Ex nA IIC T4 Gc
approved
Rated Load Current
06: 6 Amps
Control Voltage
D: 4-32 VDC
General Notes
(A) Not all combinations of ratings are available.
(B) No grounding wire required. DC inductive loads must be diode suppressed.
(C) 4 Pin connector for dual channel output only. Mating connector: MOLEX 050579404 or equivalent.
(D) 4 Terminal screws Pozidrive #1, 3/16 in (4.8 mm).
(E) Minimum wire insulation strip length 0.20 in (5.1 mm), maximum 0.28 in (7.1 mm).
X
12
Control Voltage
D: 4-32 VDC
A: 200-265 VAC
AC
Output
B: 90-140 VAC
Only
E: 18-36 VAC
STAT
E RE
Please read all installation instructions before using SeriesOne DR SSRs.
Install the relay on the DIN rail (as shown in drawing).
To install
on DIN rail
Wire the relay to the input side. AWG #22 minimum,
AWG #16 maximum (0.3-1.3 mm2). Temperature rating of 111ºC.
Wire the relay to the output side. AWG #22 minimum
(0.3 mm2), AWG #14 (2.1 mm2) x 2 or AWG #12
To remove
(3.3 mm2) x 1 (standed/solid) maximum. Temperature
from DIN rail
rating of 111ºC.
Maximum recommended terminal screw torque input
4.4 in-lbs (0.5 Nm) & output 7 in-lbs (0.8 Nm).
If multiple units are installed be sure to follow derating
curves (reverse side of this sheet).
Rated Load Current
03: 3 Amps
06: 6 Amps
12: 12 Amps
X
Switching Type
Blank: Zero Voltage Turn-On
R: Instantaneous Turn-On
R
Agency Approvals (F)
X: ATEX II 3G Ex nA IIC T4 Gc
approved
Required for valid part number
For options only and not required for valid part number
Copyright © 2015 Custom Sensors & Technologies. Specifications subject to change without notice.
Rev: 041515
Rail Mount
InstallationDIN
Sheet
WIRING DIAGRAMS (B)
DERATING CURVES
Derating curves are not for the ATEX certificate evaluation
AC SUPPLY
1/A
1
AC/DC CONTROL
VOLTAGE
DRxxx03
3.0
+3/A
1
1/A1
+3/A1
Load Current (Amp)
dA
Loa
Load Current (Amp)
For DRDxxD06 versions
For DRxxx03, DRxxx06 or DRxxx12 versions
2.0
1.0
2/A
4/A
2
0.0
2
3/B1
AC SUPPLY
4/B2
2/T1
1/L1
L
+A
-A
+B
-B
dB
Loa
(F) THIS EQUIPMENT IS OPEN-TYPE DEVICE AND IS MEANT TO BE INSTALLED IN AN
ENCLOSURE SUITABLE FOR THE ENVIRONMENT SUCH THAT THE EQUIPMENT IS ONLY
ACCESSIBLE WITH THE USE OF A TOOL. SUITABLE FOR USE IN CLASS I, DIVISION 2,
GROUPS A, B, C AND D HAZARDOUS LOCATIONS, OR NON-HAZARDOUS LOCATIONS
ONLY. WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT WHILE THE
CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOWN TO BE FREE OF IGNITABLE
CONCENTRATIONS. WARNING - EXPLOSION HAZARD - SUBSTITUTION OF ANY
COMPONENT MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.
Load Current
(Combined for Dual) [Amp]
INPUT
INPUT
STATUS STATUS
INPUT
STATUS
AC/DC SUPPLY
oad
DC (C)
CONTROL
10
20
30
40
50
60
70
80
Ambient Temperature (°C)
2/A2
4/A2
(D, E)
5.0
4.0
3.0
2.0
1.0
0.0
0
(D, E)
DRxxx06
6.0
0
10
20
30
40
50
60
70
80
Ambient Temperature (°C)
DRxxx12 & DRDxxD06
12.0
Single and multiple units for DRxx03
Installed single unit, distance to adjacent
components ≥ 11 mm for DRxxx06 and ≥ 18
mm for DRxxx12 & DRDxxD06
10.0
8.0
6.0
4.0
Multiple units, no minimum spacing between
components
2.0
0.0
0
10
20
30
40
50
60
70
80
Ambient Temperature [°C]
WARNING
RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE
• The product's side panels may be hot, allow the product to cool before touching.
• Follow proper mounting instructions including torque values.
• Do not allow liquids or foreign objects to enter this product.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Turn off power supply before working on this equipment.
Failure to follow these instructions can result in serious injury, or equipment damage. Failure to follow these instructions will result in death or serious injury.
2320 Paseo de las Americas, Suite 201. San Diego, CA 92154 USA
Tech Support
Americas +1 (877) 502 5500
EMEA +44 (0) 1202 606030
Rev: 041515
Asia +86 (21) 8125 7177