12 24 D DR R 06 24 D DRD R

PART NUMBER NOMENCLATURE
Single Channel (A)
AC/DC Output Single Channel &
AC Output Dual Channel
Crydoms SeriesOne DR Solid State Relays were developed to offer the advantages of Crydom's thermal
management technology in a compact 11 & 18 mm wide IP20 housing with unique integrated heat sink.
The SeriesOne DR provides a quick and easy installation onto any standard 35 mm DIN rail profile
paired with high output power ratings.
Max Output Voltage
06: 1 to 60 VDC
10: 1 to 100 VDC
24: 24 to 280 VAC
48: 48 to 600 VAC
Series
DR
24
D
INSTALLATION INSTRUCTIONS
Please read all installation instructions before using SeriesOne DR SSRs. To install on DIN rail
Install the relay on the DIN rail (as shown in drawing)
Wire the relay to the input side. 22 AWG minimum,
16 AWG maximum
To remove from
Wire the relay to the output side. 22 AWG minimum,
DIN rail
14 AWG x 2 or 12 AWG x 1 (standed/solid) maximum
Maximum recommended terminal screw torque
input 4.4 in/lbs (0.5 Nm) & output 7.0 in/lbs (0.8 Nm)
If multiple units are installed be sure to follow
derating curves (reverse side of this sheet)
12
R
Control Voltage
D: 4 to 32 VDC
A: 208 to 265 VAC
B: 90 to 140 VAC
E: 18 to 36 VAC
FEATURES
Single channel 6 & 12 Amps output power rating
Two independent 6 Amp channels in dual channel versions
Single channel 60 & 100 VDC, 24 to 600 VAC operating voltage ratings
Dual channel 24 to 600 VAC operating voltage ratings
4-32 VDC, 24, 120 & 230 VAC control input options available for single channel versions
4-32 VDC control input for dual channel versions
AC Output versions with Zero Voltage Turn-On for resistive loads and Random Turn-On for inductive loads
LED indicates only Input status. Does not represent Output status.
Output Current
06: 6 Amps
12: 12 Amps
AC
Output
Only
Option
Blank: Zero Voltage Turn-On
R: Random Turn-On
(AC Output Only)
Dual Channel
Series
DRD
Max Output Voltage
24: 24 to 280 VAC
48: 48 to 600 VAC
24
D
Output Current
06: 6 Amps
06
Control Voltage
D: 4 to 32 VDC
Required for valid part number
For options only and not required
for valid part number
(A)
Not all combinations of ratings are available.
R
Option
Blank: Zero Voltage Turn-On
R: Random Turn-On
(AC Output Only)
Rev: 072310
WIRING DIAGRAMS (B)
DERATING CURVES
For DRDxxD06 versions
dA
Loa
1
1/A
DC/AC CONTROL
VOLTAGE
AC SUPPLY
DRxxx06
+3/A
1
1/A1
+3/A1
Load Current (Amps)
For DRxxx06 or DRxxx12 versions
6.0
5.0
4.0
3.0
2.0
1.0
2
2/A
4/A
2
0.0
2/A2
4/A2
(E)
d
Loa
B
No grounding wire required. DC inductive loads must be diode suppressed.
4 Pin connector for dual channel ouput only. Matting connector: MOLEX 050579404 or equivalent.
4 Terminal screws Pozidriv #1, 3/16 in [4.8 mm].
Minimum wire strip lenght 0.20 in [5.1 mm], maximum 0.28 in [7.1 mm].
WARNING
DANGER
RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE
• The product's side panels may be hot, allow the product to cool before touching.
• Follow proper mounting instructions including torque values.
• Do not allow liquids or foreign objects to enter this product.
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Failure to follow these instructions can result in serious injury, or equipment damage.
Failure to follow these instructions will result in death or serious injury.
• Turn off power supply before working on this equipment.
Load Current
(Combined for Dual) [Amps]
(D)
3/B1
(C)
AC SUPPLY
4/B2
2/T1
1/L1
DC/AC SUPPLY
Loa
10
20
30
40
50
60
70
80
70
80
Ambient Temperature (°C)
INPUT
INPUT
STATUS STATUS
INPUT
STATUS
DC CONTROL (C)
+A
-A
+B
-B
d
(B)
0
(D, E)
(D, E)
DRxxx12 & DRDxxD06
12.0
10.0
8.0
6.0
4.0
2.0
0.0
0
10
20
30
40
50
60
Ambient Temperature [°C]
Installed single unit, distance to adjacent components ≥ 11 mm
for DRxxx06 and ≥ 18 mm for DRxxx12 & DRDxxD06
Multiple units, no minimum spacing between components
Rev: 072310