Solid State Relays & Timers The Global Expert in Solid State Switching Technology SeriesOne DR Single Channel DIN Rail Mounted AC/DC Output Solid State Relays • • • • • • • • 3, 6 & 12 Amps output power rating 60 & 100 VDC, 24 to 600 VAC operating voltage ratings 4-32 VDC, 24, 120 & 230 VAC control input options available IP20 housing with unique integrated heat sink design AC Output versions with Zero Voltage Turn-On for resistive loads and Random Turn-On for inductive loads High power density for multiple units UL & cUL Listed CE & RoHS compliant AC OUTPUT SPECIFICATIONS (A) Operating Voltage Range (47-63Hz AC Only) [VAC] Maximum Load Current [Arms] (B) Minimum Load Current [Arms] Maximum Surge Current (60 Hz, 1 cycle) [Apk] (Duration in ms) Maximum Surge Current (50 Hz, 1 cycle) [Apk] (Duration in ms) Maximum On-State Voltage Drop @ Rated Current [Vpk] Maximum Off-State Leakage Current @ Rated Voltage [mArms] Transient Overvoltage [Vpk] Minimum Off-State dv/dt @ Max. Rated Voltage [V/µsec] (C) Maximum l2t for Fusing (10/8.3 ms) [A2sec] Power Factor (Minimum) with Maximum Load Maximum Turn-On Time (D) Maximum Turn-Off Time (E) UL Motor Controller Ratings @ 240 VAC [HP / FLA] UL Motor Controller Ratings @ 380 VAC [HP / FLA] UL Motor Controller Ratings @ 480 VAC [HP / FLA] DC OUTPUT SPECIFICATIONS (A) Operating Voltage Range (47-63Hz AC Only) [VDC] Maximum Load Current [ADC] (B) Minimum Load Current [mA DC] Maximum Surge Current [Apk] (Duration in ms) Maximum On-State Voltage Drop @ Rated Current [Vpk] Maximum On-State Resistence [Ohm] Maximum Off-State Leakage Current @ Rated Voltage [mADC] Maximum Turn-On Time [µsec] (D) Maximum Turn-Off Time [µsec] (E) INPUT SPECIFICATIONS (A) Control Voltage Range Minimum Turn-On Voltage Minimum Turn-Off Voltage Reverse Polarity Protection Typical Input Current GENERAL SPECIFICATIONS (A) Dielectric Strength, Input to Output. AC Output Versions (50/60Hz) [Vrms] Dielectric Strength, Input to Output. DC Output Versions [Vrms] Dielectric Strength, Input-Output to Case (50/60Hz) [Vrms] Minimum Insulation Resistance (@ 500 VDC) [Ohm] Maximum Capacitance, Input/Output [pF] Ambient Operating Temperature Range [ºC] Ambient Storage Temperature Range [ºC] Weight (typical) [oz] (gr) Housing Material DR24x03 DR48x03 DR24x06 DR48x06 DR24x12 DR48x12 24-280 3 0.15 300 (16.6) 285 (20) 1.3 0.1 600 500 410/375 0.5 1/2 cycle 1/2 cycle 1/4 / 2.9 N/A N/A 48-600 3 0.15 300 (16.6) 285 (20) 1.3 0.1 1200 500 410/375 0.5 1/2 cycle 1/2 cycle 1/4 / 2.9 1/3 / 2.3 1/2 / 2.5 24-280 6 0.15 300 (16.6) 285 (20) 1.3 0.1 600 500 410/375 0.5 1/2 cycle 1/2 cycle 1/2 / 4.9 1 / 5.1 2 / 6 48-600 6 0.15 300 (16.6) 285 (20) 1.3 0.1 1200 500 410/375 0.5 1/2 cycle 1/2 cycle 1/2 / 4.9 1 / 5.1 2 / 6 24-280 12 0.15 750 (16.6) 715 (20) 1.3 0.1 600 500 2560/2330 0.5 1/2 cycle 1/2 cycle 1 / 8 2 / 7.7 3 / 8.5 48-600 12 0.15 750 (16.6) 715 (20) 1.3 0.1 1200 500 2560/2330 0.5 1/2 cycle 1/2 cycle 1 / 8 2 / 7.7 3 / 8.5 DR06x03 DR10x03 DR06x06 DR10x06 DR06x12 DR10x12 1-60 3 2.5 60 (10) 0.6 0.1 0.1 600 300 1-100 3 2.5 60 (10) 0.6 0.1 0.1 600 300 1-60 6 2.5 60 (10) 0.6 0.1 0.1 600 300 1-100 6 2.5 60 (10) 0.6 0.1 0.1 600 300 1-60 12 2.5 100 (10) 0.5 0.045 0.1 600 300 1-100 12 2.5 100 (10) 0.5 0.045 0.1 600 300 DRxxDxx DRxxExx DRxxBxx DRxxAxx 4-32 VDC 4 VDC 1 VDC Yes 10 mA @ 24 VDC (C) 18-36 VAC 18 VAC 4 VAC N/A 6 mA @ 24 VAC 90-140 VAC 90 VAC 10 VAC N/A 5 mA @ 120 VAC 200-265 VAC 200 VAC 90 VAC N/A 3 mA @ 230 VAC DRxxx03 1.76 (50) DRxxx06 4000 2500 2500 109 10 -30 to 80 -40 to125 1.76 (50) UL 94 V0 Self-extinguishing Complete specifications of these & other Crydom products available at: www.crydom.com DRxxx12 3.17 (90) SeriesOne DR Dual Channel DIN Rail Mounted AC Output Solid State Relays • • • • • • • • • Two independent 6 Amp channels DIN rail mount 18 mm wide package 4-32 VDC control input 24 to 600 VAC operating voltage ratings IP20 housing with unique integrated heat sink design AC Output versions with Zero Voltage Turn-On for resistive loads and Random Turn-On for inductive loads High power density for multiple units UL & cUL Listed CE & RoHS compliant OUTPUT SPECIFICATIONS (A) Operating Voltage Range (47-63Hz) [VAC] Maximum Load Current (B) Minimum Load Current [Arms] Maximum Surge Current [Apk] @ 60 Hz (Duration in ms) Maximum Surge Current [Apk] @ 50 Hz (Duration in ms) Maximum On-StateVoltage Drop @ Rated Current [Vpk] Maximum Off-State Leakage Current @ Rated Voltage [mArms] Transient Overvoltage [Vpk] Minimum Off-State dv/dt @ Max. Rated Voltage [V/µsec] (C) Maximum l2t for Fusing (10/8.3 ms) [A2sec] Power Factor (Minimum) with Maximum Load Maximum Turn-On Time (D) Maximum Turn-Off Time UL Motor Controller Ratings @ 240 VAC [HP / FLA] UL Motor Controller Ratings @ 380 VAC [HP / FLA] UL Motor Controller Ratings @ 480 VAC [HP / FLA] DRD24D06 DRD48D06 24-280 6 Arms per channel 0.15 750 (16.6) 715 (20) 1.3 0.1 600 500 2560/2330 0.5 1/2 cycle 1/2 cycle 1/2 / 4.9 1 / 5.1 2 / 6 48-600 6 Arms per channel 0.15 750 (16.6) 715 (20) 1.3 0.2 1200 500 2560/2330 0.5 1/2 cycle 1/2 cycle 1/2 / 4.9 1 / 5.1 2 / 6 INPUT SPECIFICATIONS (A) 4-32 4 1 Yes 10 mA @ 24 VDC (F) GENERAL SPECIFICATIONS (A) DRDxxD06 Dielectric Strength, Input to Output. (50/60 Hz) [Vrms] Dielectric Strength, Input-Output to Case (50/60Hz) [Vrms] Minimum Insulation Resistance (@ 500 VDC) [Ohm] Maximum Capacitance, Input/Output [pF] Ambient Operating Temperature Range [ºC] Ambient Storage Temperature Range [ºC] Weight (typical) [oz] (gr) Housing Material Part Number Nomenclature DR Blank Strips Part no.: CNLB Numbered 1 to Strips Part no.: CNLN 2500 2500 109 10 -30 to 80 -30 to 125 3.17 (90) UL 94 V0 Self-extinguishing 10 Numbered 11 to 20 Strips Part no.: CNL2 (G) Operating Voltage 06: 1-60 VDC 10: 1-100 VDC 24: 24-280 VAC 48: 48-600 VAC D Packages of 10 plastic strips comprising 10 individual markers which can be placed for easy identifications during the use of multiple units. DRDxxD06 Control Voltage Range [VDC] Minimum Turn-On Voltage [VDC] Minimum Turn-Off Voltage [VDC] Reverse Polarity Protection Typical Input Current (per channel) Series ID Marker Strips CNLB, CNLN, CNL2 24 Number of Channels Blank: One N.O. Channel D: Two N.O. Channels D General Notes Rated Load Current 03: 3 Amps (One Channel Only) 06: 6 Amps 12: 12 Amps (One Channel Only) 06 Control Voltage D: 4-32 VDC A: 200-265 VAC One B: 90-140 VAC Channel, AC Output E: 18-36 VAC Only R Switching Type Blank: Zero Voltage Turn-On (AC Output Only) R: Random Turn-On (AC Output, DC Control Only) (A) All parameters at 25ºC unless otherwise specified (B) Minimum spacing required between devices (see derating curves on the reverse side of this brochure) (C) Off-State dv/dt test method per EIA/NARM standard RS-433, paragraph 13.11.1 (D) Turn-On time for Random-type AC output is 0.1 ms for DC control models and 20 ms for AC control models (E) Turn-Off time for AC Output versions with AC control is 30 ms (F) Input circuit incorporates active current limitation (G) Not all combinations of ratings are available Required for valid part number For options only and not required for valid part number America Tel.: +1 (877) 502 5500 [email protected] EMEA Tel.: +44 (0) 1202 606030 [email protected] Asia Pacific Tel.: +86 (0) 21 6065 7725 [email protected] Mechanical Dimensions Wiring Diagrams DRxxx03, DRxxx06 or DRxxx12 Tolerances: ±0.02 in / 0.5 mm All dimensions are in: inches [millimeters] DRDxxD06 FRONT VIEW dA Loa AC SUPPLY 1 +3/A 1 1/A1 +3/A1 2/A 4/A 2 DRDxxD06 3.40 [86.4] 3.40 [86.4] dB Loa DRXXX03 L 3.3 [83.7] 2 Block Diagrams (L) DC Control, AC Output +DC +3/A1 2.88 [73] 2.02 [51.2] DRxxx06 & DRxxx03 3/B1 AC SUPPLY 4/B2 AC Supply Load B 2/T1 1/L1 Power Supply Control +A -A +B -B 2/A2 4/B2 Load d Current Limiter 2.88 [73] 2.02 [51.2] SIDE VIEW 1/A1 3/B1 STATUS B Load A INPUT A AC Supply INPUT STATUS DC (K) CONTROL +A -A +B -B Loa AC/DC SUPPLY DRxxx12 & DRDxxD06 (K) 0.72 [18.3] 2/A2 4/A2 (H, J) +3/A1 2/T1 Control 4/A2 +1/L1 (H, J) DRxxx06 & DRxxx03 0.43 [11] 1/A AC/DC CONTROL VOLTAGE S O L ID S TAT E R E L AY 3/B1 DRDXXXXX L 3.3 [83.7] 4WB8 4WB8 S O L ID S TATE RE LAY 2/A2 (DR24Dxxx & DR48Dxxx) +3/A1 2/T1 Visible LED Control 4/A2 +1/L1 AC Load 1/L1 Load Load A 2/A2 4/B2 AC Supply Load B Control +A -A +B -B INPUT STATUS A B A Trigger Circuit B -DC -4/A2 4/B2 1/A1 3/B1 AC Supply Power Supply 2/T1 Load AC 1/L1 Load AC 1.77 [45] 1.77 [45] 2.59 [65.9] 2.59 [65.9] 3.45 [87.6] 3.45 [87.6] AC Control, AC Output (DR24xxxx & DR48xxxx A, B, E suffixes) DRDxx06 Visible LED +3/A1 A AC/DC Converter +DC Trigger Circuit Current Limiter +A DC Control, DC Output AC -DC -A +DC +B B (M) Current Limiter (DR06Dxxx & DR10Dxxx) + -DC -4/A2 1/L1 Control Circuit 2/T1 + AC A Trigger Circuit Load 2/T1 Load 1/A1 B -4/A2 +DC 3/A1 Visible LED +DC Load A 2/A2 Load AC 3/B1 Load AC Visible LED A Trigger Circuit B Load -DC -DC B -B Load 4/B2 AC Derating Curves DRxxx06 Load Current (Amp) Load Current (Amp) DRxxx03 3 2 1 0 0 10 20 30 40 50 60 Ambient Temperature (°C) 70 80 6 5 4 3 2 1 0 0 10 20 30 40 50 60 70 Ambient Temperature (°C) (H) 4 Terminal screws Pozidrive #1, 3/16 in (4.8 mm). (J) Minimum wire insulation strip length 0.20 in (5.1 mm), maximum 0.28 in (7.1 mm). (K) 4 Pin connector for dual channel output only. Mating connector: MOLEX 050579404 or equivalent. 80 Load Current (Combined for Dual) [Amp] Single and multiple units for DRxx03 Installed single unit, distance to adjacent components ≥ 11 mm for DRxxx06 and ≥ 18 mm for DRxxx12 & DRDxxD06 Multiple units, no minimum spacing between components DRxxx12 & DRDxxD06 12 10 8 6 4 2 0 0 10 20 30 40 50 60 Ambient Temperature [°C] (L) Load can be wired in position A or B (M) No grounding wire required. DC inductive loads must be diode suppressed. Complete specifications of these & other Crydom products available at: www.crydom.com 70 80 SeriesOne DR Timer DIN Rail Mounted AC & DC Output Solid State Relay Timers • • • • • • • • • • Single channel 6 Amps output power rating Compact Size (11 mm wide) 60 VDC & 280 VAC operating voltage ratings 12-24, 90-140 & 180-240 VAC/DC control input options available 8 Industry standard functions (A/At, B, C, D/Di, H/Ht, L/Li, Ac, Bw) IP20 Housing with unique integrated heat sink LED Input/Timer status indicator AC Output versions with Zero Voltage Turn-On for resistive loads and Random Turn-On for inductive loads UL Listed & cUL recognized UL & IEC General Use & Motor Control rated OUTPUT SPECIFICATIONS (A) Operating Voltage Range [Vrms] Maximum Load Current [Arms] Minimum Load Current [Arms] 1 Cycle Surge Current (50/60 Hz) [Apk] Maximum Surge Current (10ms) [Adc] Maximum On-State Voltage Drop @ Rated Current [Vpk] Maximum On-State Resistance (RDS-ON) [Ohms] Maximum Off-State Leakage Current @ Rated Voltage [mA] Transient Overvoltage [Vpk] Maximum Operating Voltage Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] Maximum I²t for Fusing (50/60Hz) [A² sec] Minimum Power Factor (with Maximum Load) UL 508 Resistive Load [A] (R) UL 508 Motor Controller [HP/FLA] (R) IEC 62314 LC-A [FLA] IEC 62314 LC-B [Kw] INPUT SPECIFICATIONS (A) Control Voltage Range [VAC/DC] Minimum Turn-On Voltage [VAC/DC] Must Turn-Off Voltage [VAC/DC] Minimum Input Current (for On-State) [mA ± 10%] (S) Maximum Input Current [mA ± 10%] (S) Maximum Turn-On Time Maximum Turn-Off Time DRTx24x06x DRTx06D06 24-280 VAC (47-440 Hz) 6 0.15 285/300 (N) NA ≤ 1.3 V NA 0.1 600 NA 500 410/375 0.5 6 1/3 / 3.6 6 0.250 1-60 VDC 6 2.5 mA NA 60 (P) ≤ 0.6 VDC 0.034 0.25 (Q) NA 1-48 VDC NA NA NA 6 NA NA NA DRTx24D06x DRTx24A06x 12-24 12 1 7.6/6.3 @ 12 VAC/DC 12.1/9.1 @ 24 VAC/DC 180-240 180 20 7.2/7.1 @ 180 VAC/DC 9.7/9.6 @ 240 VAC/DC DRTx24B06 DRTx24x06x GENERAL SPECIFICATIONS (A) 3750 Dielectric Strength, Input-Output to Baseplate (50/60Hz) [Vrms] Minimum Insulation Resistance (@ 500 VDC) Maximum Capacitance, Input/Output [pF] Ambient Operating Temperature Range [ºC] Ambient Storage Temperature Range [ºC] Status Indicator Display Air Gap (Spacing) ratings (Amps) Weight (typical) in either [oz] (gr) Housing Material Terminal Finish Humidity DRTx06D06 90-140 90 10 7.6/7.4 @ 90 VAC/DC 12.5/12.3 @ 140 VAC/DC Per function (T, U) Per function (T, U) 12-24 12 1 15.7/12.4 @ 12 VAC/DC 27.9/20.3 @24 VAC/DC DRTx06D06 109 10 -30 to 80 -40 to125 Green (V) 6 A / 11 mm or 4.5 A / No Spacing 1.76 (50) Self-extinguishing Sulfamate Nickel 5 to 85% 2500 TABLE 1. Timing Ranges (U) General Notes (N) Tj initial: 25ºC, tp: 8.3 ms (P) Output Voltage = 2.5 VDC (Q) Output Voltage = 150 V, Control Voltage = 0 V, TJ = 125ºC (R) For UL listing the housing can not exceed 130ºC or the load terminals exceed 105ºC (S) Input current varible ± 10% per function (T) Timing accuracy ± 10% (U) See TABLE 1 and TABLE 3 (V) See TABLE 2 America Tel.: +1 (877) 502 5500 [email protected] EMEA Identification Timing Range 1s 0.1 s to 1 s 10 s 1 s to 10 s 1 min 0.1 min to 1 min 10 min 1 min to 10 min 1h 0.1 h to 1 h 10 h 1 h to 10 h 100 h 10 h to 100 h Tel.: +44 (0) 1202 606030 [email protected] Asia Pacific Tel.: +86 (0) 21 6065 7725 [email protected] Part Number Nomenclature Operating Voltage 06: 60 VDC 24: 280 VAC Series DRT Required for valid part number For options only and not required for valid part number A 24 D Rated Load Current 06: 6 Amps 06 R Switching Type (24 suffix only) Blank: Zero Voltage Turn-On R: Random Turn-On Timing Function Control Voltage A: A/At, Delay on Make D: 12-24 VAC/DC AC B: Single Shot A: 180-240 VAC/DC Output C: Delay on Break B: 90-140 VAC/DC Only H: H/Ht, Interval L: L/Li, Repeat Cycle U: Multifunction (A/At, H/Ht, D/Di, B, C, Ac & Bw) TABLE 2. LED Status by Function Function A/At Delay On Make H/Ht Interval Control Voltage Y1 Repeat Cycle Output State LED Status Notes At function is identical to the A function except when Y1 is connected to A1 timing is paused. When Y1 is removed timing resumes until relay times out. To reset timer remove control power. Off Off Off Off On On Off Long Flashes On Timed Out On On Off Off Off Off On On On Long Flashes Timed Out On D/Di Timing Off Off Off Off A C At T On On/Off Long Flashes/Short Flashes L/Li Off Off Off H C C Ht T On On On/Off Long Flashes/Short Flashes L Single Shot C Delay On Break Ac Delay On Make / Delay On Break Bw Off Open Off Off Off On Open Off Off Short Flashes On Closed On On Long Flashes Closed Timed Out Off Open Off Off Off On Open Off Off Short Flashes On Closed Off On On On Open On On Long Flashes On Open Timed Out Off Short Flashes Off Open Off Off Off On Open Off Off Short Flashes On Closed On Off Long Flashes On Closed Timed Out On On On Open On On Long Flashes On Open Timed Out Off Short Flashes Off Open Off Off Off On Open Off Off Short Flashes On Closed On On Long Flashes On Closed Timed Out Off Short Flashes t3 L C D A1Y1 T T T T T Di T T T T T L To select between on time (Li) first or off time (L) first Y1 is connected A1. Default is On time (Li) first, for Off time (L) first connect Y1 to A1. Time delay is independent of each other. L C A1Y1 Toff Ton Toff Ton Toff Li Ton Y1 switch can be momentary or maintained to A1. To reset timer after relay has timed out Y1 has to be opened. Ton Toff C B Y1 T L Y1 switch to A1 must be momentary for timing to begin. If during timing Y1 is closed again the time delay is reset and will begin again once Y1 is removed. Once timed out timer is reset and ready for the next cycle. C To start Delay on Make (A) timing connect Y1 to A1 and maintain until LED is on Solid then to start Delay on Break (c) portion remove Y1 until relay times out. Removing Y1 During (A) portion or Connecting Y1 during (c) portion will reset time for that portion. Ac Y1 to A1 switch can be momentary or maintained. If maintained until relay has timed out removing it will start timing again. If momentary and timers has timed out reapplying Y1 will start timing again. Bw Complete specifications of these & other Crydom products available at: www.crydom.com Toff L Short Flashes On Off t2 T=t1+t2+t3 To select between on time (Di) first or off time (D) first Y1 is connected. Default is On time (Di) first, for Off time (D) first connect Y1. Equal On/Off time. L B t1 Y1 C Repeat Cycle t3 Ht function is identical to the H function except when Y1 is connected to A1 timing is paused. When Y1 is removed timing resumes until relay times out. To reset timer remove control power. L Off t2 T=t1+t2+t3 L C On t1 Y1 L Short Flashes Off C C Y1 T L C Y1 T T L C Y1 L T T Derating Curves Wiring Diagram (X) DRTxxxx06x Single or Multi Unit (W) A2 Multiple Units No Spacing Load Current (Amps) 6 A1 AC/DC CONTROL VOLTAGE (Input) Y1 5 4 3 2 1 0 0 10 20 30 40 50 60 70 80 Ambient Temperature (ºC) Block Diagram L1 (+ / ) Load AC/DC SUPPLY (Output) +1/L1 INPUT CONTROL +3/A1 d Load Loa (+ / ) T1 (Y) Y1 Status Indicator AC Output Only Mechanical Dimensions Tolerances: ±0.02 in / 0.5 mm All dimensions are in: inches [millimeters] TIMER 4/A2 DC Output Only 2.87 [73.0] 2/T1 (– / ) Load (Y) 0.44 [11.0] 2.02 [51.2] (– / ) TABLE 3. Timer Settings 3.44 [87.3] Identification INPUT STATUS Side View 5 6 7 4 5 6 7 8 9 10 4 5 6 7 4 10h100 h 10h100 h T off 4/A2 8 9 10 4WB8 S OLI D S TATE TI MER +3/A1 Fine Adjustment INPUT STATUS Delay on Make 5 6 7 4 10h100 h Single Shot Range 8 9 10 2.59 [65.9] 3.45 [87.7] 1 2 3 B 1.76 [44.8] 1s 10s 10m1 h 1m Interval +1/L1 Y1 A H 2/T1 DRTL06D06 3.27 [83.0] Fine Adjustment 1 2 3 10h100 h T on 8 9 10 1 2 3 AcBw 1s 10s 1s 10s 10m1 h 1m Repeat Cycle Function 10m1 h 1m L Range Di [A/At, H/Ht, D/Di, B, C, Ac, Bw] Front View AH BC Multifunction 10m1 h 1m U 1s 10s 1 2 3 Timing Function Fine Adjustment C (W) Minimum spacing between units is 11 mm (X) No grounding wire required. DC inductive loads must be diode suppressed (Y) Load is allowed in either terminal L1 or terminal T1 Delay on Break America Tel.: +1 (877) 502 5500 [email protected] EMEA Tel.: +44 (0) 1202 606030 [email protected] Asia Pacific Tel.: +86 (0) 21 6065 7725 [email protected] Custom Sensors & Technologies (CST) is a specialist in sensing, control and motion products. Crydom is the world leading brand of Solid State Relays, all manufactured and sold by Custom Sensors & Technologies (CST). Crydom product offer includes thousands of catalog off-the-shelf items, as well as custom-designed solid state relays and related products. Through its brands, BEI Kimco, BEI Sensors, BEI PSSC, Crouzet, Crydom, Kavlico, Newall and Systron Donner Inertial, CST offers customizable, reliable and efficient components for missioncritical systems in Aerospace & Defense, Transportation, Energy & Infrastructures, Commercial & Industrial OEMs, Medical, Food and Beverage and Building Equipment markets. At Crydom virtually everything is accomplished in-house to assure complete control over production, delivery and above all quality. With design, development, manufacturing and management personnel under one roof, we're geared for fast response to your requirements. Focused on premium value offers and committed to excellence, CST, with 4,400 employees worldwide and sales of $604M US in 2012, is the dependable and adaptable partner for the most demanding customers. Because of our dedication to quality, most Crydom products are approved by UL, CSA, VDE and TUV; and carry the CE mark signifying conformance with European directives. Also, our products comply with the latest legal environmental directives, like RoHS and China RoHS which always provide a competitive advantage to our customers. Our ongoing R&D programs have allowed us for years to be leaders in our industry. We are well known for constantly innovating new circuit and technology-related inventions to satisfy the switching needs of the most demanding applications. Our more than 40 years of experience providing top notch switching solutions and support make Crydom the indisputable global expert in solid state relay technology and preferred choice of companies all over the world. www.crydom.com www.cstsensors.com AMERICA Mexico Sales Support: Tel. : +52 (222) 409 7000 Fax : +52 (222) 409 7810 [email protected] Southern & Central Tel.: +55 (11) 2505 7500 Fax: +55 (11) 2505 7507 United Kingdom Sales Support Tel.: +44 (0) 1202 606030 Fax: +44 (0) 1202 606035 [email protected] Belgium Tel.: +32 (0) 2 460 4413 Fax: +32 (0) 2 461 2614 [email protected] Italy Tel.: +39 (0) 2 665 99 260 Fax: +39 (0) 2 665 99 268 [email protected] Technical Support [email protected] France Tel.: +33 (0) 810 123 963 Fax: +33 (0) 810 057 605 [email protected] Spain Tel.: +34 902 876 217 Fax: +34 902 876 219 [email protected] Germany Tel.: +49 (0) 180 3000 506 Fax: +49 (0) 180 3205 227 [email protected] Netherlands Tel.: +31 (0) 71 582 0068 Fax: +31 (0) 71 542 1648 [email protected] South Korea Tel.: +82 2 2629 8312 Fax: +82 2 2629 8310 [email protected] India Tel: +91 (80) 4113 2204 /05 Fax: +91 (80) 4113 2206 [email protected] United States & Canada Sales Support: Tel.: +1 (877) 502 5500 Fax: +1 (619) 210 1590 [email protected] Technical Support: Tel.: +1 (877) 702 7700 [email protected] EUROPE, MIDDLE EAST & AFRICA Austria & Switzerland Tel.: +44 (0) 1202 606030 Fax: +44 (0) 1202 606035 [email protected] ASIA PACIFIC China & Hong Kong Sales Support Tel.: +86 (0) 21 6065 7725 Fax: +86 (0) 21 6065 7749 [email protected] Technical Support [email protected] © 2013 Crydom Inc., All Rights Reserved. Specifications are subject to change without prior notice. Crydom and the Crydom logo are registered trademarks of Crydom Inc. 06/2013 Rev.060713 CAT/CR/SOL/EN Distributed by : Middle East, Africa & Other European Countries Tel. : +44 (0) 1202 606030 Fax: +44 (0) 1202 606035 [email protected] South East Asian & Pacific Countries Tel.: +886 2 8751 6388 ext.131 Fax: +886 2 2657 8725 [email protected] [email protected]