Crimp

Visual inspection of crimped connections
Insulation crimping
Wire crimping
B or F-Crimp
Contact twisted
Mismatch
Cross-section contact
Insulation
pierced
0.03 – 0.56 mm2
0.30 – 0.81 mm2
0.50 – 2.50 mm2
2.50 – 6.00 mm2
10°
(AWG 32 –20)
(AWG 22 –18)
0.25 +/- 0.15 mm
0.25 +/- 0.15 mm
0.40 +/- 0.20 mm
0.60 +/- 0.30 mm
Crimp flanks hit upon the
crimp contact base
Insert slope
(trumpet, bell mouth) must be visible!
Insulation is enclosed and fixed
The crimp flanks are closed
Note: In case of double crimping with differing
cross-sections and/or outer diameters, the smaller
cable is ALWAYS at the bottom!
Crimp too
high
Iso-crimp
overfilled
The twisting between the crimp zone and the contact
body must be a maximum of 10°!
Insulation
pierced
Position deviation
Insulation crimp
Crimp flank bent
Overlapping crimp
Mismatch
Cross-section contact
Individual strands are not enclosed in wire crimp –
insertion error
3° 5°
Crimp not closed
Insertion slope allowed
Crimp not filled
Crimp is overpressed
Crimp too low
Insulation
pierced
Crimp too high
Mismatch
Cracks in crimp base and severe burr formation
Dividing tab must be present! (max. 0.5 mm)
Insulation is enclosed and fixed
The crimp flanks “overlap”
Insulation damaged
Note: In case of double crimping with differing
cross-sections and/or outer diameters, the smaller
cable is ALWAYS at the bottom!
Crimp too
high
Crimp flanks are closed, support each other and are
uniformly curledt
Insulation
pierced
Asymmetry:
Max. material
thickness
Note: The same quality standards
apply for processing single wire seals
O or enclosed crimp
Iso-crimp is
“overpressed”
Insulation is enclosed and fixed.
The crimp flanks “overlap” one another
Iso-crimp too large
Insulation not enclosed
Position of the conductor in the crimp contact
Wire crimp is not closed and is overfilled
Crimp flanks curl unevenly
Mismatch: conductor cross-section contact
Mismatch: conductor
cross-section contact
Min. half
material thickness
Burr height
less than material
thickness
Conductor and insulation
must be visible!
Mismatch: conductor cross-section contact
No damage to the insulation permissible!
Pressure marks must be visible!
Contact is not
centred to the tool
Burr height
less than half material thickness
Functional zone of crimp contacts
Strands cut off or broken
Dividing tab too long and deformed
Contact functional zone damaged and deformed
End of the conductor must be visible!
Transition
damaged
Horizontal
± max. 3°
Axial shift
Cable inserted too short
Cable stripped too short
Strands are broken in
the wire crimp
The insulation is not stripped, but only inserted
in the insulation crimp zone and crimped.
The 30° deflection is applied without extraction force.
Extraction force in accordance with DIN 46 249 Part 1, SEN 245010 and EN 60352-2: 2006
Always perform extraction tests with insulation crimp open!
Individual wires break off irregularly beyond the insert slope = Test OK!
The cable must not fall out!
Individual wires break irregularly beyond the insert slope = Crimp too low!
Wire crimp without cable
Nominal conductor
cross-section
mm2
0.14
0.25
0.50
0.75
1.00
1.50
2.50
4.00
6.00
Extraction force (N) min.
Nominal size
(plug width)
2.8
2.8
2.8
2.8
2.8
4.8
4.8
4.8
4.8
4.8
6.3
6.3
6.3
6.3
6.3
6.3
6.3
Measuring crimping dimensions
Nominal size
2.8
Nominal size
4.8–9.5
20
40
60
70
80
20
40
80
120
160
200
250
350
500
9.5
9.5
For different conductor cross sections the lower extraction force is definitive
in each case.The extraction forces for the nominal size 2.8 arise from the
lower material thickness. Excerpt: DIN 46 249 Part 1.
Crimp too high!
Note: It is not sufficient to simply measure the conductor extraction
force, as it could have the same value for different compression levels!
Inspection of the crimp dimensions is required!
Extraction forces in accordance with
SEN 245010: The SEN 245010 standard
applies the most stringent QA requirements
for a crimp connection in international
comparison.
Cross-section
0,75–50 mm2
–95 mm2
over 95 mm2
Extraction for
150 N per mm2
120 N per mm2
100 N per mm2
Pull-Out Force of Crimp Connections
Testing has to be in accordance with Test 16d of IEC 60512.
Wire Gauge
mm
0.05
0.08
0.12
0.14
0.22
0.25
0.32
0.5
0.75
0.82
1.0
2
AWG
30
28
26
24
22
20
18
Pull-Out
Force
N
6
11
15
18
28
32
40
60
85
90
108
Wire Gauge
mm
1.3
1.5
2.1
2.5
3.3
4.0
5.3
6.0
8.4
10.0
2
AWG
16
14
12
10
8
Crimp height
Crimp dimensions and tolerances for the crimp
contact under test are to be taken from the relevant
processing specification!
Pull-Out
Force
N
135
150
200
230
275
310
355
360
370
380
IEC 60760, Section 17 and IEC 61210, table 9, show the same
values for validation of crimp connections.
Crimp width
Definition of insulation crimp height in accordance with DIN 41 611 Part 3
www.we-online.com
Note: Crimp contacts with damaged, bent and deformed
functional zones (snap locks etc.) must NOT be “straightened out” and must always be disposed of as “bad parts”!
Note:
Divider tab must be visible.
Length max. 0.5 mm
Cable stripped too long
Anvil
Measuring tip
Copyright by KabelForum –
All rights reserved!
www.kabelforum.de
DIE NECKARPRINZEN 999927. 0912.1‘.DD
Cable inserted too far
Vertical
± max. 5°